Controlled Electronic Management Systems S700PXV1-00 S700 multi smart card reader User Manual

Controlled Electronic Management Systems Ltd S700 multi smart card reader

Contents

User Manual

S700-IM-0088-1.72S700Installation Manual
NoticeThe information in this manual was current when published.  The manufacturer reserves the right to revise and improve its products.  All specifications are therefore subject to change without notice. CopyrightUnder copyright laws, the contents of this manual may not be copied, photocopied, reproduced, translated or reduced to any electronic medium or machine-readable form, in whole or in part, without prior written consent of © 2017 Tyco Security Products.  All Rights Reserved.TrademarksThe trademarks, logos, and service marks displayed on this document are registered in the United States (or other countries).  Any misuse of the trademarks is strictly prohibited and Tyco Security Products will aggressively enforce its intellectual property rights to the fullest extent of the law, including pursuit of criminal prosecution wherever necessary.  All trademarks not owned by Tyco Security Products are the property of their respective owners, and are used with permission or allowed under applicable laws.Product offerings and specifications are subject to change without notice.  Actual products may vary from photos.  Not all products include all features.  Availability varies by region.  Contact your sales representative for more information.  Licence informationYour use of this product is governed by certain terms and conditions.SupportIf you require technical assistance using CEM products, please contact the CEM Support team using the following telephone number:Telephone:+44(0)2890 456656Email: cem.support@tycoint.com• Please provide our support engineers with as much information as possible. This may include:• Site name• Product name and model• CEM software version• Description of the problemPublication DateFebruary 2017
S700 Installation Manual3Warning - For FCC Labelled S700TerminalsThis device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:(1) This device may not cause harmful interference, and(2) This device must accept an interference received, including interference that may cause undesired operation.This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. End users must follow the specific operating instructions for satisfying RF exposure compliance. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.Installation of this device shall be performed by a qualified person in accordance to all local regulations.This system must be installed within the protected premise in accordance with the National Electrical Code (NFPA70), and the local authorities having jurisdiction.Equipment changes or modifications without the approval of the party responsible for compliance could void the user's authority to operate the equipment and could create a hazardous condition.
S700-IM-0088-1.724
S700 Installation Manual5Chapter 1 Introduction  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Terminal user interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Using the reader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Presenting your card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Mode-specific response screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Checking the device status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15CEM S700 product codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Simplified AC2000 network topology  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Hardware installation process. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Chapter 2 Mounting the Terminal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Preparing for mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Chapter 3 Wiring the Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Cabling requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29The front board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30The input/output board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Wiring locks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Terminal with Request to Exit switch  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Configuration information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36Terminal with third-party OSDPv2 read head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Terminal with third-party Wiegand read head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Terminal with DIU 230 and third-party Wiegand read head . . . . . . . . . . . . . . . . . . . 39Configuration information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40S700e with S700s exit reader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42S700 with DIU 210 and S700s exit reader . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44S700 terminal with DIU 230  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46Tamper detection on reader inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Chapter 4 Reader Network Configuration . . . . . . . . . . . . . . . . . . . . . . 51Checking the network status of the S700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51Accessing the System Configuration Menu  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52Chapter 5 AC2000 Software Configuration . . . . . . . . . . . . . . . . . . . . . 55Reader addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55Adding the device to AC2000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Configuring devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
S700-IM-0088-1.726Next steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Chapter 6 The System Configuration Menu  . . . . . . . . . . . . . . . . . . . . 65Menu overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66Accessing the system configuration menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67Chapter 7 S700 Operational Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . 75Door mode timings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75Passenger Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79Interlock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82Equipment mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87Appendix 1  Updating Firmware  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91Appendix 2  Broadcast and Timezone Priorities  . . . . . . . . . . . . . . . . 95Appendix 3  Loading card definitions . . . . . . . . . . . . . . . . . . . . . . . . . 97
7Chapter 1 IntroductionThe S700 reader is an access terminal that provides secure door control and access monitoring at the controlled location.Used as part of the AC2000 system, the S700 reader controls access to restricted areas while also giving you a range of information tools and applications at the door.Figure 1 Photograph of the S700 terminalMulti-colour2.4 inch QVGALCD ScreenContextstatus lightSpeakersensitivefunction keysCapacitiveKeypadbar
S700-IM-0088-1.72CHAPTER  1 : Introduction81.1 Terminal user interfaceUse the S700 interface to display information and enable user interaction to perform specific functions. The screen displays the date, time, and the reader system address.Date and time: The date, time, and day are permanently displayed.Reader address: The reader address displays a unique five-digit number for each terminal on the AC2000 system.Figure 2 Terminal screen1.2 Using the readerThe S700 is always in one of three modes:•  Door mode•  Free access•  Locked out modeThe home screen displays one of the following modes:ReaderaddressDate and timedisplayInformationNetworkstatusdisplayindicator
S700 Installation Manual9Door stateFigure 3 Door modeDoor mode enables access for all valid cardholders after a card is swiped.Free access modeFigure 4 Free access modeFree access mode means that no card swipe is necessary to gain entry or exit because the door is unlocked.
S700-IM-0088-1.72CHAPTER  1 : Introduction10Locked out modeFigure 5 Locked out modeLocked out mode means that the door is locked and no access is permitted.1.3 Presenting your cardTo open a door, present your card to the access control card no more than 3 cm in front of the terminal. The multi-coloured LCD status of the terminal changes colour and the response screen displays.Note: The read range depends on the card technology that is used and the mounting arrangement of the reader; 3 cm is the minimum read range that can be expected for all cards.
S700 Installation Manual11A typical card swipe takes you through the following steps:1. Home screen: When the terminal is idle, the home screen is displayed.
S700-IM-0088-1.72CHAPTER  1 : Introduction122. Swipe Card: Swipe your card in close proximity to the terminal.3. Response screen: The response screen appears and access is granted.
S700 Installation Manual13Response ScreensThe response screens are described in Table 1: Response Screens for S700:UI Screen Message Description Multi-colour status lightAccess granted Access is granted GreenNot in system Access is not granted as card is not registered on the systemRedExpiring Card Access is granted and your card is set to expire within 14 daysGreenExpired card Access is not granted as your card has expiredRedLost or Stolen card Access is not granted as your card has been reported as lost or stolenRedTable 1: Response Screens for S700
S700-IM-0088-1.72CHAPTER  1 : Introduction14Wrong time Access is not granted as you are attempting to gain access outside the allocated timeAmberWrong zone Access is not granted as you do not have permission to enter this zoneAmberPIN Entry, time out Access is not granted as you have taken too long to enter your PINAmberCard passed back Access is not granted, you must comply with the anti-passback site access policyAmberUI Screen Message Description Multi-colour status lightTable 1: Response Screens for S700
S700 Installation Manual151.4 Mode-specific response screensTable 2: Mode-specific Response screens describes mode-specific response screens for the S700.1.5 Checking the device statusWhen you have installed the S700 reader, you can use the device to ensure that you have the correct version number, or confirm the part and serial numbers in the event of a support call.To check the product codes, part numbers, serial numbers, and build version of the S700 reader, complete the following step:•  Tap the left function key quickly at least three times. The S700: Device Status screen appears showing the device information, as shown in Figure 6.UI Screen Message DescriptionSelect access: Passenger or Staff Press Staff or Passenger for extended or timed access.The countdown timer starts when the door is opened when Passenger mode is selected.Swipe your card to prompt the user to extend or end the mode.Present Card In Passenger mode, the countdown timer has started.To set the time, select the device and use the Properties tab in the Devices application.Table 2: Mode-specific Response screens
S700-IM-0088-1.72CHAPTER  1 : Introduction16Figure 6 Device status information1.6 CEM S700 product codesContact CEM sales for further information.Important: The correct card definitions must be loaded onto the CEM Central Database Computer (CDC). See Loading card definitions on page 97. If you are using DESFire EV1 cards, which are sourced outside of CEM Systems, see the User Defined Keys manual to configure card keys.Using DESFire EV1There are two different types of DESFire EV1 card. CEM Systems can provide a personalised DESFire EV1 card with pre-defined attributes or non-personalised DESFire EV1 cards you can use. If using non-personalised cards, refer to the User Defined Keys manual to configure card keys.Card Technology EthernetHost Serial Host Exit FCC Approved ModelProx, iCLASS / PicoPass “Multi Tech”RDR/700/003 RDR/701/003 RDR/702/003 QABS700PXV1-00MiFareDESFire / Prox Duel-tech ReaderRDR/700/004 RDR/701/004 RDR/702/004 QABS700PXV1-00PicoPass RDR/700/006 RDR/701/006 RDR/702/006  QABS700V1-00DESFire RDR/700/007 RDR/701/007 RDR/702/007 QABS700V1-00iCLASS RDR/700/008 RDR/701/008 RDR/702/008 QABS700V1-00Table 3: List of CEM S700 product codes
S700 Installation Manual171.6.1 Terminal dimensions100142 Wall8.0o153048Note the angle of thereader to the wall, which is represented by the bluelineFigure 7 Illustration of S700, including dimensionsNote: All dimensions are in mm.1.6.2 Part ratingsThe S700 has been tested and operates within the following ranges, which are shown in Table 4: Part ratings.Part RatingSupply Voltage (Vdc) 9 to 28Power (W) Typical: 2.4 / Peak: 4.8Inputs Four analogue inputs - voltage suppliedComms to exit reader RS485 serial comms / Wiegand protocolComms to system host 10/100 Base-T TCP/IP CAT6 / RS485 serial commsDry contacts output 24 Vdc @ 2 AOperating temperature (°C)-20 to +70 (-4 °F to +158 °F)IP rating IP65Table 4: Part ratings
S700-IM-0088-1.72CHAPTER  1 : Introduction181.6.3 Onboard memoryThe system memory, 256 Mb RAM, 2 Gb NAND Flash, can hold the following:•  Up to 250,000 cardholder records - offline•  Up to 50,000 transactions - offline
S700 Installation Manual191.6.4 Terminal key component partsFigure 8 shows the key components of the S700 reader.Figure 8 Illustration of the key component partsBack casingI/O boardRibbon cableFront casingFront boardBackFrontOperational LED: This light flashes if the reader is operational and working correctlyRJ45 Ethernet socket
S700-IM-0088-1.72CHAPTER  1 : Introduction201.7 Simplified AC2000 network topologyFigure 9 Network typology provides you with a basic illustration of a typical AC2000 network, including S700 configurations.Figure 9 Network typology
S700 Installation Manual211.8 Hardware installation processMountingthe TerminalWiringthe TerminalNetworkcongurationRemove screws from the S700 front casingDisconnect ribbon cable from the back I/O boardIf required, remove the I/O board from the back casingNote: The speaker wires must be temporarily disconnectedDrill holes in the back casing for cable entry and mountingMount the terminal back casing to the tted back box or wallIf required, re-t the I/O board   Reconnect the speaker wires if they have been disconnectedConnect the input devices to the I/O board terminals   Connect the lock   If required, connect a third-party exit read head: Wiegand orOSDP   If required, connect an S700 exit reader and DIU   Connect 12 Vdc or 24 Vdc power to the I/O boardReconnect the ribbon cable to the I/O boardConnect either the Ethernet or RS485 network cableFit the security screws and side panelsCongure terminal network settingFigure 10 Hardware installation flow chart
S700-IM-0088-1.72CHAPTER  1 : Introduction22
23Chapter 2 Mounting the TerminalYou can mount the S700 terminal on the following standard electrical back boxes:•  UK single back box•  US single back box•  75mm VESA mount2.1 Preparing for mountingTake care with the internal components when you are disassembling the terminal.2.1.1 Recommended toolsThe recommended tools for mounting the terminal are as follows:•  2.5 mm flat-head screwdriver for input and output connections•  3 mm flat-head screwdriver for DC power connections•  Wire cutters and strippers•  Security hex screwdriver - size H20•  Pozi-head screwdriver - size PZ1Product CEM Product CodeSecurity screw driver handle HTO/000/001Security screw driver bit HTO/000/000Table 5: Security screwdriver product codes
S700-IM-0088-1.72CHAPTER  2 : Mounting the Terminal242.1.2 Opening the terminalImportant: Take care not to strain the ribbon cable connecting the two halves of the terminal.Figure 11 Opening the terminalTo open the terminal, complete the following steps:1. Set the terminal on a stable, level surface to reduce the risk of the front of the terminal falling when it is disconnected.2. Remove the four screws using a security hex screwdriver.3. Carefully lift the top casing away from the back of the terminal, pivoting as shown in Figure 11 Opening the terminal.4. Disconnect the ribbon cable from the I/O board before you start wiring.
S700 Installation Manual252.1.3 Mounting the terminal back casingTo access the mounting screw positions of the terminal, the I/O board must first be removed from the back box.Figure 12 Exploded view illustration of the back casing and I/O boardTo mount the terminal back casing, complete the following steps: 1. Remove the four screws and spacers using a Pozi-head screwdriver.2. Disconnect the two yellow internal speaker wires from connector J6 on the I/O board using a 2.5 mm screwdriver.3. Lift the I/O board away from the mountings.4. Drill the back outer casing as required for cable access and back box mounting. For more information, see Figure 12.Important: Ensure that the large case O ring and the 4 small O rings are in place.5. Fit the back casing to the back box.ABCDCDA - Back casingB - I/O boardC - SpacersD - Screws
S700-IM-0088-1.72CHAPTER  2 : Mounting the Terminal266. Re-attach the input/output Printed Circuit Board (PCB) to the back casing, ensuring you replace the spacers.7. Connect the internal speaker to the I/O board. The yellow speaker wires can be wired to the J6 speaker terminal in any order.Figure 13 Speaker wiring
S700 Installation Manual27Drilling the back casingUse the illustration in Figure 14 and the information in Table 6: S700 mounting descriptions to drill the back casing.Figure 14 S700 back casing drill hole dimensionsNote: All dimensions are in mm.Mounting hole DescriptionBUK single back boxCUS single back boxE75mm VESA mountFS610 mounting holesTable 6: S700 mounting descriptions
S700-IM-0088-1.72CHAPTER  2 : Mounting the Terminal28
29Chapter 3 Wiring the Terminal3.1 Cabling requirementsTable 7: Terminal installation cabling requirements outlines the cabling requirements for each of the connectors on the S700 terminal.3.1.1 Ethernet communicationsEthernet communications must be cabled and terminated for 10/100Base-T operation according to IN ANSI/TIA/EIA-568-A / TIA/EIA-568-B. Purpose Recommended Cable ConnectorEthernet comms CAT 6 RJ4512 Vdc or 24 Vdc power supplied separately Recommend using a CEM Door Interface Unit 210/230 16 AWG Screw TerminalInputs Belden 95XX (24 AWG shielded twisted pairs) or equivalent(XX = the number of pairs from 01 - 50)16 AWG Screw TerminalOutputs Belden 9462 (22 AWG shielding twisted pair) or equivalent 16 AWG Screw TerminalConnection with exit reader or DIU Belden 8723 (22 AWG shielded twisted 2-pair) or equivalent  16 AWG Screw TerminalWiegand Belden 9514 (7 x 22 AWG), Alpha 1229C(9 x 22 AWG) or equivalent 16 AWG Screw TerminalSerial Comms Belden 8723 (22 AWG shielded twisted 2-pair) or equivalent 16 AWG Screw TerminalTable 7: Terminal installation cabling requirementsType Cable Connector LocationHost CAT6 RJ45 Socket Terminal boardTable 8: Ethernet host
S700-IM-0088-1.72CHAPTER  3 : Wiring the Terminal30There must be enough spare cable left within the enclosure/back box to allow a service engineer to open the terminal case without straining the RJ45 connector. If the cable is subject to movement or vibration, stranded ethernet cable, and appropriate connectors, must be used.3.2 The front boardThe front PCB contains the main electronic components of the reader; it is also where ethernet communications must be connected. Figure 15 Illustration of the front boardTamper SwitchAntennaconnector(DO NOTDISTURB)Network linkspeed LEDEthernetactivity LEDRJ45connector Ribbonconnector tothe I/O boardOperationalLEDComponent DescriptionRJ45 connector Used for Ethernet communicationsRibbon connector Connects the front PCB to the I/O PCBAntenna Connector This is used for the PROX antenna. If fitted, DO NOT remove or tamper with the wires from this connectorOperational LED This light flashes if the reader is operational and working correctlyEthernet activity LED Flashing green indicates Ethernet activityNetwork link LED Orange indicates 100Base-T connection speed - unlit indicates 10Base-T connection speedTamper switch Used to trigger an alarm when the case is openedTable 9: Description of front board components
S700 Installation Manual313.3 The input/output boardThe input/output board provides the connections points for terminal power, inputs, outputs, third-party Wiegand read heads, communications with exit readers, and Door Interface Units (DIUs). Figure 16 Illustration of the Input/Output boardComponent DescriptionWiegand interface Interface for third-party exit heads using Wiegand protocolSupply Input and Speaker Connector12 Vdc or 24 Vdc power, either from a CEM Door Interface Unit (DIU) or an appropriate power source must be supplied to this connectorThis is also the audio output for the internal speaker.Output 0 Lock output, either 12 Vdc or 24 Vdc: voltage provided to relay common connection can be taken internally through the J9 Supply Input terminal or externallyRibbon connector Connects the I/O PCB to the front PCBOutput 1 Spare output. This output is also used when configuring the reader in interlock mode.Table 10: Description of I/O board componentsInputconnectorWiegand read headinterfaceComms to exit/DIU or Commsto HostSupply Inputand SpeakerOutput 0Ribbon connectorConnectorSafety GND Output 1Supply InputCurrent(spare) (lock)12 Vdc / 24 VdcSupply Input
S700-IM-0088-1.72CHAPTER  3 : Wiring the Terminal32Note:Supply Input Current:The power requirement of 2.5 A is based on the following:Host reader peak current @ 12 Vdc = 450 mAExit reader peak current @ 12 Vdc = 450 mAFully loaded DC output @ 12 Vdc = 1.6 A Total = 2.5 AThis does not include anything that is connected to the DC Output.DC Output Current:The maximum guaranteed current that can be supplied from the 12 Vdc output.Relay:Nominal voltage and current that can safely be applied to the relay.Comms to exit/DIU or Comms to HostIf this unit is configured as a serial host reader, ‘HOST’ can be used as an RS485 connection to the network.If serial communications to a CEM product, such as the S700 or DIU, is required, the ‘EXIT/DIU’ connection can be used as the connection to the DIU or exit reader.If the unit is configured as an exit reader ‘HOST’ can be used as a connection to the host.Input connectors Connection points for monitored inputs such as door position, lock sense and Request to Exit switches.Component DescriptionTable 10: Description of I/O board components
S700 Installation Manual333.4 Wiring locksThe terminal supports lock types rated up to 24 Vdc at 2 A max current.3.4.1 Wiring an internal voltage powered lockIt is possible to connect locks in a fail-safe or fail-secure configuration.Fail-safe lockIf the terminal loses power, a fail-safe lock opens, allowing free access. Therefore, a lock that is constantly powered, such as a maglock, must be used.Figure 17 Magnetic lockFail-secure lockIn fail-secure configuration, if the terminal loses power, the lock remains closed. A lock that requires power to open, such as a mortice lock, must be used.Figure 18 Mortice Lock3.4.2 Wiring an external voltage powered lockFigure 19 Illustration of wiring for lock with external power providedWhen you use an external voltage supply to power the lock the power supply ground should be connected to GND on the I/O board and not 0V.Note: All connections labelled 0V link to the same circuit.
S700-IM-0088-1.72CHAPTER  3 : Wiring the Terminal343.4.3 Inputs not in useSome inputs must be linked out when not in use, to allow the door control to operate and prevent alarms being generated on the AC2000 system.This is particularly important for DIU inputs.These inputs are outlined in the following list:•  Input 0 - door position sensor on terminal I/O board•  Fire input on a DIU•  Tamper input on a DIU•  Break Glass input on a Door Interface Unit
S700 Installation Manual353.5 Terminal with Request to Exit switchFigure 20 shows the wiring for a terminal with a Request to Exit switch.Figure 20 S700 master terminal with REX wiring diagram
S700-IM-0088-1.72CHAPTER  3 : Wiring the Terminal363.6 Configuration informationWiring an S700 terminal with a Request to Exit switch is a basic wiring configuration and is not recommended for use on high security doors.Input configurationTable 11: S700 and Request to Exit switch input configuration illustrates the configuration and operation of the inputs on the terminal when it is configured with a Request to Exit switch.Note: Wiring diagram is for the installation of the S700 terminal in Door Mode.Input number Input function Default input trigger state change0 Door position short => open1 Lock position short => open2 Request to exit switch open => momentary short => open3 Spare/Interlock short => openTable 11: S700 and Request to Exit switch input configuration
S700 Installation Manual373.7 Terminal with third-party OSDPv2 read headThe illustration in Figure 21 shows the wiring for a terminal with a third-party OSDPv2 read head.Figure 21 Wiring for terminal with third-party OSDPv2 read head
S700-IM-0088-1.72CHAPTER  3 : Wiring the Terminal383.8 Terminal with third-party Wiegand read headFigure 22 shows the wiring for a terminal with a third-party Wiegand read head.Figure 22 S700 master terminal with Wiegand read head wiring
S700 Installation Manual393.9 Terminal with DIU 230 and third-party Wiegand read headFigure 23 shows the wiring for a terminal with DIU 230 and third-party Wiegand read head.Figure 23 S700 terminal with DIU230 and Wiegand read head wiring
S700-IM-0088-1.72CHAPTER  3 : Wiring the Terminal40Note: To configure an exit reader as the master reader, see Configuring a Third-Party Reader as a Master on page 85.Important: For regulatory compliance, the drain wire must be disconnected at the reader-end of the cable.Table 12: Configuration and operation of terminal inputs contains the details for the configuration and operation of terminal inputs when configured with third-party Wiegand read heads.Table 12: Configuration and operation of terminal inputsImportant: If fire and break glass units are not required, the inputs must be connected to GND to ensure that the DIU functions normally. The tamper input must also be connected to the GND when it is not in use to prevent alarms being generated on AC2000.3.9.1 Software configuration for terminal with DIU 230 and third-party Wiegand read headTo configure AC2000 for use with the terminal, a DIU 230 and a third-party Wiegand read head, complete the following steps:1. Add the device in the Devices application as S700+DIU+Slave. For more information on the procedure for adding a device, see Adding the device to AC2000 on page 56.2. Enable the third-party read head. For more information on the procedure for enabling a third-party read head, see Configuring a third-party read head on page 57.3.10 Configuration informationThe S700 terminal facilitates the use of a third-party exit Wiegand head with three LEDs.Supported third-party read headsCEM support the use of HID R10 heads for reading Mifare and iClass cards.Input number Input location Input function Default input trigger state function0 DIU Door position short => open1 DIU Lock position short => open2 DIU Request to exit switch open => momentary short => open3 DIU Fire short => open4 DIU Breakglass short => open5 DIU Mains power fail Internally triggered6 DIU Battery low Internally triggered7 DIU DIU tamper short => open8 Master terminal Spare short => open9 Master terminal Spare short => openA Master terminal Spare short => openB Master terminal Spare/Interlock short => open
S700 Installation Manual41Typical Wiegand read head wiringFor specific read head wiring, consult the third-party manufacturer.Important: For regulatory compliance, the drain wire must be disconnected at the reader-end of the cable. Input configurationTable 15: S700 and third-party read head input configuration illustrates the configuration and operation of the inputs on the terminal when configured with a third-party Wiegand read head.Product CEM Product CodeHID iClass SE R10 SmartCard Reader HDS/053/010HID iClass SE R30 SmartCard Reader HDS/053/030HID iClass SE R40 SmartCard Reader HDS/053/040Table 13: Read head product codeI/O board connection Typical HID colourGND BlackSounder YellowGreen LED OrangeAmber LED Not fittedRed LED BrownData 1 WhiteData 0 GreenHead 12V RedTable 14: Typical Wiegand head wiringInput number Input function Default input trigger state change0 Door position short => open1 Lock position short => open2 Request to exit switch open => momentary short => open3 Spare / Interlock short => openTable 15: S700 and third-party read head input configuration
S700-IM-0088-1.72CHAPTER  3 : Wiring the Terminal423.11 S700e with S700s exit readerFigure 24 S700e with S700s exit reader
S700 Installation Manual433.11.1 Configuration informationUsing an S700 exit reader provides a higher level of security at the door than using a third-party read head.Input configurationThe S700 reader has four inputs and two relay outputs, which are spare in this configuration.Product CEM Product CodeS700 Card Reader (DESfire) RDR/702/007S700 Card Reader (iCLASS) RDR/702/008S700 Card Reader (Pico Pass) RDR/702/006Table 16: S700 product codesInput number Input location Input function Default input trigger state change0Master terminal Door position short => open1Master terminal Lock position short => open2Master terminal Request to exit switch open => momentary short => open3Master terminal Spare / Interlock short => open4 S700s exit Spare normally open5 S700s exit Spare normally open6 S700s exit Spare normally open7 S700s exit Spare normally openTable 17: S700e with S700s exit reader input configuration
S700-IM-0088-1.72CHAPTER  3 : Wiring the Terminal443.12 S700 with DIU 210 and S700s exit readerFigure 25 shows the wiring for an S700 master reader with a DIU 210.Figure 25 S700 master terminal with a DIU 210 wiring
S700 Installation Manual453.12.1 Configuration informationUsing a CEM DIU 210 provides the highest level of security at a door, removing power for the lock and input monitoring away from the door reader. Important: The DIU210 uses mains electricity and must only be installed by qualified personnel.Input configurationWhen a DIU210 is used with a terminal, the DIU controls the main CEM reserved inputs and the inputs on the readers become spare. The exception to this is input three on the terminal, input B in Table 7 on page 29, which maintains its status as being used for interlock mode.Important: If fire and break glass units are not required, the inputs must be connected to GND to ensure that the DIU functions normally. The tamper input must also be connected to GND when not in use to prevent alarms being generated on AC2000.Product CEM Product CodeDIU 200 (Compact board only DIU module) DIU/700/200DIU 210 Full DIU incl Enclosure/PSU (Does not include backup batteries) DIU/700/210Table 18: Door Interface Units product codeInput number Input location Input function Default input trigger state change0 DIU Door position short => open1 DIU Lock position short => open2 DIU Request to exit switch open => momentary short => open3 DIU Break glass short => open4 DIU Fire short => open5 DIU Mains power fail Internally triggered6 DIU Battery low Internally triggered7 DIU DIU tamper short => open8Master terminal Spare short => open9Master terminal Spare short => openAMaster terminal Spare short => openBMaster terminal Spare / Interlock short => openC Exit reader Spare normally openD Exit reader Spare normally openE Exit reader Spare normally openF Exit reader Spare normally openTable 19: S700 and DIU210 input configuration
S700-IM-0088-1.72CHAPTER  3 : Wiring the Terminal463.13 S700 terminal with DIU 230Figure 26 shows the wiring for the S700 terminal with DIU 230.Figure 26 S700 terminal with DIU 230 wiring
S700 Installation Manual473.13.1 Configuration informationUsing a CEM DIU230 also provides the highest level of security at a door, removing power for the lock and input monitoring away from the door reader. The DIU is a PoE+ device and does not require specialist electrical qualifications to install.Input configurationWhen a DIU230 is used with an S700 terminal, the DIU controls the main CEM reserved inputs and the inputs on the readers become spare. The exception to this is input three on the S700 terminal, input B in the Table 21: S700 and DIU230 input configuration, which maintains its status as being used for interlock mode..Important: If fire and break glass units are not required, the inputs must be connected to GND to ensure that the DIU functions normally. The tamper input must also be connected to GND when it is not in use to prevent alarms being generated on the AC2000 system.Product CEM Product CodeDIU 230 PoE+ (board only) DIU/700/230DIU 230 PoE+ (with enclosure) DIU/700/231Table 20: DIU230 product codesInput number Input location Input function Default input trigger state change0 DIU Door position short => open1 DIU Lock position short => open2 DIU Request to Exit switch open => momentary short => open3 DIU Fire short => open4 DIU Breakglass short => open5 DIU Mains power fail Internally triggered6 DIU Battery low Internally triggered7 DIU DIU tamper short => open8Master terminal Spare short => open9Master terminal Spare short => openAMaster terminal Spare short => openBMaster terminal Spare / Interlock short => openC Exit reader Spare normally openD Exit reader Spare normally openE Exit reader Spare normally openF Exit reader Spare normally openTable 21: S700 and DIU230 input configuration
S700-IM-0088-1.72483.14 Tamper detection on reader inputsTerminal inputs can be monitored for 4-state tampering, open, close, tamper short, and tamper cut. If an input is tampered with, an alarm is triggered in the AC2000 software. The alarm is a universal tamper alarm and does not distinguish between the four different states. To monitor inputs for tamper short and tamper cut, a resistor network must be installed on the input sensor wiring and the AC2000 software configured to monitor the input.3.14.1 Wiring the resistor networkFigure 27 Illustration of the resistor network for four state tamper detection on inputsImportant: It is imperative that the tamper resistor network is wired as close to the sensor as possible.3.14.2 Configuring software for tamper detectionTo configure software for tamper detection, complete the following steps:1. From the AC2000 Floatbar, click Device Configuration, and click Devices.2. Select the device on which inputs are to be configured for 4-state tamper detection.3. Select the Configuration tab.4. Select the Input Config tab.5. Select each input element to be configured for four state and tick the 4 state check box.6. Click Save.
S700 Installation Manual493.14.3 Re-assembling the terminalTo re-assemble the terminal, complete the following steps:1. Ensure that there is adequate cable length available to reach the connectors comfortably for each of the following:– 12 or 24 Vdc– CAT6 cable for communications– Output wiring for lock– Wiring for inputs, for example, door position sensor, lock senseImportant: To maintain the IP65 rating of the terminal, the cable access hole must be adequately sealed before completing the installation process.Note: Ensure the speaker is connected.2. Attach the front pane of the terminal using the ribbon connector.3. Attach the front of the terminal to the back casing and fix in places with the screws.4. Attach the protective side panels to the terminal.Note: If the terminal needs to be opened after installation, the side panels can be removed by inserting an access card into the slot under the centre of the panel and sliding along the length of the panel.
S700-IM-0088-1.72CHAPTER  3 : Wiring the Terminal50
51Chapter 4 Reader Network ConfigurationThe network settings are accessed using the installer configuration menu on the terminal.4.1 Checking the network status of the S700The network status is continuously displayed on the home screen of the reader.Figure 28 Checking the network statusNetwork status indicator
S700-IM-0088-1.72CHAPTER  4 : Reader Network Configuration52Each section of the status indicator represents a different aspect of the network connectivity. The presence or absence of a block indicates whether or not the connection is good.Figure 29 The network status indicator4.2 Accessing the System Configuration MenuTo access the configuration menu, complete the following steps:1. On the terminal keypad, quickly tap the right function key at least three times.2. When you are prompted to Enter Setup PIN, type the default code: 67670000.Figure 30 Accessing the configuration menuNote: After the AC2000 system setup is complete, the pass code is 6767XXXX, where XXXX is the code set by the system. The final four digits of this PIN are configurable for the terminal in the Devices application; for more information on configuring passcodes, see section Accessing the system configuration menu on page 67.The top block indicates that the terminal has received its onboard database of cardholders, timezones and so onThe centre block indicates that the terminal has received its configuration settings from the CDCThe bottom block indicates that the terminal is connected with the RTC The TCP/IP indicator shows Ethernet connectivity
S700 Installation Manual534.2.1 Setting the terminal IP address, gateway, and subnet maskTo set the IP address, gateway, and subnet mask of the terminal, complete the following steps:1. To access the Network Settings menu, press key 5.Figure 31 Configuring the terminal network settings2. Select Next to highlight the relevant field.3. Select Change to edit the selected field.4. Enter the IP Address, Subnet mask and Gateway settings using the keypad. Press the left function for a ‘.’5. To exit settings, press key 0 and select Save to save the new settings, or Quit to discard changes.
S700-IM-0088-1.7254
55Chapter 5 AC2000 Software ConfigurationThis section of the manual focuses on the initial addition and configuration of the device and input alarms. All other advanced configuration options are covered in the relevant function sections. The S700 terminal is added to the AC2000 system and configured using the Devices application. Note: This manual assumes access to the necessary AC2000 applications and should be performed by persons trained in its use.5.1 Reader addressingThe AC2000 system communicates with all devices on the access control network using the CEM reader addressing system. All devices are allocated a five-digit reader address, the address is displayed in the top right of the terminal display.Figure 32 Location of the reader address on the screenEach digit of the reader address signifies a position on the Devices hierarchy.Figure 33 Illustration describing AC2000 reader addressingReader addressRTC number ranges from 00 - DEDevice group number 0 - FDevice number 0 - FMaster / Exit0 = Master reader1 = Exit reader
S700-IM-0088-1.72CHAPTER  5 : AC2000 Software Configuration565.2 Adding the device to AC2000To add the address of a device to AC2000, complete the following steps:1. Log on to the AC2000 Floatbar, click Device Configuration, and click Devices.2. Select the controller and device group to which the device is being added.3. Click Add and select Add Device, or, right-click on the device group and select Add Device.The Devices application enters Add Mode. You can add a device.Figure 34 The Devices application in Add mode4. Use the drop-down Device Number list to select the device number.5. Into the Device Location field, enter the device location.Mixed case is available for the description of the device location.Note: It is advisable that you use a naming convention for the location of each device, especially if the AC2000 system is partitioned. This minimises the chance of calling two devices by the same name, for example, Partition 1: Server Room and Partition 2: Server Room.6. Select the Device Family drop-down list to choose the device family. For the S700, select 700E (Ethernet). 7. Select the Device Type drop-down list to choose the device type.1 For the S700, the device type is S700 + Slave.8. Select the Configuration Mode drop-down list to choose S700E + Slave.29. Select one of the following check boxes if the setting is relevant to your device setup:– Maintenance Mode– Restricted Mode– Soft Anti-Passback– Look at Camera1.If an exit or auxiliary device is added to the master reader, ensure to select the correct type, that is, an S700 device with an Exit Reader has a Device Type of S700 + Slave. This configures the Master device with an attached exit reader. Any exit reader added to a master appears as a child node in the Overview Pane of the master reader with which it is associated.2.The configuration mode contains default settings, however these can be user defined. for more information on creating a configuration mode, see the Setup Guide for the AC2000 system.
S700 Installation Manual5710. If an exit reader has been added by including it in the Device Type, enter a unique Slave Location to describe the location of the exit reader.11. Select the Settings tab. Enter the unique MAC Address or IP Address of the device into the relevant fields.The unique address of the device is found by navigating from the Configuration Menu to the Network Status menu on the S700 itself.12. Select the Offline Database drop-down list and select one of the following two options for the device:i. Card Numberii. Card Number, Timezone, Status, PIN13. Click Save. This adds the device to the AC2000 system.Note: Threat groups are only used if threat levels have been activated on AC2000. For further information, see the AC2000 Threat Levels manual.5.2.1 Configuring a third-party read headTo configure the Slave to be a third-party read head only, complete the following steps:Note: Following the instructions, Adding the device to AC2000 on page 56, a Slave is added to a master reader. The master reader configured the exit reader by default.1. Log on to the AC2000 Floatbar, click Device Configuration, and click Devices.Figure 35 Third-party read head configuration2. Select the device, with associated exit reader, to be configured.3. Select the Properties tab.Properties contains the most commonly used tabs. To access more specialised tabs, click Advanced View.4. Select Slave Settings from the list in the Properties pane.5. In the Slave Settings pane at the bottom of the interface, ensure the Slave reader enabled check box is clear.Configuration tabsProperties tabSelected device and associated exit readerExit reader settings
S700-IM-0088-1.72CHAPTER  5 : AC2000 Software Configuration586. Select Save.The Exit reader associated with the master device is now configured as a third-party read head and not an Exit reader.5.3 Configuring devicesUse the Devices application to configure the inputs that are used to trigger alarms or events in the AC2000 system.5.3.1 Adding an input alarmTo add an input alarm to a device, complete the following steps:1. Log on to the AC2000 Floatbar, click Device Configuration, and click Devices.2. Select the device to configure from the overview pane on the left of the screen.3. Select the Inputs tab on the main pane.4. Click Enable and the Alarm and Broadcast drop-down lists became active.Figure 36 Adding inputs dialog with example input 0 configuration5. From the Alarm drop-down list, select an alarm type.6. From the Broadcast drop-down list, select a broadcast type.7. Select the alarm Type from the drop-down list.8. In the Pulse Time box, set the time in seconds.9. Click Save.Alarm type
S700 Installation Manual595.3.2 Configuring 4-state tamper inputsTo configure the 4-state tamper inputs, complete the following steps:Figure 37 4-state tamper1. Log on to the AC2000 Floatbar, click Device Configuration, and click Devices.2. Select the device to configure from the overview pane on the left of the screen.3. Select the Properties tab, and click Advanced View.4. Select the Input Config tab.5. Select each input element to be configured and select the 4 state check box.6. Click Save.Note: The following instructions are only required if the settings need to be edited during or after terminal installation.5.3.3 Editing device propertiesTo edit the device properties, complete the following steps:1. Select the master device in the overview pane.2. Make the required changes and click Save.5.3.4 Editing a device inputTo edit a device input, complete the following steps:1. Select the Input and the Input State that is to be edited from the Device Inputs list.2. Click Save when changes have been completed.Note: Save is only displayed when a change has been made.
S700-IM-0088-1.72CHAPTER  5 : AC2000 Software Configuration605.3.5 Deleting a device inputTo delete a device input, complete the following steps:1. Select the input from the Device Inputs list.2. Click Delete.3. From the window that appears, click Delete to delete the device from the system or Cancel to cancel the process.Note: Care should be taken when deleting an input as no warning message appears.5.3.6 Input alarmsThe following input tables describe the set-up for each of the S700 configurations outlined in this manual, including the AC2000 alarms that must be selected for each sensor state where appropriate:Input table for S700 with REX and S700 with third-party read head:Input number Input function Sensor state AED alarm0 Door position Open Door forcedClosed Door closed1 Lock position Open Lock not engagedClosed Lock engaged2 Request to exit No default3 Spare / interlock No defaultTable 22: S700 and REX / Third-party read head input alarms
S700 Installation Manual61Input table for S700 with S700s exit readerInput table for S700 with DIU210 and S710s exit reader:Input number Input function Sensor state AED alarm0 Door position Open Door forcedClosed Door closed1 Lock position Open Lock not engagedClosed Lock engaged2 Request to exit No default3 Spare / interlock No default4 Spare No default5 Spare No default6 Spare No default7 Spare No defaultTable 23: S700 and S700s exit reader input alarmsInput number Input function Sensor state AED alarm0 Door position Open Door forcedClosed Door closed1 Lock position Open Lock not engagedClosed Lock engaged2 Request to exit No default3 Break glass Open BreakglassClosed Breakglass reset4 Fire Open Fire alarmClosed Fire alarm reset5 Mains power fail Open Mains power failClosed Mains OK6 Battery low Open DIU battery low7 DIU tamper switch Open DIU tamper8 Spare No default9 Spare No defaultA Spare No defaultB Spare / interlock No defaultC Spare No defaultD Spare No defaultE Spare No defaultF Spare No defaultTable 24: S700 and DIU210 input alarms
S700-IM-0088-1.72CHAPTER  5 : AC2000 Software Configuration62Input table for S700 with DIU230 and S700s exit readerInput table for four-state tamper configuration 5.4 Next stepsThe S700 terminal is fully installed. The remainder of the manual details how to perform more complex tasks with the terminal including:•  Using the system configuration menu to view maintenance information and perform terminal tests•  Configuring the terminal in additional modes such as Passenger Mode and Door Control.Input number Input function Sensor state AED alarm0 Door position Open Door forcedClosed Door closed1 Lock position Open Lock not engagedClosed Lock engaged2 Request to exit No default3 Fire Open Fire alarmClosed Fire alarm reset4 Break glass Open Break glassClosed Break glass reset5 Mains power fail Open Mains power failClosed Mains OK6 Battery low Open DIU battery low7 DIU tamper switch Open DIU tamper8 Spare No default9 Spare No defaultA Spare No defaultB Spare / interlock No defaultC Spare No defaultD Spare No defaultE Spare No defaultF Spare No defaultTable 25: S700e with DIU230 and S700s input alarmsInput number Input function Sensor state AED alarm0 Door position Open Door forcedClosed Door closedTamper Input Tamper1 Lock position Open Lock not engagedClosed Lock engagedTamper Input TamperTable 26: Input table for four-state tamper configuration
S700 Installation Manual63•  Upgrading terminal firmware•  Configuring device settings using the Device Settings Remote ApplicationImportant: Advanced configuration of the terminal must only be carried out by users that have completed CEM AC2000 installer training.
S700-IM-0088-1.7264
65Chapter 6 The System Configuration MenuThe S700 utilises a Graphical User Interface (GUI) to access terminal functionality. At the basic level, the screen is used to display messages regarding the current card swipe transaction. The more advanced options allow the user to access information and reports that are relevant to them. The S700 screen is a high quality, full colour, LCD screen. This is complimented by a capacitive touch keypad, which is highly responsive in multiple weather conditions. The reader interface provides access to a variety of tools, reports and information, such the as the following:•  Terminal configuration options•  Diagnostics and tests•  Software and hardware versions
S700-IM-0088-1.72CHAPTER  6 : The System Configuration Menu666.1 Menu overviewThe following image is an overview of the System Configuration Menu.Figure 38 Overview of the System Configuration Menu6.2 NavigationYou can access the menus on the terminal by touching the number on the keypad that corresponds to the menu designation.Figure 39 Expanding and closing reader menus
S700 Installation Manual676.3 Accessing the system configuration menuTo access the configuration menu, complete the following steps:1. On the keypad terminal, quickly tap the right function key at least three times.2. When prompted to enter a passcode, type 6767000.Note: See Accessing the System Configuration Menu on page 52 for more details on passcodes.Figure 40 Accessing the configuration menuConfiguring the passcodeTo configure the passcode, complete the following steps:Note: You can change the final four digits of the passcode, making it specific to a site or reader.1. Access the AC2000 system through the AC2000 workstation interface. enter your username and password.2. Log on to the AC2000 Floatbar and open the Devices application.3. In Devices, select the relevant reader.4. Select the Properties tab and click Advanced View.5. Select Other and click Diagnostic PIN from the options.Note: You must scroll down to locate the Diagnostic PIN option.
S700-IM-0088-1.72CHAPTER  6 : The System Configuration Menu68Figure 41 Diagnostic PIN6. Into the Current Value field, type your new PIN and click Close.7. To save the new PIN, click Save.The System Configuration Menu has a 10-option list, each of which contains specific terminal maintenance functions.6.3.1 Device settings menuImportant: You must have the following information before contacting CEM Support with any issues.Figure 42 The system configuration menuYou can access the following settings through the System Configuration Menu. The following settings are available:Quit Settings: key 0Use this setting to exit the System Configuration Menu and return to the terminal home screen.
S700 Installation Manual69Index: key 1Use the index to return to the System Configuration Menu from any point in the menu system.Network status: key 2Use the Network status information section to view details about terminal network settings.Figure 43 Network statusTable 27: Network status describes the fields in the Network status information window:Information DescriptionIP address The IP address of the terminalSubnet mask The subnet mask of the network hosting the terminalGateway The IP address of the gateway serverMAC address The MAC address of the terminalRun time Total terminal run time since the system was last resetCEM address The CEM reader address of the terminalRTC IP The IP address of the RTC controlled the terminalExit reader Indicates if an exit reader has been enabled in AC2000 and if it is operatingDIU Indicates if a Door Interface Unit has been enabled in AC2000 and if it is operatingOSDP head Indicates if an OSDP third-party head has been enabled in the AC2000 system, and, if it is operatingTable 27: Network status
S700-IM-0088-1.72CHAPTER  6 : The System Configuration Menu70Device Status: key 3Use the Device status information section to view details about all the hardware and software versions of the terminal.Figure 44 Device statusTable 28: Device settings describes the fields in the Device status information window:Database Status: key 4Use the Database status information section to view detailed information about the onboard card database.Figure 45 Database statusInformation DescriptionF/W Version Firmware versionF/W Date Date of firmware buildemWin Ver. Graphics library versionMCP Code Micro card processor part numberMD Code Main board part numberUnit Code Terminal part numberMCP s/n Micro card processor serial numberUnit s/n Terminal serial numberHW Build Terminal hardware buildTable 28: Device settings
S700 Installation Manual71Table 29: Database status describes the fields in the Database status information window:Network Settings: key 5The Network Settings section contains information the installer uses to configure the terminal network settings.Figure 46 Network SettingsSound Settings: key 6Use the Sound settings menu to change the volume of the internal speaker on the terminal.Information DescriptionCS Count The number of card records with which the local database was initializedCS Time This is the time the local card database was last initialisedDB Format This shows the database formatDB Count This is the current number of valid cards in the local databaseDB update This shows the time of the last database updateDB state This shows the database stateOff events This is the number of offline buffered event waiting to be uploaded to the serverTable 29: Database statusSubnet mask displays the address of the network to which the terminal is connectedGateway displays the IP address of the gateway server - where it is appropriateIP address displays the IP address assigned to the terminal
S700-IM-0088-1.72CHAPTER  6 : The System Configuration Menu72Figure 47 Sound SettingsSelecting this menu option twice can be used to change the setting on the exit reader.LCD Brightness: key 7Use the LCD Brightness menu to change the brightness of the terminal LCD screen to be adjusted.Selecting this menu option twice can be used to change the setting on the exit reader.Figure 48 LCD Brightness
S700 Installation Manual73Firmware Update: key 8The Firmware Update menu can be used to update the firmware if updates are available.A complete description of the firmware update process can be found in Updating Firmware on page 91.Figure 49 Firmware UpdateInputs Tests: key 9The S700 terminal has built-in tests that can be performed to check specific functionality.The Input tests screen displays the four terminal inputs states. When peripherals such as the exit reader or the Door Interface Unit are attached to the terminal, their inputs are also displayed on the screen.Figure 50 Inputs testThe Inputs test screen displays the following input states and inputs:• Input state: To test the inputs, change the state of the input, for example, open and close the door to test if the terminal is registered the state change.• Inputs: Each number correlates with a terminal input number as detailed in Wiring the Terminal on page 29. For example, input 0 is door position. The position of each input corresponds to an input state, which is defined on the left of the screen.Input state Inputs
S700-IM-0088-1.72CHAPTER  6 : The System Configuration Menu74Two-state input testWhen an input is wired in a 2-state open and closed configuration, only the Open and Short tests can be administered.These states are as follows:Open: The input is openShort: The input is closedFour-state input testWhen an input has been wired in a 4-state configuration, all four input state tests can be administered. For more information on configuration, see Configuration information on page 36.The following states are outlined as follows:Open: Indicates a tamper cut conditionOpen SW: The input is openClosed: The input is closedShort: Indicates a tamper short condition
75Chapter 7 S700 Operational ModesThe S700 intelligent access terminal can be configured to function in different modes other than the standard door mode described in the main section of the manual. The Door mode list in Devices is as follows:•  Door•  Turnstile•  Turnstile (Pulse)•  Passenger•  Equipment7.1 Door mode timingsDoor mode is the normal terminal configuration that is described in the main installation section of this manual. Use door mode to allow a terminal to control access to a door and monitor specific inputs associated with that door.When a valid card is presented at a terminal in door mode, a chain of events takes place. This chain is dictated by specific settings in the Devices application. These timings are configurable in the Devices application and also on the terminal itself.The chain of events is outlined in the following section, S700: Door mode timing on page 75.S700: Door mode timingThe following chart shows the timing sequence for a typical door mode.The door event starts on the left and move right as events and time occur.A valid card, remote Oneshot or REX (Request to Exit) input, typically starts the Lock Open Time sequence.
S700-IM-0088-1.72CHAPTER  7 : S700 Operational Modes76Table 30: Illustration of door timingsThe following steps outline the door open cycle:1. The valid card is swiped at the terminal and access is granted.2. Lock power is dropped for a period of time known as Lock open time: five second default. If the door is not opened by the end of this time, the lock re-engages.3. After the door is opened by the cardholder the lock power remains off for a period of time to prevent the lock re-engaging and closing the door before it is fully opened. This is the Lock open time 2. The default for this is one second.4. The door is closed. If the door remains open longer than the Door close after time, a door held alarm is generated on the terminal and the AC2000 system. The default is 15 seconds.Configuring the timings in the Devices applicationTo configure timings in the Devices application, complete the followings steps:1. Log on to the AC2000 Floatbar, click Device Configuration, and click Devices.2. Select the terminal you want to modify and select the Properties tab.Lock output Lock Open Time Lock Open Time Normal open Door close afterSounder warning, legal open time running outPre-alarmAllowing time to close Close timeDoor held alarm and alarm sounderAlarm TimeNotes If the door is not detected open before the Lock Open Time period expires, the lock is re-secured and the door mode returns to the idle stateThe door has been detected openIf the door is detected closed before the Door close after period, the Lock Open Time 2 is cancelled and the door mode returns to the idle stateThe pre-alarm starts the defined second before Door close after expiresClose Time is to allow an automatic door time to close when the cycle is complete; the pre-alarm continues during the Close Time
S700 Installation Manual773. From the main panel, select the timing you want to amend. This panel is shown in the following figure. Update the value you require in seconds.Figure 51 Updating the door cycle timingsDoor mode is the default terminal configuration that is described in the main installation section of this manual. Use door mode to allow a terminal to control access to a door and monitor specific inputs associated with that door.7.1.1 Multi-swipe accessThe S700 terminal can be configured to require swipes from up to five valid cards before granting access. Configure this using the Devices application. When this setting is configured, an initial valid swipe prompts a request for further valid swipes on the screen before opening the door. When all valid cards are swiped the terminal grants the user access.Figure 52 Multi-swipe request screen and access granted screenThe multi-card request swipe screen shows the number of valid cards required to grant access, up to a maximum of five cards. As each valid card is swiped, the S700 reader increments the card values shown in the card count display section and access is granted.Software configuration for multi-swipe accessTo activate multi-swipe access mode, complete the following steps:1. Log on to the AC2000 Floatbar, click Device Configuration, and click Devices.2. Select the terminal you want to configure.3. Select the Properties tab and click Advanced View.
S700-IM-0088-1.72CHAPTER  7 : S700 Operational Modes784. Select Other, and select Multi swipe mode.5. Select the Enable Options check box.Figure 53 Configuring multi-swipe access6. Use the drop-down Options lists to configure Multi swipe mode. In Figure 53 Configuring multi-swipe access the options are configured to 10 seconds and 2 swipes.
S700 Installation Manual797.2 Passenger ModePassenger mode enables a door to stay open for a longer period of time when swiped with a special usage card. This configuration is frequently used in airports to allow the free access of passengers through the door.When the reader is in this mode, it allows a normal card access through the door. However, a card that has been assigned Special Usage in the Personnel application is given the option to open the door as Staff or Passenger.Passenger mode keeps the door open for an extended period of time. The default time is 30 minutes.7.2.1 Configuring passenger mode in the softwareFor passenger mode to work correctly, the terminal must be configured in passenger mode and the cardholders using that terminal must be allocated special usage in the Personnel application. To activate special usage, select the Special Usage check box in the personnel record of the relevant cardholder.Card Swipe to End ModeFigure 54 Timing diagrams shows the timing sequences that take place when a card swipe is used to start and end the activation of third-party equipment. It also shows the options of either using or not using activations sensing.Figure 54 Timing diagrams Configuring the terminal as a passenger mode terminalTo configure the terminal as a passenger mode terminal, complete the following steps:1. Log on to the Floatbar, click Device Configuration, and click Devices.2. Select the terminal from the list and select the Properties tab.
S700-IM-0088-1.72CHAPTER  7 : S700 Operational Modes803. Select the terminal you want to configure.Figure 55 Configuring passenger mode4. Select Door Mode. You may have to scroll down to see this option.5. Use the Options drop-down list to select Passenger.6. Ensure the Enable Options check box is selected.7. Click Save on the toolbar of the Devices application.
S700 Installation Manual81Adding special access to a cardholderTo add special access to a cardholder, complete the following steps:1. Log on to the AC2000 Floatbar, click Enrolment, and click Personnel.2. Search for the cardholder to which the special access is to be applied.3. Select the Special Usage check box.4. Click Save.7.2.2 The passenger mode cycleTable 31: Illustration of passenger mode timing outlines the door open cycle. The passenger mode cycle is located within that cycle; it is only available to the system if Passenger mode is selected.Table 31: Illustration of passenger mode timingTo activate passenger mode on a terminal, complete the following steps:1. To give a cardholder the ability to use the door in Passenger mode, you must go to their Personnel record on the AC2000 system. When you locate their record using the Personnel application, select the Special Usage check box. When the check box is selected, Passenger mode is activated for those cardholders who swipe their access cards on this terminal.2. The terminal asks the cardholder if they require Passenger or Staff. Click the left function key for Passenger and the right function key for Staff. Selecting staff access causes the terminal to act as in Door Mode.Lock output Lock Open Time Lock Open Time Normal open Door close afterSounder warning, legal open time running outPre-alarmAllowing time to close Close timeDoor held alarm and alarm sounderAlarm TimeNotes If the door is not detected open before the Lock Open Time period expires, the lock is re-secured and the door mode returns to the idle stateThe door has been detected openIf the door is detected closed before the Door close after period, the Lock Open Time 2 is cancelled and the door mode returns to the idle stateThe pre-alarm starts the defined second before Door close after expiresClose Time is to allow an automatic door time to close when the cycle is complete; the pre-alarm continues during the Close Time
S700-IM-0088-1.72CHAPTER  7 : S700 Operational Modes823. The cardholder selects Passenger.Figure 56 Pressing the passenger operations button4. Lock power is dropped for a period of time known as Lock open time - this has a five second default time. If the door is not opened by the end of this time, the lock re-engages.5. After the door is opened, the lock power remains off for a period of time to prevent the lock re-engaging and closing the door before it is fully opened. This is the Lock open time 2. The default time for this is one second.6. After the previous two steps, the terminal enters Passenger Mode and the door can be held open for the period of time before an alarm sounds. The default time for this is three minutes. The period of time is defined using the Passenger time option in the Devices application.7. You can deactivate Passenger mode by swiping a valid Special Usage card and selecting Finish.7.2.3 Lobby modeLobby mode is a combination of passenger mode and interlocking terminals. Two terminals may be interlocked directly, or more than two terminals may be interlocked using a third-party logic controller or interposing relays.In lobby mode, as long as one door is open in passenger mode, interlocked doors are locked out to passengers but can be accessed with a valid card swipe from a special-usage cardholder. 7.3 InterlockInterlocking terminals are linked together so that only one terminal opens its door at any given time. This is achieved using a combination of wiring and software configuration. Interlocking between two terminals is achieved using a simple wiring configuration, however interlocking more than two terminals requires the use of a third-party logic controller or interposing relay system.
S700 Installation Manual837.3.1 Wiring two terminals for interlockFigure 57 Wiring two terminals for interlockSoftware configuration for interlockTo configure the software for interlock, complete the following steps:1. Log on to the AC2000 Floatbar, click Device Configuration, and click Devices.2. Select the terminal you want to configure and select the Properties tab.3. Select the Input Config panel and select Input 3, or with DIU select Input B.
S700-IM-0088-1.72CHAPTER  7 : S700 Operational Modes844. Clear the check box for Normal Input. Ensure the check box for Local output disabled is selected.Figure 58 Configuring input 3 for interlock5. Select the Common tab.6. Select Second swipe action.Figure 59 Configuring interlock functionality7. Select the No access on interlock and Make relay 0 active check boxes.8. Click Close and click Save on the toolbar of the Devices application.
S700 Installation Manual857.3.2 The interlock process in door modeInterlock is configured and works the same way in Passenger Mode and Door Mode, with only a slight change to end functionality.Figure 60 Interlock locked out display message in door modeInterlock configuration processThe following outlines the interlock configuration process:1. The spare outputs of terminals are linked to input 3 of the other interlocked terminals.2. When input 3 of the terminal is closed the terminal remains idle.3. When a valid card is swiped at an interlocked terminal, both outputs on the terminal change to the open state. This drops lock power at the swiped terminal and simultaneously opens input 3 on any interlocked terminals.4. Interlocked terminals lock down and display the lockdown message.5. The interlock function ends when the original swiped door is closed.7.3.3 The interlock process in passenger modeThe following outlines the interlock process in passenger mode:1. The spare outputs of terminals are linked to input 3 of the other interlocked terminals.2. When input 3 of the terminal is closed the terminal remains idle.3. When a valid card is swiped at an interlocked terminal, both outputs on the terminal change to the open state. This drops lock power at the swiped terminal and simultaneously opens input 3 on any interlocked terminals.4. The swiped terminal displays a countdown screen showing the time that the doors remain interlocked - that is, Passenger time in the Devices application.
S700-IM-0088-1.72CHAPTER  7 : S700 Operational Modes86Figure 61 Passenger mode countdown on the swiped terminal5. The interlocked terminals with input 3 now open locks down, preventing access until the swiped door is closed or the mode ended. Interlocked terminals displays a no-passenger access message. Normal card access is allowed.Important: If using a third-party logic controller to control multiple doors, the interlock principles remain the same. The spare output opens on a valid special usage swipe and input 3 is opened on interlock terminals to trigger lock down.
S700 Installation Manual877.4 Equipment modeA reader configured for Equipment mode must not be used to control a door lock.The S700 reader controller can be used to enable third-party external equipment by using a valid card swipe. The S700 enables the equipment; the actual control of the equipment is carried out by the equipment. An S700 reader and exit combination can be used to enable two independent pieces of equipment, for example, a generator or conveyor belt.7.4.1 Setting up Equipment modeThe following outlines the hardware and software configuration for the Equipment mode on the S700 reader and the AC2000 system.ConnectionsThe relay outputs on the S700 are used to enable equipment. The relays are low-voltage rated contacts, so appropriately rated, interposing relays must be used if you want to enable mains-powered equipment. The relays can either be configured as follows:•  To pulse at the start and pulse at the end of the required enable period•  To activate for the full duration of the required enable periodIf necessary, the inputs on the S700 can be used to monitor feedback of the activation state from the external equipment. Table 32: Equipment mode connections outlines the intended usage of the available inputs and outputs.ConfigurationThe configuration fields that are used by the Equipment enable mode are outlined in Table 33: Equipment enable Timers.Equipment set User interactionConnection on the Master Purpose CommentOne Master Relay 1 Enable equipment, controlLow voltage switch capable onlyOne Master Input 0 Equipment activated, sense Use volt-free contacts on third-party equipmentTwo Exit Relay 2 Enable equipment, Two Low-voltage switch capable onlyTwo Exit Input 1 Equipment activated, sense Use volt-free contacts on third-party equipmentTable 32: Equipment mode connectionsConfiguration item Abbreviation CommentLock open time LOT Mode start time, also stop relay time when LOT2 is zeroLock open time 2 LOT2  Non-pulsed relay and mode activation timeTable 33: Equipment enable Timers
S700-IM-0088-1.72CHAPTER  7 : S700 Operational Modes88Note: The feedback inputs, Input 0 and Input 1, in the table are optional. If they are not to be used, Input 0 and Input 1 must be disabled.Selecting Equipment mode in the Devices applicationTo select and enable Equipment mode for a device, complete the following steps:Figure 62 Equipment Enable in the Properties tab1. Launch the Devices application and select the device from the devices tree on the left.2. Select the Properties tab and click Advanced View.3. From the Configuration Properties pane, select Door mode.4. To select Equipment enable mode, use the Options drop-down list to select Equipment.5. In the Current Value field, set the value, and ensure the Enable Options check box is selected.6. Click Close and click Save.Occupancy swipe time OST Pulsed mode activation timeInput 0 enable IPE(0) Used to enable activation feedback sense for Master controllerInput 1 enable IPE(1) Used to enable activation feedback sense for Exit controllerConfiguration item Abbreviation CommentTable 33: Equipment enable Timers
S700 Installation Manual89Operating Equipment modeWhen Equipment mode has been selected for a device, it operates in the following sequence:1. When you perform a valid card swipe, two operations take place:i. The relay activates, enabling the third-party equipment. The equipment can be externally controlled.ii. The LCD on the S700 reader shows you that the equipment has been activated. In addition, an alarm is sent: Check-in enabled. There is also a Check-in Disabled and a Check-in Equipment Fail Alarm.Figure 63 S700 display: Equipment enabled2. When the equipment is externally activated, the following takes place:i. The equipment sends an output to signal that it is in use, causing the sense input to change state on the S700 reader.ii. The equipment must be activated within the configured value of Lock open time using the Properties tab in the Devices application.iii. The display on the S700 reader changes to the Equipment activated state.iv. Cost Charging is optional, and can be implemented.Note: When you implement this, you see a Card Valid Used or Card Valid Unused transaction. If a card is swiped but the feedback input is not activated, the report shows a Card Valid Unused transaction. If a card is swiped and the feedback input is activated, the report shows a Card Valid Used transaction. These transactions can be used for a Cost charging scenario.Note: As an example, Cost charging is implemented when the airport authority charges an airline company for the use of a baggage carousel. This action works when an event is sent to the AC2000 system and that can be used to start cost charging for the use of external, third-party equipment.v. While the S700 has the equipment enabled, the equipment can be deactivated and reactivated repeatedly.
S700-IM-0088-1.7290Figure 64 S700 display: Equipment activated3. When the further usage of the equipment is no longer required, you can do the following:i. Swipe a valid card to end the operation or allow the timers to run out.ii. The operator swipes a valid card; this deactivates the S700 relay output.iii. The AC2000 system sends an event; this stops cost charging for the use of external equipment.Figure 65 S700 display: Equipment stopped or Equipment fault4. If the equipment remains active for longer than the permitted period, the following happens:i. The S700 deactivates automatically; this deactivates the S700 relay output.ii. A Check-in Disabled alarm is sent. The AC2000 system stops cost charging for the use of external equipment.5. When the equipment has been stopped, the S700 returns to its idle state ready to start a new sequence.
S700 Installation Manual91Appendix 1 Updating FirmwareUpdating the S700 terminal firmware, device defrosting, is accomplished by using the AC2000 web pages to load the firmware pack on to the terminal and manually updating the terminal.Note: This process must only be carried out by an AC2000 administrator with the relevant permissions.Accessing the System Configuration MenuTo access the configuration menu, complete the following steps:1. On the terminal keypad, quickly tap the right function key at least three times.2. When prompted to enter passcode type 67670000.Figure 66 Accessing the configuration menuNote: After the AC2000 system setup is complete, the pass code is 67670000, where 0000 is the code set by the system. The final four digits of this PIN are configurable for the terminal in the Devices application. For more information on configuring the passcode, see section 6.3   Accessing the system configuration menu, on page 67.3. Select Device Status from the configuration menu by pressing the 3 key on the terminal keypad.The firmware version is displayed at the top of the screen. Check for the number beside the F/W Version heading.
S700-IM-0088-1.7292Checking the firmware version of the terminalTo check the status of your device quickly, complete the following step:•  Tap the left function key quickly at least three times. The appears with information on the firmware on the S700 terminal, as shown in Figure 66 Accessing the configuration menu.Figure 67 Device statusLoading the firmware onto the terminalTo load the firmware onto the terminal, complete the following steps:1. Obtain the firmware pack from CEM Systems and save to an accessible location on the network.2. Log into the web pages by opening a web browser.3. Into the browser, enter the Server IP Address, for example:https://192.168.1.10If the IP address has been changed from the default, enter the new IP address.4. Enter the username and password.5. Click Login.6. Select AC2000 WEB, select Reader Setup, and select Device Defrost.7. Click Choose file and select the S700 device image file (.z70) that is to be loaded.Note: This image is provided by CEM Support and must be saved in a secure location.8. Click Upload9. Click OK.A message appears similar to the following:Initiating defrost to device:XXXX with firmware file:<filename>
S700 Installation Manual93Updating the terminalWhen the terminal has received the firmware file, the reader address is displayed in the colour cyan instead of white.Figure 68 Cyan reader addressTo update the terminal, complete the following steps:1. Access the System Configuration Menu of the terminal.2. Press the number 8 on the keypad. This opens the Firmware Upgrade menu.3. Select Apply.Figure 69 Upgrading the terminal firmwareThe reader updates and reboots.Note: The reader goes offline for up to 30 seconds while the upgrade takes place.Reader address displayed in cyan
S700-IM-0088-1.7294
S700 Installation Manual95Appendix 2  Broadcast and Timezone PrioritiesA state machine is used to determine the priority that different events such as broadcast and timezone changes have on the terminal. The order is listed in descending priority, which is outlined in the following way:1. Broadcast open2. Interlock input3. Locked out TZ (timezone)4. Door override TZ (timezone)5. Card only TZ (timezone)6. PIN only TZ (timezone)ExampleIf there is an overlap between the Locked out TZ and the Card only TZ, the Locked out TZ will take priority due to it being higher up the list. When the Locked out TZ ends the Card only TZ takes over.Regardless of which state the terminal is in, a Broadcast open opens the door, overriding all other options.Note: For more information on timezones, see the AC2000 Setup Guide, and for information about broadcasts, see the AC2000 Operator Guide.
S700-IM-0088-1.7296
S700 Installation Manual97Appendix 3  Loading card definitionsIn order for AC2000 to correctly process the information encoded on the smart cards, the correct card definitions must be loaded onto the CDC. These are loaded using the AC2000 Web pages.1. Log into the AC2000 client software. This is done to allow access to the definition files on the CDC.2. Log into the web pages by opening a web browser.3. Enter the Server IP Address, for example:https://192.168.1.10If the IP address has been changed from the default, enter the new IP address.4. Enter the username and password.5. Click Login.6. Select AC2000 WEB, select System, and click Software Update.7. Click Browse and navigate to Z:\\card_defs\patches.8. Select the device image file (.cpio.bz) that is to be loaded. Figure 70 Card definition file list9. Click Upload10. Click OK.
CEM Systems195 Airport Road WestBelfastBT3 9EDUnited KingdomTel: +44(0)2890 456767