Honeywell 50025034 50025034 User Manual OneWireless XYR 6000 Transmitter

Honeywell International Inc. 50025034 OneWireless XYR 6000 Transmitter

Pro Install Guide

Download: Honeywell 50025034 50025034 User Manual OneWireless XYR 6000 Transmitter
Mirror Download [FCC.gov]Honeywell 50025034 50025034 User Manual OneWireless XYR 6000 Transmitter
Document ID996143
Application ID7MdAkboKwFsWZ0bBthGCIg==
Document DescriptionPro Install Guide
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize38.19kB (477375 bits)
Date Submitted2008-09-05 00:00:00
Date Available2008-09-05 00:00:00
Creation Date2008-08-27 08:25:00
Producing SoftwareAcrobat Distiller 8.1.0 (Windows)
Document Lastmod2008-08-27 08:25:49
Document TitleOneWireless XYR 6000 Transmitter
Document CreatorAcrobat PDFMaker 8.1 for Word
Document Author: 50021956

OneWireless XYR 6000 Transmitter
Professional Installation Guide
Document ID: 50021956
Document File: OneWireless XYR 6000 Pro-Install Guide Rev B.doc
Last Revision Date: 27 August 2008
Version: Rev B
Preliminary
This document and the information contained herein are confidential to and the property of Honeywell, Inc. and are made available
only to Honeywell employees for the sole purpose of conducting Honeywell's business. This document, and any copy thereof, and the
information contained herein shall be maintained in strictest confidence; shall not be copied in whole or in part except as authorized
by the employee's manager; and shall not be disclosed or distributed (a) to persons who are not Honeywell employees, or (b) to
Honeywell employees for whom such information is not necessary in connection with their assigned responsibilities. Upon request,
or when the employee in possession of this document no longer has need for this document for the authorized Honeywell purpose,
this document and any copies thereof shall be returned to the employee's manager. There shall be no exceptions to the terms and
conditions set forth herein except as authorized in writing by the responsible Honeywell Vice President.
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 1 of 28
Date
15 October 2007
18 August 2008
Revision
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Reason
Document Release
a) Added FCC and IC Compliance Statement information in
Section 3
b) Added IC Compliance Statement and regulations in Section
17
c) Added label information in Section 15
d) Moved Abbreviations and Definitions to Section 1
e) Added Intended Country usage in Section 6
f) Add grounding wire information in Section 10
g) Removed IC ICES-001 statements
h) Added 4 dBi Integral Antenna
i) Added MSG information for FHSS/DSSS radios to Section 5
j) Split Table 10 into two parts (Table 11 and Table 12) so as to
better show differences between FHSS and DSSS EIRP levels
k) Split Table 11 into two parts (Table 13 and Table 14) so as to
better show differences between FHSS and DSSS power
levels
l) Added cable lengths and cable losses to Table 11 and Table
12
m) Added restrictions for units installed in France to Table 11
and Table 12
n) Added and changed notes for Table 11 and Table 12
o) Added Multiple DI and Temperature DI to Table 1
p) Added note in French to Section 3.1
q) Added Table 7 for XYR 6000 with N connectors
r) Added information for installation in Thailand
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 2 of 28
TABLE OF CONTENTS
TABLE OF CONTENTS............................................................................................................................................................. 3
LIST OF FIGURES ..................................................................................................................................................................... 5
LIST OF TABLES ....................................................................................................................................................................... 5
DESIGNATION, SCOPE AND PREFACE....................................................................................................................... 6
1.1
1.2
1.3
1.4
1.5
DESIGNATION.................................................................................................................................................................. 6
SCOPE ............................................................................................................................................................................. 6
PREFACE ......................................................................................................................................................................... 6
SITE SURVEY................................................................................................................................................................... 6
ABBREVIATIONS & DEFINITIONS..................................................................................................................................... 8
FEDERAL COMMUNICATION COMMISSION (FCC) ............................................................................................... 9
2.1
FCC COMPLIANCE STATEMENTS .................................................................................................................................... 9
INDUSTRY CANADA (IC) ................................................................................................................................................ 9
3.1
IC COMPLIANCE STATEMENTS ........................................................................................................................................ 9
RF SAFETY STATEMENT: .............................................................................................................................................. 9
FCC AND INDUSTRY CANADA (IC) IDENTIFICATION NUMBERS: .................................................................. 10
5.1
5.2
FHSS RADIOS ............................................................................................................................................................... 10
DSSS RADIOS ............................................................................................................................................................... 10
INTENDED COUNTRY USAGE..................................................................................................................................... 11
6.1
6.2
6.3
NORTH AMERICA..................................................................................................................................................... 11
ASIA PACIFIC ............................................................................................................................................................ 11
EUROPEAN UNION................................................................................................................................................... 11
XYR 6000 TRANSMITTER GENERAL DESCRIPTION ............................................................................................ 12
7.1
7.2
INTENDED USE .............................................................................................................................................................. 12
XYR 6000 TRANSMITTER DIAGRAMS ........................................................................................................................... 12
PRODUCT SPECIFICATIONS ....................................................................................................................................... 13
8.1
8.2
8.3
8.4
8.5
8.6
FREQUENCY HOPPING SPREAD SPECTRUM (FHSS) RADIO, 2.4 GHZ ............................................................................ 13
DIRECT SEQUENCE SPREAD SPECTRUM (DSSS) RADIO, 2.4 GHZ ................................................................................. 13
XYR 6000 TRANSMITTER USER ENVIRONMENT ........................................................................................................... 14
XYR 6000 INSTRUMENT POWER SPECIFICATIONS ........................................................................................................ 14
WEIGHT ........................................................................................................................................................................ 14
DIMENSIONS.................................................................................................................................................................. 15
CABLES.............................................................................................................................................................................. 16
9.1
9.2
9.3
XYR 6000 TRANSMITTER WITH RP-TNC CONNECTORS ANTENNA OR LIGHTNING ARRESTOR CABLES ....................... 16
XYR 6000 TRANSMITTER WITH N CONNECTORS ANTENNA OR LIGHTNING ARRESTOR CABLES .................................. 16
LIGHTNING ARRESTOR TO ANTENNA CABLES ............................................................................................................... 16
10
ANTENNA LIGHTNING ARRESTORS .................................................................................................................... 17
11
APPROVED ANTENNA TYPES/GAINS ................................................................................................................... 17
12
EQUIVALENT ISOTROPICALLY RADIATED POWER (EIRP) ......................................................................... 18
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 3 of 28
13
EIRP LIMITS................................................................................................................................................................. 18
14
SETTING TX POWER ................................................................................................................................................. 23
15
AGENCY LABEL INFORMATION ........................................................................................................................... 24
15.1 EXTERNAL FCC/IC LABELS .......................................................................................................................................... 24
15.1.1 50016195-001 – Transmitters with FHSS Radios................................................................................................ 24
15.1.2 50016195-002 – Transmitters with DSSS Radios ................................................................................................ 24
15.2 INTERNAL FCC/IC LABELS ........................................................................................................................................... 24
16
RF SAFETY, MAXIMUM PERMISSIBLE EXPOSURE (MPE) STATEMENT................................................... 25
17
AGENCY COMPLIANCE............................................................................................................................................ 26
17.1 RADIO AND EMC CERTIFICATIONS ............................................................................................................................... 26
17.1.1 Federal Communication Commission (FCC)....................................................................................................... 26
17.1.2 Industry Canada (IC) ........................................................................................................................................... 26
17.1.3 European Telecommunications Standards Institute (ETSI) ................................................................................. 26
17.1.4 Australian communications and media authority (ACMA) .................................................................................. 26
17.1.5 Thailand National Telecommunications Commission (TNTC) ............................................................................ 26
17.2 PRODUCT SAFETY AGENCY CERTIFICATIONS ................................................................................................................ 27
17.2.1 Canadian Standards Association (CSA)............................................................................................................... 27
17.2.2 Factory Mutual (FM) ........................................................................................................................................... 27
17.2.3 European ATEX Certification (ATEX) ................................................................................................................. 28
17.3 EUROPEAN UNION CERTIFICATION (CE-MARK) ............................................................................................................ 28
18
REFERENCE DOCUMENTS ...................................................................................................................................... 28
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 4 of 28
LIST OF FIGURES
Figure 1 – XYR 6000 Transmitters showing Right-angle Integral Antenna (left), Straight Integral Antenna
(center) and Remote Antenna connector (right) options__________________________________________ 12
Figure 2 – Dimensions of the XYR 6000 Transmitter with Right-angle -2 dBi Integral Antenna __________ 15
LIST OF TABLES
Table 1 – Model Key Numbers .....................................................................................................................................6
Table 2 –Table of Abbreviations and Definitions ..........................................................................................................8
Table 3 – Specifications of FHSS Radio Module in XYR 6000 Transmitter ...............................................................13
Table 4 – Specifications of DSSS Radio Module in XYR 6000 Transmitter...............................................................13
Table 5 – User Environment Specifications for XYR 6000 Transmitter......................................................................14
Table 6 – Transmitter to Antenna or Lightning Arrestor Cable Specifications for XYR 6000 with RP-TNC connectors
....................................................................................................................................................................................16
Table 7 – Transmitter to Antenna or Lightning Arrestor Cable Specifications for XYR 6000 with N connectors.......16
Table 8 – Lightning Arrestor to Antenna Cable Specifications ...................................................................................16
Table 9 – Lightning Arrestor Specifications for Remote Antenna(s) ..........................................................................17
Table 10 – Approved Antenna Types/Gains...............................................................................................................17
Table 11 – Maximum EIRP Limits for FHSS Radios ..................................................................................................18
Table 12 – Maximum EIRP Limits for DSSS Radios ..................................................................................................19
Table 13 – FHSS Transmit Power Settings for the antennas and cable lengths specified above for FCC, IC, ETSI,
ACMA and TNTC approvals .......................................................................................................................................21
Table 14 – DSSS Transmit Power Settings for the antennas and cable lengths specified above for FCC, IC, ETSI,
ACMA and TNTC approvals .......................................................................................................................................22
Table 15 – Reference documents..............................................................................................................................28
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 5 of 28
1
1.1
DESIGNATION, SCOPE AND PREFACE
Designation
This document is valid for the following XYR 6000 Model Key numbers:
Table 1 – Model Key Numbers
Model Key Number
STTW400
STTW8
Description
Temperature Transmitter (remote sensors)
Temperature Transmitter with integral probe
STTW401
Temperature/Digital Inputs
STTW500
Multiple Digital Inputs
STIW600
High Level Analog Input Transmitter
STGW9
Gauge and Absolute Pressure Transmitters
STDW9
Differential Pressure Transmitters
CETW6000M
Corrosion Transmitter
Model Selection Guide Table IV selections XF, EF or JF mean that the XYR 6000 has a FHSS radio.
Model Selection Guide Table IV selections XD, ED or JD mean that the XYR 6000 has a DSSS radio.
For the complete model number information, please see the appropriate XYR 6000 Transmitter Model Selection Guides.
1.2
Scope
This document outlines professional installation requirements for the Honeywell XYR 6000 Transmitter for the Honeywell
OneWireless Network. Professional installation is required to comply with certification agency and legal requirements. This
document must be adhered to for all installations of the Honeywell OneWireless XYR 6000 Transmitters.
1.3
Preface
This manual covers professional installation of the Honeywell OneWireless XYR 6000 Transmitters. See the Getting Started
with Honeywell OneWireless, Honeywell OneWireless Planning Guide and Honeywell OneWireless XYR 6000 User’s
Guides for general information on overall system implementation, configuration, and management of these devices.
Since these devices may require that the Transmit (TX) power limit settings for the higher gain antennas be manually adjusted,
then the XYR 6000 is classified by the FCC as a device that must be professionally installed. To be in compliance with FCC
requirements, the radio must be installed with one of approved antennas listed in this document.
1.4
Site Survey
It is assumed for the purposes of this document that a site survey has been performed and that the antenna types, cable lengths
and lightning surge arrestors were appropriately selected per the results of that survey. Any changes to these items as a result
of the actual installation of the XYR 6000 transmitters into the site may require that the TX power setting of the radio board
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 6 of 28
needs to be adjusted from the factory setting in order to maintain agency approvals. See Sections 13 and 14 for more
information.
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 7 of 28
1.5
Abbreviations & Definitions
The term Honeywell XYR 6000 Transmitter will be used to describe the composite unit which includes the Honeywell FHSS
or DSSS RF Module and all subassemblies housed within the XYR 6000 Transmitter enclosure.
Table 2 –Table of Abbreviations and Definitions
ACMA
AD
ATEX
AWG
Co-located
COTS
CSA
DCS
DSSS
EMC
ETSI
EU
FCC
FHSS
FM
FSK
GFSK
HLAI
IC
IEEE
IR
IrDA
LUI
MPE
MSG
MTBF
NA
NEMA
PCB
PCI
OQPSK
RAM
RJ-45
RPN
SQA
TNTC
TX
Wi-Fi
WNSIA
Australian Communications and Media Authority
Authentication Device
Potentially Explosive Atmospheres Directive
American Wire Gauge
Two or more radios transmitting simultaneously and with less than 20cm
of separation distance.
Commercial Off-The-Shelf
Canadian Standards Association
Distributed Control System
Direct Sequence Spread Spectrum
Electromagnetic Compatibility
European Telecommunications Standards Institute
European Union
Federal Communications Committee
Frequency-Hopping Spread Spectrum
Factory Mutual
Frequency Shift Keying
Gaussian Frequency Shift Keying
High Level Analog Input
Industry Canada
Institute of Electrical and Electronics Engineers
Infrared
Infrared Data Association
Local User Interface
Maximum Permissible Exposure
Honeywell Model Selection Guide
Mean Time Between Failures
North America – United States of America and Canada
National Electrical Manufacturers Association
Printed Circuit Board
Peripheral Components Interconnect
Offset Quadrature Phase-Shift Keying
Random Access Memory
Registered Jack-45
Reverse Polarity N-type
Supplier Quality Assurance
Thailand National Telecommunications Commission
Transmit
Wireless Local Area Network based on IEEE 802.11 Specifications
Wireless Network for Secure Industrial Application
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 8 of 28
2
2.1
3.1
FEDERAL COMMUNICATION COMMISSION (FCC)
FCC Compliance Statements
¾
This device complies with Part 15 of FCC Rules and Regulations. Operation is subject to the following two
conditions: (1) This device may not cause harmful interference and (2) this device must accept any interference
received, including interference that may cause undesired operation.
¾
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses, and can radiate radiofrequency energy and, if not
installed and used in accordance with these instructions, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which
case the user will be required to correct the interference at his own expense.
¾
Intentional or unintentional changes or modifications must not be made to the XYR 6000 unless under the
express consent of the party responsible for compliance. Any such modifications could void the user’s authority
to operate the equipment and will void the manufacturer’s warranty.
INDUSTRY CANADA (IC)
IC Compliance Statements
¾
To reduce potential radio interference to other users, the antenna type and its gain should be so chosen that the
equivalent isotropic radiated power (EIRP) is not more than that permitted for successful communication.
¾
Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this
device must accept any interference, including interference that may cause undesired operation of the device.
¾
This Class A digital apparatus complies with Canadian ICES-003.
¾
French: Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
RF Safety Statement:
To comply with FCC’s and Industry Canada’s RF exposure requirements, the following antenna installation and
device operating configurations must be satisfied.
¾
Remote Point-to-Multi-Point antenna(s) for this unit must be fixed and mounted on outdoor permanent
structures with a separation distance between the antenna(s) of greater than 20cm and a separation distance of at
least 20cm from all persons.
¾
Furthermore, when using integral antenna(s) the XYR 6000 unit must not be co-located with any other antenna or
transmitter device and have a separation distance of at least 20cm from all persons.
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 9 of 28
5
5.1
FCC and Industry Canada (IC) Identification Numbers:
FHSS Radios
•
Honeywell XYR 6000 Transmitter FHSS Radio Module Identification
Honeywell Identification for Class 1 Div 2 RF Modules: 50016517-001
Honeywell Identification for Intrinsically Safe RF Modules: 50025132-001
Honeywell XYR 6000 Transmitter FHSS Radio Limited Modular Approval
Federal Communication Commission Identification for Class 1 Div 2 RF Modules: S5750016517
Federal Communication Commission Identification for Intrinsically Safe RF Modules: S5750016517
Honeywell XYR 6000 Transmitter FHSS Radio Limited Modular Approval
Industry Canada Identification for Class 1 Div 2 RF Modules: 573I-50016517
Industry Canada Identification for Intrinsically Safe RF Modules: 573I-50016517
•
•
5.2
DSSS Radios
•
Honeywell XYR 6000 Transmitter DSSS Radio Module Identification
Honeywell Identification for Intrinsically Safe RF Modules: 50025034-001
Honeywell XYR 6000 Transmitter DSSS Radio Limited Modular Approval
Federal Communication Commission Identification for Intrinsically Safe RF Modules: S5750025034
Industry Canada Identification for Intrinsically Safe RF Modules: 573I-50025034
•
This information is shown on the label attached to each RF Module.
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 10 of 28
6
INTENDED COUNTRY USAGE
6.1
NORTH AMERICA
Country
UNITED STATES
CANADA
6.2
ISO 3166 2 letter code
US
CA
ASIA PACIFIC
Country
AUSTRALIA
THAILAND
NEW ZEALAND
6.3
ISO 3166 2 letter code
AU
TH
NZ
EUROPEAN UNION
Country
Austria
Belgium
Bulgaria
Cyprus
Czech Republic
Denmark
Estonia
Finland
France
Germany
Greece
Hungary
Iceland
Ireland
Italy
ISO 3166
2 letter code
AT
BE
BG
CY
CZ
DK
EE
FI
FR
DE
GR
HU
IS
IE
IT
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Country
Latvia
Liechtenstein
Lithuania
Malta
Netherlands
Norway
Poland
Portugal
Romania
Slovakia
Slovenia
Spain
Sweden
Switzerland
United Kingdom
Honeywell Proprietary
50021956
ISO 3166
2 letter code
LV
LI
LT
MT
NL
NO
PL
PT
RO
SK
SI
ES
SE
CH
BG
Rev B
27 August 2008
Page 11 of 28
7
XYR 6000 TRANSMITTER GENERAL DESCRIPTION
7.1
Intended Use
The XYR 6000 Transmitter is a key component of the Honeywell Wireless Network for Secure Industrial Application
(WNSIA). These transmitters are available for various sensor types including Digital Inputs, Temperature, High Level Analog
Inputs, Pressure and Corrosion. The XYR 6000 Transmitter uses a low-powered FHSS or DSSS 2.4 GHz radio to
communicate with Multinode and Gateway devices that are connected to a wired DCS network.
7.2
XYR 6000 Transmitter Diagrams
Figure 1 shows unit-level drawings of the XYR 6000 Transmitter antenna options.
Figure 1 – XYR 6000 Transmitters showing Right-angle Integral Antenna (left), Straight Integral Antenna
(center) and Remote Antenna connector (right) options
The XYR 6000 Transmitter is available with either an integral antenna or with a remote antenna. Remote antennas are attached
via cables to a connector on the XYR 6000. The integral antennas and/or the remote antenna connectors are not replaceable or
changeable in the field.
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 12 of 28
8
8.1
PRODUCT SPECIFICATIONS
Frequency Hopping Spread Spectrum (FHSS) Radio, 2.4 GHz
Warning! The XYR 6000 Transmitter must be Professionally Installed in accordance with the requirements specified in this
document. See Section 10, for professional installation maximum TX power setting requirements. Only the specified TX
power settings, antenna types and gains and cable lengths (attenuation) as outlined in this document are valid for XYR 6000
Transmitter installations.
Table 3 – Specifications of FHSS Radio Module in XYR 6000 Transmitter
Item
Specification
Wireless Standard
Frequency Hopping Spread Spectrum (FHSS), 2.4 GHz
Data Rates and Modulation
Data Rate: 250 kbps
Modulation: Gaussian Frequency Shift Keying (GFSK)
Frequency Band
2,402 – 2,482 MHz
Module Transmit Power
Maximum: 20 dBm
(Maximum transmit power will vary by channel)
Receive Sensitivity
(typical)
8.2
-97 dBm
Direct Sequence Spread Spectrum (DSSS) Radio, 2.4 GHz
Warning! The XYR 6000 Transmitter must be Professionally Installed in accordance with the requirements specified in this
document. See Section 10, for professional installation maximum TX power setting requirements. Only the specified TX
power settings, antenna types and gains and cable lengths (attenuation) as outlined in this document are valid for XYR 6000
Transmitter installations.
Table 4 – Specifications of DSSS Radio Module in XYR 6000 Transmitter
Item
Specification
Wireless Standard
FCC 15.247 / IEEE 802.15.4 Direct Sequence Spread Spectrum (DSSS), 2.4 GHz
Data Rates and Modulation
Data Rate: 250 kbps
Modulation: Offset Quadrature Phase-Shift Keying (OQPSK – DSSS)
Frequency Band
2,405 – 2,475 MHz
Module Transmit Power
Maximum: 20 dBm
(Maximum transmit power will vary by channel)
Receive Sensitivity
(typical)
OneWireless XYR 6000 Transmitter
Professional Installation Guide
-100 dBm
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 13 of 28
8.3
XYR 6000 Transmitter User Environment
Table 5 – User Environment Specifications for XYR 6000 Transmitter
Item
Specification
Operating Temperature:
–40ºC to +85ºC (–40°F to +185°F)
Storage Temperature:
–40ºC to +85ºC (–40°F to +185°F)
Operating Humidity:
0 to 100% RH
8.4
XYR 6000 Instrument Power Specifications
The XYR 6000 Transmitters operate from two (2) D-size 3.6V Lithium batteries. These are joined in series to produce a
maximum voltage of +7.6 Vdc. An optional external +24 Volt power supply option will be available at a future date.
8.5
Weight
The weight of the complete XYR 6000 Transmitter units shall be 14.0 lb. (6.4 kg) maximum. This weight does not include
remote cables and antennas.
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 14 of 28
8.6
Dimensions
Figure 2 – Dimensions of the XYR 6000 Transmitter with Right-angle -2 dBi Integral Antenna
Option
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 15 of 28
9
9.1
Cables
XYR 6000 Transmitter with RP-TNC Connectors Antenna or Lightning Arrestor
Cables
Table 6 – Transmitter to Antenna or Lightning Arrestor Cable Specifications for XYR 6000 with RP-TNC connectors
Honeywell
Part Number
50018110-001
50018110-003
50018110-010
9.2
Cable
Type
400 Series
400 Series
400 Series
Connector
Type
RP-TNC to N male
RP-TNC to N male
RP-TNC to N male
Frequency
(GHz)
2.4
2.4
2.4
Length
(m)
10
Loss
(dB)
XYR 6000 Transmitter with N Connectors Antenna or Lightning Arrestor Cables
Table 7 – Transmitter to Antenna or Lightning Arrestor Cable Specifications for XYR 6000 with N connectors
Honeywell
Part Number
50018278-001
50018278-003
50018278-010
9.3
Cable
Type
400 Series
400 Series
400 Series
Connector
Type
N male to N male
N male to N male
N male to N male
Frequency
(GHz)
2.4
2.4
2.4
Length
(m)
10
Loss
(dB)
Lightning Arrestor to Antenna Cables
Table 8 – Lightning Arrestor to Antenna Cable Specifications
Honeywell
Part Number
50018278-001
50018278-003
50018278-010
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Cable
Type
400 Series
400 Series
400 Series
Connector
Type
N male to N male
N male to N male
N male to N male
Honeywell Proprietary
50021956
Frequency
(GHz)
2.4
2.4
2.4
Rev B
Length
(m)
10
Loss
(dB)
27 August 2008
Page 16 of 28
10 Antenna Lightning Arrestors
Table 9 – Lightning Arrestor Specifications for Remote Antenna(s)
Honeywell Part
Number
Manufacturer
Manufacturer
Part Number
50018279-090
ALTELECON
AL-NFNFB-9
Specification
Connector Type
50 ohm
N Female to N
Female
Frequenc
(GHz)
0–3
Attenuatio
(dB)
0.4 (max)
The lightning surge arrestor must be properly grounded in order to perform per specification. Connecting to local ground using
a No. 12 (4 mm2) copper conductor is recommended. See the installation manual for other details.
11 Approved Antenna Types/Gains
Table 10 – Approved Antenna Types/Gains
Antenna
Type
Antenna
Application
Manufacturer
Manufacturer
Part Number
Honeywell
Part Number
Beam
Width
Peak
Gain
(dBi)
Freq.
(GHz)
Agency
Compliance
Omni
(integral)
Point to
Multi-Point
CENTURIO
MAF94152
50016185-001
Omni
-2 1
2.4
FCC, IC,
ETSI,
ACMA
Omni
(integral)
Point to
Multi-Point
HYPERLINK
WHON511 –
0001
50029933-001
Omni
2.4
FCC, IC,
ETSI,
ACMA
Omni
(remote)
Point to
Multi-Point
HYPERLINK
HGV-2409U
50018414-001
Omni
2.4
FCC, IC,
ETSI,
ACMA
Directional
(remote)
Point to
Multi-Point
HYPERLINK
HG2414D
50018415-001
25°
14
2.4
FCC, IC,
ETSI,
ACMA
Note:
1. The Centurion antenna listed in Table 10 has a specified gain of 2.2 dBi. Through EIRP measurements performed during
antenna qualification testing, this antenna when installed in the Honeywell Radome and attached to the XYR 6000 Transmitter
body in either the right-angle or straight integral antenna options has an actual gain of -2 dBi. This value is used in
determining the maximum EIRP for Agency Compliance.
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 17 of 28
12 Equivalent Isotropically Radiated Power (EIRP)
In radio communication systems, Equivalent Isotropically Radiated Power (EIRP) or, alternatively, Effective Isotropic
Radiated Power, is the amount of power that would have to be emitted by an isotropic antenna (that evenly distributes power in
all directions and is a theoretical construct) to produce the peak power density observed in the direction of maximum antenna
gain. EIRP can take into account the losses in transmission line and connectors and includes the gain of the antenna. The EIRP
is often stated in terms of decibels over a reference power level that would be the power emitted by an isotropic radiator with
an equivalent signal strength. The EIRP allows making comparisons between different emitters regardless of type, size or
form. From the EIRP, and with knowledge of a real antenna's gain, it is possible to calculate real power and field strength
values.
EIRP(dBm) = Radio TX Power (dBm) – Cable Loss (dB) + Antenna Gain(dBi)
Antenna gain is expressed relative to a (theoretical) isotropic reference antenna (dBi).
13 EIRP LIMITS
Table 11 – Maximum EIRP Limits for FHSS Radios
Antenna
Type
-2 dBi
Omni
4 dBi
Omni
8 dBi
Omni
14 dBi
Directiona
Radio Usage /
Application
Point to
MultiPoint
Point to
MultiPoint
Point to
MultiPoint
Point to
MultiPoint
Integral
Integral
Remote
Remote
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Freq.
(GHz)
2.4
2.4
2.4
2.4
Max.
Ant.
Gain
(dBi)
-2
14
Min.
Cable
Length
(m)
Honeywell Proprietary
50021956
Min.
Cable
Loss (dB)
Agency/Country
Max. Radio
Output
Power
(dBm)
Max.
EIRP
(dBm)
FCC, IC
20
18
ETSI, ACMA, TNTC
20
18
France
2400-2454 MHz
20
18
France
2454-2482.5 MHz
Do not use 3
---
FCC, IC
20
24
ETSI, ACMA, TNTC
16
20
France
2400-2454 MHz
16
20
France
2454-2482.5 MHz
Do not use 3
---
FCC, IC
18
25
ETSI, ACMA, TNTC
13
20
France
2400-2454 MHz
13
20
France
2454-2482.5 MHz
Do not use 3
---
FCC, IC
12
25
ETSI, ACMA, TNTC
20
France
2400-2454 MHz
20
France
Do not use 3
---
Rev B
27 August 2008
Page 18 of 28
2454-2482.5 MHz
Table 12 – Maximum EIRP Limits for DSSS Radios
Antenna
Type
-2 dBi
Omni
4 dBi
Omni
8 dBi
Omni
14 dBi
Directiona
Radio Usage /
Application
Point to
MultiPoint
Point to
MultiPoint
Point to
MultiPoint
Point to
MultiPoint
Integral
Integral
Remote
Remote
Freq.
(GHz)
2.4
2.4
2.4
2.4
Max.
Ant.
Gain
(dBi)
-2
14
Min.
Cable
Length
(m)
Min.
Cable
Loss (dB)
Agency/Country
Max. Radio
Output
Power
(dBm)
Max.
EIRP
(dBm)
FCC, IC
20
18
ETSI, ACMA, TNTC
14
12
France
2400-2454 MHz
14
12
France
2454-2482.5 MHz
Do not use 3
---
FCC, IC
20
24
ETSI, ACMA, TNTC
12
France
2400-2454 MHz
12
France
2454-2482.5 MHz
Do not use 3
---
FCC, IC
18
25
ETSI, ACMA, TNTC
12
France
2400-2454 MHz
12
France
2454-2482.5 MHz
Do not use 3
---
FCC, IC
14
25
ETSI, ACMA, TNTC
-2
11
France
2400-2454 MHz
-2
11
France
2454-2482.5 MHz
Do not use 3
---
Notes for Table 11 and Table 12:
1. The values in the above tables have been determined through agency certification testing.
2. The following shall apply for antenna type, frequency range, application/usage and agency/country compliance:
• Antenna gains above the maximum values shown shall not be used.
• Cable length/loss below the minimum values shown shall not be used.
• Maximum overall radio output power shown shall not be exceeded.
• Maximum EIRP values shown above shall not be exceeded.
3. France restricts outdoor use to 10mW (10 dBm) EIRP in the frequency range of 2,454-2,483.5 MHz. Installations
in France must limit EIRP to 10 dBm for operating modes utilizing frequencies in the range of 2,454 – 2,483.5MHz.
For this reason, Honeywell does not recommend configuring frequency hopping modes that use this frequency range.
For installations in France, use only the following OneWireless Frequency Hopping (FH) Mode Selections: EU
Channel #1, EU Channel #7, NA/EU Guard Bands and NA/EU Channel 3 (FH Mode selections #4, 5, 8 and 10).
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 19 of 28
4.
Industry Canada Compliance Statement: This device has been designed to operate with the antenna types listed in this
document, and having a maximum gain of 14 dBi. Antenna types not included in this list or having a gain greater than
14 dBi are strictly prohibited for use with this device. The required antenna impedance is 50 ohms.
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 20 of 28
Table 13 – FHSS Transmit Power Settings for the antennas and cable lengths specified above for FCC, IC, ETSI,
ACMA and TNTC approvals
Description
Model Selection Guide Table III
Cable(s) Length
(m)
TX Power Setting for
ETSI/ACMA/TNTC
(dBm)
TX Power Setting
for FCC/IC
(dBm)
-2 dBi Integral
Antenna
V 0 0 0 0 or S 0 0 0 0
N/A
16
16
4 dBi Integral Antenna
R 0 0 0 0 or H 0 0 0 0
N/A
16
16
8 dBi Omni w/o
suppressor
M 0 1 0 0 or M 0 3 0 0
1, 3
13
16
8 dBi Omni w/o
suppressor
M1000
10
15
16
8 dBi Omni with
suppressor
M0101
1+1
15
16
8 dBi Omni with
suppressor
M 0 1 0 3 or M 0 3 0 3 or M 0 3 10 or
M 0 3 0 1 or M 1 0 0 3 or M 1 0 1 0
1+3, 3+3, 3+10,
3+1, 10+3, 10+10
16
16
14 dBi directional w/o
suppressor
D 0 1 0 0 or D 0 3 0 0
1,3
12
14 dBi directional w/o
suppressor
D1000
10
14
14 dBi directional with
suppressor
D0101
1+1
14
14 dBi directional with
suppressor
D 0 1 0 3 or D 0 3 0 1 or D 0 3 0 3
1+3, 3+1, 3+3
10
15
14 dBi directional with
suppressor
D 0 3 1 0 or D 1 0 0 3
3+10, 10+3
11
16
14 dBi directional with
suppressor
D1010
10+10
13
16
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 21 of 28
Table 14 – DSSS Transmit Power Settings for the antennas and cable lengths specified above for FCC, IC, ETSI,
ACMA and TNTC approvals
Description
Model Selection Guide Table III
Cable(s) Length
(m)
TX Power Setting for
ETSI/ACMA/TNTC
(dBm)
TX Power Setting
for FCC/IC
(dBm)
-2 dBi Integral
Antenna
V 0 0 0 0 or S 0 0 0 0
N/A
14
16
4 dBi Integral Antenna
R 0 0 0 0 or H 0 0 0 0
N/A
16
8 dBi Omni w/o
suppressor
M 0 1 0 0 or M 0 3 0 0
1, 3
16
8 dBi Omni w/o
suppressor
M1000
10
16
8 dBi Omni with
suppressor
M0101
1+1
16
8 dBi Omni with
suppressor
M 0 1 0 3 or M 0 3 0 3 or M 0 3 10 or
M 0 3 0 1 or M 1 0 0 3 or M 1 0 1 0
1+3, 3+3, 3+10,
3+1, 10+3, 10+10
16
14 dBi directional w/o
suppressor
D 0 1 0 0 or D 0 3 0 0
1,3
-2
12
14 dBi directional w/o
suppressor
D1000
10
14
14 dBi directional with
suppressor
D0101
1+1
-1
14
14 dBi directional with
suppressor
D 0 1 0 3 or D 0 3 0 1 or D 0 3 0 3
1+3, 3+1, 3+3
-2
15
14 dBi directional with
suppressor
D 0 3 1 0 or D 1 0 0 3
3+10, 10+3
16
14 dBi directional with
suppressor
D1010
10+10
16
Notes for Table 13 and Table 14:
1. The Model Number of any instrument may be found on the identification name plate located on the outside of the
XYR 6000 transmitter. The values in the Cable(s) Length column represent those customer selections from Table III
of the XYR 6000 Model Selection Guides.
2. In the Cable(s) Length column, entries of the form “X+X” indicate that there are two cables between the XYR 6000
and the remote antenna, with a lightning surge arrestor used to connect the two cables together. Entries of the form
“X” mean that there is a single cable and that no lightning surge arrestor is used. For entries of the form “X+X”; the
first value is the length of the cable between the instrument and the arrestor while the second value is the length of the
cable between the arrestor and the remote antenna. All cables are 400 series types as specified in Table 6 and Table 7.
3. TX Power is set by the Honeywell factory producing the XYR 6000 to the values shown in the above tables. These
factory values are determined by the customer’s model number selections in Table III for antenna type, cables and the
lightning suppressor. If the cable lengths, antenna type or the use of a lightning surge arrestor are changed in the field
away from the Model Number listed on the instrument, then the TX power setting should likewise be changed per the
tables above to match the new antenna/cable/arrestor selections.
4. The TX Power Setting values given in Table 12 and Table 13 represent the power produced by the Radio circuit
within the RF Module. These TX Power Setting values do not include antenna gains nor do they include losses caused
by cables, connectors and lightning arrestors. When these external gains and losses are included, using the TX power
values in Table 13 and Table 14 ensures that the EIRP will not exceed the maximum limits as given in Table 11 and
Table 12.
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 22 of 28
14 Setting TX Power
Warning! The XYR 6000 Transmitter must be Professionally Installed in accordance with the requirements specified in this
document. Only the specified power settings, antenna types and gains and cable lengths (attenuation) as outlined in this
document are valid for XYR 6000 Transmitter installations.
TX Power setting is accomplished with the Authentication Device when a special application (app) is installed. This app is
considered to be Honeywell sensitive material and is made available only to the qualified Professional Installer.
When this app is installed in the AD, the XYR 6000 TX power setting, normally a read-only parameter, becomes a read/write
parameter.
Using the virtual keyboard in the Device Local Configuration AD routine to manipulate the local user interface (LUI),
navigate to the TX_POWER display in the RADIO setup group. The XYR 6000 as shipped from the factory should show a
TX Power value consistent with those given in Table 13 and Table 14.
The TX Power adjustment feature is provided for Professional Installers to adjust the XYR 6000 TX power to match the
specific selection of antenna and cables at the installation site and keep the total TX power under the regulatory thresholds.
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 23 of 28
15 Agency Label Information
The following information shall be clearly and permanently labeled on the XYR 6000 Transmitter unit:
15.1 External FCC/IC Labels
15.1.1 50016195-001 – Transmitters with FHSS Radios
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
FCC ID: S5750016517 / IC: 573I-50016517
15.1.2 50016195-002 – Transmitters with DSSS Radios
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
FCC ID: S5750025034 / IC: 573I-50025034
15.2 Internal FCC/IC Labels
50021957-001
RF MOD 50016517-001
FCC ID: S5750016517
IC: 573I-50016517
OneWireless XYR 6000 Transmitter
Professional Installation Guide
50021957-002
50021957-003
RF MOD 50025132-001
FCC ID: S5750016517
IC: 573I-50016517
Honeywell Proprietary
50021956
RF MOD 50025034-001
FCC ID: S5750025034
IC: 573I-50025034
Rev B
27 August 2008
Page 24 of 28
16 RF Safety, Maximum Permissible Exposure (MPE) statement
To comply with FCC’s and Industry Canada’s RF exposure requirements, the following antenna installation and device
operating configurations must be satisfied:
Remote antenna(s) for this unit must be fixed and mounted on outdoor permanent structures with a separation distance
between the antenna(s) of at least 20 cm and a separation distance of at least 20 cm from all persons.
When using integral antenna(s) the XYR 6000 Transmitter unit must not be co-located with any other antenna or transmitter
device and have a separation distance of at least 20 cm from all persons.
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 25 of 28
17 Agency Compliance
17.1 Radio and EMC Certifications
17.1.1 Federal Communication Commission (FCC)
¾
Specification: FCC Part 15.247 Subpart B for unintentional radiators
¾
Specification: FCC Part 15.247 Subpart C for intentional radiators
17.1.2 Industry Canada (IC)
¾
Method: RSS-210, Issue 7
¾
RSS-Gen, Issue 2
¾
ICES-003, Issue 4
17.1.3 European Telecommunications Standards Institute (ETSI)
¾
Emissions Specification and Method: EN 300 328 V1.7.1
¾
Emissions Spec and Method: EN 301 893 V1.3.1
¾
Immunity Specification: EN 301 489-17 V1.2.1
¾
Immunity Method: EN 301 489-1 V1.6.1
¾
Product Standard: IEC61326-1 (1st Edition, 2002-02, Industrial Locations)
17.1.4 Australian communications and media authority (ACMA)
¾
Specification: AS NZS 4771-2000
17.1.5 Thailand National Telecommunications Commission (TNTC)
¾
Specification: เรื่อง เครื่องวิทยุคมนาคมและสถานีวิทยุคมนาคมที่ไดรับยกเวนไมตองไดรับใบอนุญาต (Specification for
non-licensed Radio and Radio Station Telecommunications)
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 26 of 28
17.2 Product Safety Agency Certifications
17.2.1 Canadian Standards Association (CSA)
ANSI/ISA S82.02.01 (61010-1) CSA C22.2 No. 1010-1, ANSI/UL 61010-1, Safety Standard for Electrical Equipment for
Measurement, Control and Laboratory Use – Part 1: General Requirements
C22.2 No. 0, General Requirements - Canadian Electrical Code, Part II
C22.2 No. 25, Enclosures for Use in Class II, Group E, F & G Hazardous Locations
C22.2 No. 94, Special Purpose Enclosures, Industrial Products
C22.2 No. 14, Industrial Control Equipment, Industrial Products
C22.2 No. 30, Explosion Proof Enclosures for Use in Hazardous Locations, Industrial Products
C22.2 No. 157, Intrinsically Safe and Non-Incendive Equipment for Use in Hazardous Locations
C22.2 No. 213, Non-Incendive Electrical Equipment for Use in Class I, Division 2 Hazardous Locations
E60079-0, Electrical Apparatus for Explosive Gas Atmospheres, Part 0: General Requirements
E60079-1, Electrical Apparatus for Explosive Gas Atmospheres, Part 1: Flameproof “d”
E60079-11, Electrical Apparatus for Explosive Gas Atmospheres, Part 11: Intrinsic Safety "i"
E60079-15, Electrical Apparatus for Explosive Gas Atmospheres, Part 15: Electrical Apparatus With Type of Protection "n"
•
Temperature code: T4 (135°C) based on the maximum specified ambient of 85°C.
17.2.2 Factory Mutual (FM)
ANSI/ISA S82.02.01 (61010-1) CSA C22.2 No. 1010-1, ANSI/UL 61010-1, Safety Standard for Electrical Equipment for
Measurement, Control and Laboratory Use – Part 1: General Requirements
FM electrical equipment requirements for use within Class I, Division 2, Groups A, B, C and D/Zone 2, Group IIC Hazardous
Locations.
Factory Mutual Approval Standard Class No. 3600, “Electrical Equipment for Use in Hazardous (Classified) Locations –
General Requirements
Factory Mutual Approval Standard Class No. 3810, “Electrical and Electronic Test, Measuring, and Process Control
Equipment
Factory Mutual Approval Standard Class No. 3611, “Electrical Equipment for Use in Class I, Division 2, Class II, Division 2
and Class III, Division 1 and 2 Hazardous (Classified) Locations
•
Temperature code: T4 (135°C) based on the maximum specified ambient of 85°C.
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 27 of 28
17.2.3 European ATEX Certification (ATEX)
EN 60079-0, Electrical Apparatus for Explosive Gas Atmospheres, Part 0: General Requirements
EN 60079-1, Electrical Apparatus for Explosive Gas Atmospheres, Part 1: Flameproof Enclosures “d”
EN 60079-11, Electrical Apparatus for Explosive Gas Atmospheres, Part 11: Intrinsic Safety "i"
EN 60079-15, Electrical Apparatus for Explosive Gas Atmospheres, Part 15: Electrical Apparatus with Type of Protection
“n”
EN 50281, Electrical Apparatus for Use in the Presence of Combustible Dust
EN 50284, Special Requirements for Construction, Test and Marking of Electrical Apparatus of Equipment Group II,
Category 1G
The temperature code for the XYR 6000 Transmitter shall not exceed T4 (135°C) based on the maximum specified ambient
of 85°C.
17.3 European Union Certification (CE-mark)
•
Compliance with:
R&TTE Directive 1999/5/EC
EMC Directive 2004/108/EC
LVD Directive 73/23/EEC
ATEX Directive 94/9/EC
18 Reference Documents
Table 15 – Reference documents
Getting Started with Honeywell OneWireless
Honeywell OneWireless Planning Guide
Honeywell XYR 6000 User’s Manuals
Radio Antenna: A Primer White Paper
Honeywell OneWireless System Administration Guide
Honeywell OneWireless Field Network Dictionary
OneWireless Builder Parameter Reference
OneWireless Builder User’s Guide
OneWireless XYR 6000 Model Selection Guides
OneWireless XYR 6000 Transmitter
Professional Installation Guide
Honeywell Proprietary
50021956
Rev B
27 August 2008
Page 28 of 28

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.4
Linearized                      : No
Tagged PDF                      : Yes
XMP Toolkit                     : Adobe XMP Core 4.0-c316 44.253921, Sun Oct 01 2006 17:14:39
Producer                        : Acrobat Distiller 8.1.0 (Windows)
Company                         : Honeywell Intl.
Category                        : Installer Guide
Source Modified                 : D:20080827122330
Create Date                     : 2008:08:27 08:25-04:00
Creator Tool                    : Acrobat PDFMaker 8.1 for Word
Modify Date                     : 2008:08:27 08:25:49-04:00
Metadata Date                   : 2008:08:27 08:25:49-04:00
Document ID                     : uuid:d30b6984-b4f6-472c-8916-19039054ccac
Instance ID                     : uuid:9776e59f-7cb0-4d61-9242-27cbca56b9bd
Subject                         : 37
Format                          : application/pdf
Creator                         : 50021956
Title                           : OneWireless XYR 6000 Transmitter
Description                     : Professional Installation Guide
Headline                        : Professional Installation Guide
Page Count                      : 28
Page Layout                     : OneColumn
Author                          : 50021956
Keywords                        : Rev, B
EXIF Metadata provided by EXIF.tools
FCC ID Filing: S5750025034

Navigation menu