Ibis Networks 200 RF Module User Manual DataSheetPowerx

Ibis Networks Inc. RF Module DataSheetPowerx

Contents

User Manual - IS-204

IS-204, IS-205, IS-206
InteliSocket
Ibis Networks
·
828 Fort Street Mall Suite 600
·
Honolulu, HI 96813
·
www.ibisnetworks.com 1
05/28/15
FEATURES
120V/240V 15A/20A
ZigBee Pro
128 bit AES Security
20dBm RF Power
Surge Protected
0C to 40C
DESCRIPTION
The IS-204, IS-205, and IS-206 (see part numbering) smart sockets meter plug load energy
usage and provides device on/off capability. They work with other InteliSockets
TM
to form a
secure wireless mesh network for control and reporting of data. Each network has an
InteliGateway
TM
base station providing connectivity to the Ibis InteliNetwork
TM
, a cloud-based
data collection and analysis application. InteliSockets can be configured to operate on any of
the 15 ZigBee channels. In addition, the hive (PANID) has over 4000 possible settings,
preventing nearby systems from interfering with each other.
PERFORMANCE
Parameter Symbol Min Typ Max Units
Input Voltage (RMS) V
IN
108 120/240 250 V
Input Frequency 47 50/60 63 Hz
Output Current (RMS) I
OUT
20 A
Output Power P
OUT
4800 W
Power Consumption 1 W
Reporting Interval 1 15 255 s
Accuracy (Energy) 0.5 %
Accuracy (Voltage) 2 %
Accuracy (Interval) 1 ms
Resolution 1 W-s
RF Range 50 m
RF Transmit Power 0 20 dBm
Sockets per Network 120
ZigBee Channels 11 25
ZigBee Hive 0x3000 0x3FFF
Size 5.8 x 3.4 x 2.3 inches
Cord Length 20 inches
IS-204, IS-205, IS-206
InteliSocket
Ibis Networks
·
828 Fort Street Mall Suite 600
·
Honolulu, HI 96813
·
www.ibisnetworks.com 2
05/28/15
PART NUMBERING
Type Voltage Current Connector
IS-204 120 20 5-20P
IS-205 240 15 6-15P
IS-206 240 20 6-20P
COMPLIANCE
Agency File
UL916 – Energy Management Equipment E470522
ZigBee Profile (Ibis Automation) 0x114B
FCC 2AECN200
ENVIRONMENTAL
Parameter Symbol Min Typ Max Units
Operating Temperature T
O
0 25 40 C
Storage Temperature T
-40 100 C
Relative Humidity RH 0 95 %
InteliSockets are for indoor use only.
PROTOCOL
InteliSockets use the Ibis custom ZigBee profile for commands, acknowledgements, and
reporting of data. Refer to the V2 Protocol documentation for details.
DATA
InteliSockets report data typically every 15 seconds. Each report packet is comprised of socket
type, ZigBee channel, ZigBee hive (PANID), interval (seconds), voltage (RMS), frequency (Hz),
energy (watt-seconds), and power factor (fraction). From these data we can calculate
instantaneous power (watts) and current (amps).
  

IS-204, IS-205, IS-206
InteliSocket
Ibis Networks
·
828 Fort Street Mall Suite 600
·
Honolulu, HI 96813
·
www.ibisnetworks.com 3
05/28/15
  
· 
The InteliGateway appends additional information (IP, timestamp, location, etc.) before
uploading to the InteliNetwork. This allows any socket in the world to be located and
addressed individually.
PUSHBUTTON
The small pushbutton on the side provides addition control features. First and foremost, it is a
manual override for turning the outlet on and off (toggle). If pressed for at least two seconds, it
causes a reboot of the socket. Finally, if the pushbutton is pressed while plugging in the socket,
a factory reset is performed causing the socket to revert back to factory default settings. This is
a useful feature for maintenance purposes.
LED
The LED on the front indicates the state of the socket. When red the outlet is off; green is
outlet is on. If LED is blinking, the socket has not yet associated with a mesh network. During a
reboot, the LED will flash yellow for a second.
WIRING
The basic design of the IS-204 InteliSocket allows for it to be wired for either 120V or
208V/240V operation. Load current is defined by the outlet connector used, and can be up to a
maximum of 25 amps.
FCC
This equipment has been tested and found to comply with the limits for a class B digital device,
pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates,
uses, and can radiate radio frequency energy and if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the interference by
one or more of the following measures:
Reorient or relocate the receiving antenna.
IS-204, IS-205, IS-206
InteliSocket
Ibis Networks
·
828 Fort Street Mall Suite 600
·
Honolulu, HI 96813
·
www.ibisnetworks.com 4
05/28/15
Increase the separation between the equipment and receiver.
Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
The user is cautioned that changes and modifications made to the equipment without the
approval of manufacturer could void the user’s authority to operate this equipment.
To satisfy RF exposure requirements, this device and its antenna must operate with a
separation distance of at least 20 cm from all persons and must not be co-located or operating
in conjunction with any other antenna or transmitter.