NEC of America 58155 NEC NLite E 155 MB 5.8 GHz Digital Microwave Radio User Manual Part 3

NEC Corporation of America NEC NLite E 155 MB 5.8 GHz Digital Microwave Radio Part 3

User Manual Part 3

ROI-S05750 INSTALLATION2-77Chart 2-14 (Cont’d) Step Procedure7 Recheck that the wire position is as shown in step 5 before crimping the socket contact (see illustration below).WIRE SIDESOCKET CONTACTWIRE8 Wind the metallic shield tape over the braided shield.METALLIC SHIELD TAPE9 Set the cable into the plug case as shown in figure below.  Then, fix the cable using the cable clamper and two screws.CABLE CLAMPERPLUG CASE
INSTALLATION ROI-S057502-78Chart 2-14 (Cont’d) Step Procedure10 Referring to circle A, fix the drain wire with screw.11 Referring to circle B, insert each wire to the specified position (Refer Interface Terminals and Jacks for IDU in Section II OPERATING EQUIPMENT.).  Insert the socket contacts into the upper and lower row positions while taking care that the socket contacts are inserted the right way.CIRCLE ASCREWDRAIN WIRECIRCLE B
ROI-S05750 INSTALLATION2-79Chart 2-14 (Cont’d) Step Procedure12 Fix the plug case with two screws, as shown in the figure.SCREWPLUG CASE
INSTALLATION ROI-S057502-80Chart 2-15 Terminating IF Coaxial Cable with TNC-P Connector (L Angle Type)  (HIROSE made) used for IDU IF IN/OUTStep ProcedureNote: It is recommended that TNC (Male) L-angle connector for the 8D-FB IF cable is used to connect it to the IDU. When the N (Male) straight connector is attached to the 5D-FB or 10D-FB IF cable, use of the TNC (Male) - N (Female) (NJ-TNCP-LA) L-angle adapter is needed.1 Pass the tightening nut, the washer and the gasket on the cable in the order shown in the figure. Then, strip the cable jacket in the diameter shown in the figure. [Applicable cable : 8D-FB-E]Note: Be careful of insertion direction for the gasket and the tightening nut.Note: Be careful not to damage the outer conductor.Note: Do not reuse the gasket because the clamp deforms it after tightening.2 Insert the clamp to clamp the stripped cable jacket end. Open the end of the outer conductor a little,3 Insert the hood between the plastic tape with aluminium foil and the outer conductor,ClampHoodNote: Use the insertion stick to open the hole of about φ9. No gap is allowed in between the clamp, the outer conductor and the hood.
ROI-S05750 INSTALLATION2-81Chart 2-15 (Cont’d) Step Procedure4 After inserting the hood, cut off the plastic tape with aluminium foil and the dielectric at A-surface, 5 Cut off the part of the outer conductor exceeding the clamp rim with a knife,6 Check that distance between the tip of the center conductor and A-surface is 6 to 7 mm,  If it is more than 7 mm, cut the center conductor to correct length,ClampNote: Be careful not to damage the center conductor,Note: Chamfer at the tip of the center conductor,Note: There shall be no evidence of deviation or deformation or burr at the tip of the center conductor.
INSTALLATION ROI-S057502-82Chart 2-15 (Cont’d) Step Procedure7 Insert the insulation washer over the center conductor, and engage it with the F/F contact,Note: No gap is allowed in between the F/F contact, the insulation washer, and the dielectric.Note: The assembly unit after the completion of this process is called “block”.8 Combine the convex part of the clamp to the concave part of the gasket, Then insert this block to the shell,Note: Insert the hood until it hits the B-surface.
ROI-S05750 INSTALLATION2-83Chart 2-15 (Cont’d) Step Procedure9 Tighten the tightening nut sufficiently until the gasket is cut by the clamp and the tip of the clamp hits the washer,Note: Torque for the tightening nut shall be 8 to 30N•m.Note: When tightening the nut, tighten with wrench at the wrench at the wrench flat.Note: Distance between the tightening nut and the LP shell is 1.85 to 2.1 mm for reference.  Tighten the nut sufficiently.L-type dimension and cutting length of the cable.Specified length L:  Cutting length L−25.
INSTALLATION ROI-S057502-84Chart 2-16 Terminating Coaxial (IF Signal) with N-P Connector (L Angle Type) used for ODU IF IN/OUT (KOMINE made)Step ProcedureNote: It is recommended that TNC (Male) L-angle connector for the 8D-FB IF cable is used to connect it to the IDU. When the N (Male) straight connector is attached to the 5D-FB or 10D-FB IF cable, use of the TNC (Male) - N (Female) (NJ-TNCP-LA) L-angle adapter is needed.1 First fit the tying metal, washer and gasket on the cable.GASKET WASHER TYING METALCABLE2 Strip back the cable sheath, taking care not to damage the braided shield, and fit the clamp.CLAMP9 mm3 Fold back the braided shield (separating the strands of the braid) and trim it.Note: Pay attention not to damage the plait.4 Insert the ferrule.FERRULE
ROI-S05750 INSTALLATION2-85Chart 2-16 (Cont’d) Step Procedure5 Fit the bushing.BUSH6 Cut the aluminium foil and inner insulator away along the bushing and retain the inner conductor.7 Taper the edge of the center conductor using a file as shown in the enlarged view below.Note: Pay attention not to let protrusions and indents to occur.
INSTALLATION ROI-S057502-86Chart 2-16 (Cont’d) Step Procedure8 Mount the contact onto the center conductor and mount the insulator onto the contact.INSULATOR CONTACT9 Insert the cable into the shell.10 Tighten the tying metal by wrench using the wrench points. (Tighten with torque of 4 to 10 N·m)WRENCH POINTLESS THAN 0.1 mm(USUALLY NO GAPS)
ROI-S05750 INSTALLATION2-87Chart 2-17 Terminating IF Coaxial Cable with N-P Connector (L Angle Type)  used for the ODU IF IN/OUT (HIROSE made)Step ProcedureNote: It is recommended that TNC (Male) L-angle connector for the 8D-FB IF cable is used to connect it to the IDU. When the N (Male) straight connector is attached to the 5D-FB or 10D-FB IF cable, use of the TNC (Male) - N (Female) (NJ-TNCP-LA) L-angle adapter is needed.1 Pass the tightening nut, the washer and the gasket on the cable in the order shown in the figure. Then, strip the cable jacket in the diameter shown in the figure. [Applicable cable : 8D-FB-E]Note: Be careful of insertion direction for the gasket and the tightening nut.Note: Be careful not to damage the outer conductor.Note: Do not reuse the gasket because the clamp deforms it after tightening.2 Insert the clamp to clamp the stripped cable jacket end. Open the end of the outer conductor a little,3 Insert the hood between the plastic tape with aluminium foil and the outer conductor,Note: Use the insertion stick to open the hole of about φ9. No gap is allowed in between the clamp, the outer conductor and the hood.
INSTALLATION ROI-S057502-88Chart 2-17 (Cont’d) Step Procedure4 After inserting the hood, cut off the plastic tape with aluminium foil and the dielectric at A-surface, 5 Cut off the part of the outer conductor exceeding the clamp rim with a knife,6 Check that distance between the tip of the center conductor and A-surface is 6 to 7 mm,  If it is more than 7 mm, cut the center conductor to correct length,Note: Be careful not to damage the center conductor,Note: Chamfer at the tip of the center conductor,Note: There shall be no evidence of deviation or deformation or burr at the tip of the center conductor.
ROI-S05750 INSTALLATION2-89Chart 2-17 (Cont’d) Step Procedure7 Insert the insulation washer over the center conductor, and engage it with the F/F contact,Note: No gap is allowed in between the F/F contact, the insulation washer, and the dielectric.Note: The assembly unit after the completion of this process is called “block”.8 Combine the convex part of the clamp to the concave part of the gasket, Then insert this block to the shell,Note: Insert the hood until it hits the B-surface.
INSTALLATION ROI-S057502-90Chart 2-17 (Cont’d) Step Procedure9 Tighten the tightening nut sufficiently until the gasket is cut by the clamp and the tip of the clamp hits the washer,Note: Torque for the tightening nut shall be 8 to 30N•m.Note: When tightening the nut, tighten with wrench at the wrench at the wrench flat.Note: Distance between the tightening nut and the LP shell is 1.85 to 2.1 mm for reference.  Tighten the nut sufficiently.L-type dimension and cutting length of the cable.Specified length L:  Cutting length L−25.
ROI-S05750 INSTALLATION2-91Chart 2-18 Terminating IF Coaxial Cable  with N-P Connector (Straight Type) used for ODU IF IN/OUT (HIROSE made)N-type connector is used for the ODU side. Note: When the N (Male) straight connector is attached to the IF coaxial cable for the IDU IF IN/OUT, use of the TNC (Male) - N (Female) (NJ-TNCP-LA) L-angle adapter is needed.Step Procedure1 First fit the lock nut, washer and gasket on the cable as shown.CABLELOCK NUT WASHER GASKET2 Strip back the cable sheath, taking care not to damage the braided shield, and fit clamp A.CLAMP AXCONNECTOR CABLE XN260 5D-FB 25 mmN227 8D-FB 25 mmN228 10D-FB 27 mmN229 12D-FB 27 mm3 Fold back the braided shield (separating the strands of the braid) and trim it.
INSTALLATION ROI-S057502-92Chart 2-18 (Cont’d) Step Procedure4 Cut away the insulation from the center conductor and fit clamp B.  Be sure not to cut or scratch the conductor while stripping the insulation.1.0 mm CLAMP BCUT5 Cut the center conductor.  Taper the end of the center conductor using a file as shown in the enlarged view below.12 mm6 Mount the center contact onto the center conductor as shown.Note: Insert the center contact into insulator (1.5 mm).1.5 mmCENTER CONTACT
ROI-S05750 INSTALLATION2-93Chart 2-18 (Cont’d) Step Procedure7 Mount the insulator onto the center contact.TAPERING SIDEINSULATOR8 Insert the cable into the connector shell.CONNECTOR SHELL9 Tighten the lock nut.LOCK NUTLess than 0.5 mm
INSTALLATION ROI-S057502-94Chart 2-19 Terminating IF Coaxial Cable  with N-P Connector (Straight Type) used for ODU IF IN/OUT (KOMINE made)N-type connector is used for the ODU side. Note: When the N (Male) straight connector is attached to the IF coaxial cable for the IDU IF IN/OUT, use of the TNC (Male) - N (Female) (NJ-TNCP-LA) L-angle adapter is needed.Step Procedure1 The clamp nut, the washer and the gasket are inserted in the cable,GASKET WASHER CLAMP NUTCABLE2 Strip the cable as below and disentangle the braid and insert the clamp in the cable,BRAIDCLAMP25 mmDo not scratch the braid wire.3 Turn the braid on the clamp inserted and cut the braid according to the paragraph,BRAIDINSULATOR FOIL PARAGRAPH
ROI-S05750 INSTALLATION2-95Chart 2-19 (Cont’d) Step Procedure4 Cut the cable-insulator according to the surface that is turned the braid and insert the ferrule, FERRULECENTER CONDUCTOR The surface that is turned the braid.Do not scratch the center conductor.5 Insert the insulator,INSULATOR6 Cut the center-conductor as following size. Process the tip of center-conductor like a taper with a file. (Do not have a curve and burr.)  Insert the center-contact in the center-conductor and insert the insulator in the center-contact,12 mmCENTER CONTACTINSULATORProcessing chart of the tip of the center-conductor.
INSTALLATION ROI-S057502-96Chart 2-19 (Cont’d) Step Procedure7 Connector body is fit to the cable. Fit in the cable end into the body and screw the clamp nut by your hand first and tighten it with a torque wrench.  Confirm the space that it is less than 0. 5 mm between the body and the cramp nut.BODY CLAMP NUT18/2 flats less than 0.5 mmTightening torque is more than 9.8 N•m (100kgf•cm)Note: Use torque wrench.
ROI-S05750 INSTALLATION2-97Chart 2-20 Terminating Power Supply Cables with Molex ConnectorStep Procedure Note: Do not bend this part.1 Remove 3.0 to 3.5 mm of insulation.CABLE AWG#18-24 POWER SUPPLY CABLE3.0 to 3.5 mmFOR 48 V, 1A
INSTALLATION ROI-S057502-98Chart 2-20 (Cont’d) Step Procedure2 Set the socket contact to position 1 or 2 of the hand crimping tool.HAND CRIMPING TOOL57026-5000 Molexor 57027-5000(            )HAND CRIMPING TOOL TYPE57026-500057027-5000OUTSIDE DIAMETER  OF CABLEφ 1.5 to 1.8φ 1.8 to 2.2φ 2.3 to 2.6φ 2.6 to 3.1SET POSITION2112123 Squeeze the handle of the hand crimping tool, insert cable into socket contact.4 The cable should fit, so insulation and bare wire are arranged as shown.5 Squeeze the handle of the hand crimping tool until the ratchet is released.INSULATION BARREL WIRE BARRELWIRE STRIP LENGTH
ROI-S05750 INSTALLATION2-99Chart 2-20 (Cont’d) Step Procedure6 Twist cables for the  power supply,Note: Twist power cables to suppress inductive interference signals.7 Insert the socket contacts into the power connector until they lock.−48 V (*1)GND (*2)POWER CONNECTORNote : For H3040 DC-DC CONV, (*1):−20 to −60 V (or 0 V) (*2):0 V (or +20 to +60V)
INSTALLATION ROI-S057502-100Chart 2-21  BNC Connector for 3C-2V Coaxial Cable Assembling, Solder TypeThe following explains how to assemble BNC solder type as an example.LOCK NUT CLAMP 1 CLAMP 2 SHELLStep 1. Slide the lock nut onto the cable. Strip the cable sheath, taking care not to damage the braided shield wires, and fit CLAMP 1.(15.5 mm)*(39/64”)*Note *:Stripping measurements vary depend on the BNC Step 2. Fold back the braided shield wire around the CLAMP 1 (without separating the strands of the braid) and trim it.trimStep 3. Cut away the insulator from the centre conductor and fit CLAMP 2. (Be sure not to cut or scratch the conductor while stripping the insulation.)(7 mm)*(9/32”)*Note *:Stripping measurements vary depend on the BNC Step 4. Solder the pin contact to center conductor.  Use a knife to remove excess solder.SOLDERINGStep 5. Insert the connectorized cable into the BNC shell and fasten the lock nut with a wrench.
ROI-S05750 INSTALLATION2-101Chart 2-22  BNC Connector for 3C-2V Coaxial Cable Assembling, Crimping TypeThe following explains how to assemble BNC crimping type as an example. Step 1. Strip coaxial cable as illustrated left, (taking care not to damage braided shield wire), Step 2. Cut braided shield wire (without unravel the strands of braid) and trim it,Step 3. Cut dielectric, (be sure not to cut or scratch the centre conductor while stripping the dielectric),center conductordielectricshield wireSheath(15 mm)*(6.3 mm)*(4 mm)*STRIPPINGNote*: Stripping measurements vary depending on the BNC type.ABCcontraction sleeveferrulepin contact BNC shellBNC plugcontraction sleeve ferruleStep 4. Slide contraction sleeve and ferrule onto the cable,Step 6. Slide pin contact until it bottoms against the centre conductor,insulatorStep 6. Slide  braid  tube and insulator among braided shield wire and dielectric,braid tubeStep 5. Fan braided shield wire,braid tubeinsulatorpin contact
INSTALLATION ROI-S057502-102Chart 2-22 (Cont’d) Step 7. Crimp pin contact,crimppin contactcrimping toolcrimping areacrimpStep 8. Slide carefully the cable into BNC shell until insulator butts against BNC body,Step 9. Slide ferrule over shield wire until it bounds against the BNC shell body,ferruleStep 10.Crimp ferrule as close as possible to the BNC shell body and trim the excess of braid,crimping toolCrimp ferrule as close as possible.trimuse suitable crimping size
ROI-S05750 INSTALLATION2-103Chart 2-22 (Cont’d) Step 11.Position contraction sleeve over ferrule and BNC,Step 12.Heat contraction sleeve until it contracts.contraction sleeveheated air
INSTALLATION ROI-S057502-104Chart 2-23 D-Sub High Density Crimp Contacts AssemblyThe following explains how to assemble high density crimp contacts used for HARTING hand crimp tool as an example. Step 1. Strip the jacket for 2.5 −0/+0.5 mm as shown left and check if stranded wire is not damaged, Step 2. Place the handles in the open position as shown left,JacketStranded wire2.5 −0/+0.5 mmStep 3. Select the suitable chamber for the selected wire,Step 7. Take out the crimped contacts from the chamber.  Check if it should not be scratched or transformed.Step 4. Insert contact in the selected chamber,Applicable wire size : 0.14 - 0.22 mm2 (AWG26 - 24),stranded, maximum insulation: φ1.38 mm Crimp Tool(09 88 999 0596)Note: When the handles are in close position, squeeze handles completely until safety ratchet is released.JacketChamber for 0.22 mm2 (AWG 24)Chamber for 0.14 mm2 (AWG 26)Indication of the part numberStep 5. Insert the prepared wire in the contact,Step 6. Squeeze the handles together completely until the safety ratchet clicks to open,Stamped male contacts : 09 56 000 8175 (Level S4),High density male connectors : 09 56 300 5601 (#44) Crimping/inserting contacts process
ROI-S05750 INSTALLATION2-105Chart 2-23 (Cont’d) Step 8. After crimping the stranded wire to the contact using a hand tool, insert the contact into the contact chamber with the tool, working from the wiring side,Step 9. You can here the contacts snap home, audible “click”,Removing crimp contactsStep 1. Position the tool from the wiring side as shown left and insert into the contact chamber.  The contact can then easily be removed from the wiring side together with itself and reinserted in a different chamber.Step 10.Check if they are securely in place with giving the wire a gentle pull.Insertion and removal tool(09 99 000 0513)WireConnectorInsertion and removal tool[Removal]Contact can be removedtogether with wire.[Insertion]Contact can be insertedtogether with wire.Contact chamberInsertion and removal toolPosition the
INSTALLATION ROI-S057502-1062.9 Wiring and FormingChart 2-24  Wiring and Forming1 Connect cables for, signal interface, power supply, IF IN/OUT and ground to the proper connector of the IDU. (1) Connect ground cable to the ground terminal(2) Connect IF cable to IF IN/OUT connector.(3) Connect power supply cable to SELV connector.(4) Connect OC-3 NLite E, Aux. signal cables to proper connectors.(5) Connect XIF coaxial cables to opposite IDU. (XPIC configuration only.)(6) Connect XPIC CTRL cables to opposite IDU. (XPIC configuration only.)Note: When disconnect cables, perform it in revers steps.2 Fix the cables using cable binder to the rack as like as indicated position.Notes: 1. Do not cross the cables on front of indicators and power switch used for maintenance.2. Take suitable bend radius to wiring the IF cable. (e.g. 10D-FB: 70 cm)3. For the IF cable connection, it is recommended to use adapter. (Applicable adapters are listed table below).Table 2-6  IF Cable AdapterIF Cable AdapterTNC(P) - N(J) TNC(P) - TNC(J)5D-FB √8D-FB √ √10D-FB √
CautionTighten the TNC-male connector of IF cable to the IDU with engage connector nut only using fingers and holding the cable with another hand.  Tighten the engage connector nut only for the L-angle connector also. (Tightening Torque : 0.3 to 0.5 N•m (3 to 5kg•cm))IDUIDUIF CABLEIF CABLEIDUIF CABLEStraight TypeL-Angle TypeL Angle TypeIf rotate other parts of the L-angle connector as illustrated left,  it can cause connector damage.ROI-S05750 INSTALLATION2-107
INSTALLATION ROI-S057502-108NLite E  SONETSELV!XIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRFGPULLSELV!XIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRPULLSELV!XIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRFGPULLSELV!XIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRPULL(1)  Connect XIF cable to between XIF IN (Main Master ) and XIF OUT (Sub Master), and  XIF OUT (Main Master) and XIF IN (Sub Master).(2) Connect XPIC CTRL cables to between XPIC CTRL (Main Master) and  XPIC CTRL (Sub Master).AUX/ALMNMS NE SC IN/OUT EOWPROTECTCALL MMCMAINTMEMORYIDUNLite EFGLCTAUX/ALMNMS NE SC IN/OUT EOWPROTECTCALL MMCMAINTMEMORYIDUNLite ESFGLCTALMOC-3 INOC-3 OUTALMOC-3 INOC-3 OUT ONLINEONLINEALMOC-3 INOC-3 OUTALMOC-3 INOC-3 OUT ONLINEONLINEFig. 2-8  Cable Wiring for the XPIC System
ROI-S05750 INSTALLATION2-109
INSTALLATION ROI-S057502-1102.10  SONET OC-3 NLite E Frame GroundingIn mounting the IDU and ODU, perform frame grounding.  The location of the frame grounding in each IDU and ODU is shown in Fig. 2-8, and the connection for frame grounding is shown in Fig. 2-9.1+0 SYSTEMFRAME GROUND TERMINALFG1+1 SYSTEMIDUFGIFLMONRX LEV6-38 GHz ODUSELV!AUX/ALMLCT NMS NE SC IN/OUT EOWPROTECTCALL MMCMAINTMEMORYIDUXIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRNLite EPULL(Blank)GGGSELV!AUX/ALMLCT NMS NE SC IN/OUT EOWPROTECTCALL MMCMAINTMEMORYIDUXIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRNLite EPULLSELV!XIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRPULLGGGGFRAME GROUND TERMINALSELVPWR PULLPWRALM FUSE (250V/8AH)− 43VGOUTSTDGSELVPWR PULLPWRALM FUSE (250V/8AH)− 43VGOUTSTDGNWA-011060-001   DC-DC CONV UNITSER No.                DATE           ,              WEIGHT  2.5kgMADE IN JAPANNEC Corporation      TOKYO JAPAN1+0 System STD Input : 20    60V    3.4A    1.0A   Output : − 43V    1.3A   1+1 System STD Input : 20    60V    1.3A×2  3.4A    1.0A×2   Output : − 43V   FRAME GROUND TERMINAL FRAME GROUND TERMINALDC-DC CONV (Optional)ALMOC-3 INOC-3 OUTALMOC-3 INOC-3 OUT ONLINEONLINEALMOC-3 INOC-3 OUTALMOC-3 INOC-3 OUT ONLINEONLINENLite ENote: Connect the Frame Ground (G) terminal on the IDU to the mounting rack with the earth cable.  In addition, connect the mounting rack to the indoor earth terminal with the earth cable and connect the G terminal on the ODU to the ground (refer to Fig. 2-9).Fig. 2-10  Location of Frame Ground
EARTH LINEINDOOR EARTH GROUND TERMINALIDUODU COAXIAL CABLEPROTECT AREALIGHTNING RODOUTDOOR EARTH GROUND TERMINAL(EXISTING OR CUSTOMER SUPPLIED)EARTH LINEGROUNDLEVELCautions: 1. Install the ODU within the area protected by lightning rod.2. To avoid surge currents caused by lightning circulating in the equipment earth system, connect the equipment earth system (frame ground) to ground of the lightning rod at ground level.   Note:Frame Ground terminal of the IDU (5 mm square cable (means more than 2.5 mm diameter cable (AWG #10) is recommended to apply for the earth grounding. The proper press fix terminal tool shall be used.)  This connection is an example.RACK30°30°(Grounding Resistance:  less than 10 ohms)This is the buried earth wire.This type of wire is not an insulated winding wire and recommends to make a naked wire.Use a copper grounding conductor to ground the rack.The grounding conductor to the CO GND be connected to the rack.ROI-S05750 INSTALLATION2-111Fig. 2-11  Connection for Frame Grounding (1/2)
LIGHTNING RODEARTH LINEODUFGEARTH LINE*COAXIAL CABLEINDOOR EARTHGROUNDLEVELIDU(Grounding-resistance:less than 10 ohms)Notes:* NEC recommends that frame ground of ODU should be connected to earth line as NEC’s standard installation. EP : Earth Ground Point of tower FG : Frame Ground terminal of the IDU (5 mm square cable (means more than 2.5 mm diameter cable (AWG #10) is recommended to apply for the earth grounding. The proper press fix terminal tool shall be used.)  This connection is an example.ISOLATED FROMTOWER(Grounding-resistance:less than 10 ohms)(Grounding-resistance of tower: less thanGrounding cable for ODU should be connected to the nearest EP of the tower.EP LINE  It lets through the center of the steel tower as much as possible.The coaxial cable lets through the inside of the steel tower.The earth between ODU-IDU lets through the inside of the steel tower.COAXIAL CABLEEARTH LINEThis is the buried earth wire.This type of wire is not an in-sulated winding wire and recommends to make a na-ked wire. 10 ohms)Use a copper grounding conductor to ground the rack.The grounding conductor to the CO GND be connected to the rack.TOWERINSTALLATION ROI-S057502-112Fig. 2-11    Connection for Frame Grounding (2/2)
ROI-S05750 INSTALLATION2-1132.11Waterproof ProtectionAfter cable connection, the following parts should be wrapped by self-bonding tape for waterproof (see Fig. 2-10).POLEANT6/7/8 GHz BAND ODUPOLEANTHYBODUODUThese parts should be wrapped the self-bonding tape tightly, twice or more around the IF cable connector and IF IN/OUT connector of the ODU for waterproof.Note ANote ANote AODUCaution: Before connecting the IF cable between the IDU and ODU, using the circuit tester, check that the resistance of the I/F cable between center conductor and insulation is more than 100 MΩ.self-bonding tapestretchWrap twice the IF IN/OUT connector with self-bonding tape for waterproofing. a half of tape widthODUtwiceFig. 2-12  Location of Connector for Waterproof (1/2)
ODUIF CABLESELF-BONDING TAPEODUIFL CONNECTORNote: The self-bonding tape should be prepared by customer.SELF-BONDING TAPEODUIF CABLE IN CASE OF L−ANGLE6-38 GHz BAND ODUThis part should be wrapped the self-bonding tape tightly, twice or more around the IF cable connector and IF IN/OUT connector of the ODU for waterproof.Caution: Before connecting the IF cable between the IDU and ODU, using the circuit tester, check that the resistance of the I/F cable between center conductor and insulation is more than 100 MΩ.self-bonding tapestretchWrap twice the IF IN/OUT connector with self-bonding tape for waterproofing. a half of tape widthODUtwiceFor 6-52 GHz BAND ODUINSTALLATION ROI-S057502-114114 pagesFig. 2-12  Location of Connector for Waterproof (2/2)
ROI-S05750 INSTALLATION2-115
INITIAL LINE UP ROI-S057503-13. INITIAL LINE UPThis NLite E Section explains instructions for the initial lineup of the equipment. Included is information on start-up, shut-down, IDU and ODU equipment setting, antenna orientation and lineup test between two stations.When the NLite E Monitor is used for RX LEV monitoring, connect the X0818 NLite E Monitor to the ODU. The NLite E Monitor operates on a dry battery (6F22/9V).Notes: 1. Insert the battery with correct polarity.2. When the NLite E Monitor will not be used for extended periods of time, remove the battery to avoid damage from battery leakage and corrosion.3. When the NLite E Monitor will be connected to the ODU, control corresponding ODU to Antenna Alignment mode using LCT in Maintenance ON.
ROI-S05750 INITIAL LINE UP3-23.1 Start-upThe procedure for starting the equipment is shown in Chart 3-1.Warning: 1. The –48 V DC is superimposed on the centre conductor of the IF coaxial cable between the MODEM and the ODU. Connecting test equipment directly to this terminal may damage it and touching the coaxial cable core may cause electrical shock.2. Do not disconnect the IF cable between the MODEM and the ODU in operating condition, to avoid damaging the NLite E , turn the IDU power OFF before connecting/disconnecting the IF cable.3. Do not allow open or short circuit of ODU TX output with the TX power on conditions.  Perform the TX Mute control in the Maintenance mode or turn the PWR switch off at the IDU before disconnecting cable or feeder from the ODU TX output.4. After turning ON the equipment, wait at least 1 minute before turning it OFF again. Repeatedly turning the power ON and OFF within a short interval may cause the NLit E to fail.Caution: 1. In a system using the OPTICAL OC-3 INTFC, do not stare at the laser beam or look at it directly with optical instruments. Otherwise, it may hurt your eyes (Class 1 Laser Product).2. Be careful top surface above MODEM of the IDU is hot in operation.3. When replacing the MODEM, OC-3 INTFC or DC-DC CONV (optional) turn off the PWR switch and disconnect all cables connected to the module which is to be replaced.4. When dismounting the ( ) INTFC, turn off the PWR switch on the MODEM and disconnect all cables connected to the ( ) INTFC.5. In the SONET XPIC system, the system parameter setup must be performed at the Master station first, then at the Sub Station.6. In the SONET XPIC system, the Main Master and Sub Master channels must be connected to one dual polarized antenna.
INITIAL LINE UP ROI-S057503-3Chart 3-1 Start-upCaution: Do not apply a voltage to the equipment that varies sharply. The equipment may operate improperly.Caution: Do not remove/connect the IF cable with the IDU power ON.  Turn the IDU power OFF before connecting/disconnecting the IF cable, or equipment may be damaged.Apparatus:Suitable ScrewdriverDigital MultimeterStep ProcedureNotes: 1 The ODU power is supplied from the IDU1+0 SYSTEM1 Check that the IF cable between the MODEM and the ODU is firmly connected,2 Before connecting the power cable connector to the MODEM, check that the SELV input voltage is −48V (allowable range; within –40.5 to –57 V) with the digital multimeter, (see Fig. 3-1), 3 Pull out the PWR switch lever and turn on,4 Confirm that the PWR indicator on the MODEM is ON.1+1 SYSTEM1 Check that the IF cable between the No.1 MODEM and the No. 1 ODU is connected,2 Before connecting the power cable connector to the No.1 MODEM, check that the SELV input voltage is −48V (allowable range, within –40.5 to –57 V) with the digital multimeter, (see Fig. 3-1), 3 Pull out the PWR switch lever and turn on, (see Fig. 3-1),4 Confirm that the PWR indicator on the No.1 MODEM is ON.5 Repeat steps 1 to 3 for No.2 MODEM,6 Confirm that PWR indicator on the No.2 MODEM is ON.
PWR SWITCHSELV1+1 CONFIGURATION      IDUPWR SWITCHSELV!AUX/ALMLCT NMS NE SC IN/OUT EOWPROTECTCALL MMCMAINTMEMORYIDUXIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRNLite E PULL(Blank)GGGSELV!AUX/ALMLCT NMS NE SC IN/OUT EOWPROTECTCALL MMCMAINTMEMORYIDUXIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRNLite E PULLSELV!XIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRPULLGGGGPWR LED1+0 CONFIGURATION      IDUPWR LEDSELVPWR SWITCHPWR LED SELVMODEMNo.1 MODEMNo.2 MODEMCaution: The NLite E  operates only negative voltage (–48 V). Therefore, the power supply system for the existing equipment which is used floating power supply (–20 to –60 V/+20 to +60 V) must not be connected to the NLite E .4213GND –48 VPOWER SUPPLYNo.1 POWER SUPPLY3124GND –48 VNo.2 POWER SUPPLY3124GND –48 VALMOC-3 INOC-3 OUTALMOC-3 INOC-3 OUT ONLINEONLINEALMOC-3 INOC-3 OUTALMOC-3 INOC-3 OUT ONLINEONLINEROI-S05750 INITIAL LINE UP3-4Fig. 3-1  DC Power cable Connection and Power ON/OFF (1/2)
INITIAL LINE UP ROI-S057503-5Chart 3-1 (Cont’d)Step ProcedureNote: 1 The ODU power is supplied from the IDUDC Power Connection-2 (DC-DC CONV)1+0 SYSTEM1 Check that the IF cable between the MODEM and the ODU is connected,2 Connect the power cable to –43 V/OUT of the DC DC CONV and SELV of the MODEM as shown in Fig 3-1 (2/2),3 Before connecting the power cable connector to the SELV of the DC-DC CONV, check that the rated input voltage is  −24V/−48V (allowable range; within –20 to –60 V) or +24V/+48V (allowable range; within +20 to +60 V) with the digital multimeter, (see Fig. 3-1), 4 Pull out the PWR switch lever of the DC-DC CONV and turn on,5 Confirm that the PWR indicator on the DC-DC CONV is ON,6 Pull out the PWR switch lever of the MODEM and turn on,7 Confirm that the PWR indicator on the MODEM is ON.1+1 SYSTEM1 Check that the IF cable between the No.1 MODEM and the No. 1 ODU, is connected,2 Connect the power cable to –43 V/OUT of the No.1 DC DC CONV and SELV of the No.1 MODEM as shown in Fig 3-1 (2/2),3 Before connecting the power cable connector to the SELV of the DC-DC CONV, check that the rated input voltage is  −24V/−48V (allowable range; within –20 to –60 V) or +24V/+48V (allowable range; within +20 to +60 V) with the digital multimeter, (see Fig. 3-1), 4 Pull out the PWR switch lever of the No.1 DC-DC CONV and turn on,5 Confirm that the PWR indicator on the No.1 DC-DC CONV is ON,
ROI-S05750 INITIAL LINE UP3-6Chart 3-1 (Cont’d)Step Procedure 6 Pull out the PWR switch lever of the No.1 MODEM and turn on,7 Confirm that the PWR indicator on the No.1 MODEM is ON,8 Repeat steps 1 to 7 for No.2 MODEM,9 Confirm that PWR indicator on the No.2 MODEM is ON.
PWR SWITCH (IDU)SELV  IDU0 V/(or +20 to +60V) –20 to  –60V/(or 0V)SELV!AUX/ALMLCT NMS NE SC IN/OUT EOWPROTECTCALL MMCMAINTMEMORYIDUXIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRNLite E PULLGGG1+0 CONFIGURATIONPOWER SUPPLYPWR LEDMODEMNo.1 POWER SUPPLY0 V/(or +20 to +60V) –20 to  –60V/(or 0V)–20 to  –60V/(or 0V)0 V/(or +20 to +60V) SELVPWR PULLPWRALM FUSE (250V/8AH)− 43VGOUTSTDGSELVPWR PULLPWRALM FUSE (250V/8AH)− 43VGOUTSTDGNWA-011060-001   DC-DC CONV UNITSER No.                DATE           ,              WEIGHT  2.5kgMADE IN JAPANNEC Corporation      TOKYO JAPAN1+0 System STD Input : 20    60V    3.4A    1.0A   Output : − 43V    1.3A   1+1 System STD Input : 20    60V    1.3A×2  3.4A    1.0A×2   Output : − 43V   SELVPWR PULLPWRALM FUSE (250V/8AH)− 43VGOUTSTDGSELV!AUX/ALMLCT NMS NE SC IN/OUT EOWPROTECTCALL MMCMAINTMEMORYIDUXIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRNLite E PULLSELV!XIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRPULLGGGGCaution: The NLite E  operates only negative voltage (–48 V). Therefore, the power supply system for the existing equipment which uses a floating power supply (–20 to –60 V/+20 to +60 V) must not be connected to the NLite E .No.1 MODEMNo.2 MODEMNo.1 PWR SWITCHNo.1 SELVNo.2 SELVNo.1 SELVNo.2 SELVNo.2 PWR SWITCHNo.1 PWR SWITCHNo.2 PWR SWITCH–43 V/OUTNo.1 –43 V/OUT No.2 –43 V/OUT42134213No.2 POWER SUPPLY4213DC-DC CONV UNITDC-DCCONVALMOC-3 INOC-3 OUTALMOC-3 INOC-3 OUT ONLINEONLINEALMOC-3 INOC-3 OUTALMOC-3 INOC-3 OUT ONLINEONLINEINITIAL LINE UP ROI-S057503-7Fig. 3-1  DC Power cable Connection and Power ON/OFF (2/2)
ROI-S05750 INITIAL LINE UP3-83.2 Shut-downThe shut-down procedures for the equipment is shown in Chart 3-2.Warning: After turning ON the equipment, wait at least 1 minute before turning it OFF again.  Repeatedly turning the power ON and OFF with in a short interval may cause the IDU/ODU to fail.Chart 3-2 Shut-downStep Procedure1+0 SYSTEM1 Pull out the PWR switch lever on the MODEM and turn off the PWR switch (see Fig. 3-1),2 Confirm that all LED indicators on the IDU are OFF.1+1 SYSTEMNote: When turn OFF the IDU and ODU in 1+1 configuration, turn OFF power for standby side first, then working side.When turn OFF the IDU and ODU in working channel only, switchover the working to standby channel with TX and RX SW using LCT. (see Chart 3-8)1 Pull out the PWR switch lever on the corresponding MODEM is to be shut down, then turn off (see Fig. 3-1).2 Confirm that the PWR indicator on the MODEM is OFF.3 Pull out the PWR switch lever on the other MODEM, then turn off the PWR switch. (see Fig. 3-1).4 Confirm that all LED indicators on the IDU are OFF.
INITIAL LINE UP ROI-S057503-93.3 Initial SettingThe initial setup of the IDU/ODU is performed using the PC according to Table 3-1.For the details operation of the PC setup for connecting LCT, refer to the NLite E  LCT Operation Manual in Section IV Appendix.Table 3-1  Initial Setup ItemsSetup Order Setup Item LCT1. Equipment Setup Chapter 32. Date and Time Chapter 6.33. Provisioning Chapter 74. Relay/House Keeping Chapter 7Note: The “Equipment Setup” must be set properly every items before “Provisioning” setup.  The “Provisioning” setup must be performed based on the “Equipment Setup”.LCT Access Cable LCT 1+1 CONFIGURATIONSELV!AUX/ALMLCT NMS NE SC IN/OUT EOWPROTECTCALL MMCMAINTMEMORYIDUXIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRNLite E PULL(Blank)GGGSELV!AUX/ALMLCT NMS NE SC IN/OUT EOWPROTECTCALL MMCMAINTMEMORYIDUXIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRNLite E PULLSELV!XIF IN XIF OUTIF IN/OUT TXRXRESETXPIC CTRL XPICPWRODUMD/CBL PWRPULLGGGG1+0 CONFIGURATIONPC for LCT USBALMOC-3 INOC-3 OUTALMOC-3 INOC-3 OUT ONLINEONLINEALMOC-3 INOC-3 OUTALMOC-3 INOC-3 OUT ONLINEONLINEFig. 3-2  LCT Connection
ROI-S05750 INITIAL LINE UP3-103.3.1 Equipment SetupIn initial lineup, the “Equipment Setup” must be performed using LCT.Chart 3-3 Equipment SetupRefer to the NLite E  LCT Operation Manual in Section IV Appendix. for the details of “3. Equipment Setup”. The Equipment Setup items to be setup for the SONET systems are as follows:Equipment Setup Items for SONET Systems• User Interface • Redundancy Setting• INTFC• INTFC Main (WORK) *1• INTFC SUB (PROT) *1•XPIC Usage  *2• APS Function *3• Modulation Scheme• Transmission Capacity• TX RF Frequency• RX RF Frequency *5• Frame ID• TX Power Control• LAN Port Usage *4• LAN Capacity *4• TX Start Frequency• TX Stop Frequency• Frequency Step• Shift Frequency• Upper/Lower•Sub BandNotes:*1  For SONET only.*2 When the SONET XPIC is configured, set Main Master and Sub Master. Set to Not Used in other configurations. The TX/RX frequency for the Main Master and Sub Master channels must be set to the same values.  The Main Master and Sub Master channels must be connected to one dual polarized antenna. The reference local frequency and the action control of the ATPC/MTPC are applied from the Main Master channel to the Sub Master channel.*3  For SONET APS only.*4 For LAN transmission only.*5 There is two types ODU for the RX RF Frequency setup mode.Type 1.When the transmitting frequency is set, the receiving frequency is automatically assigned.Type 2.When the transmitting frequency is set, the receiving frequency is automatically assigned and assignment of it in manual is also available.
INITIAL LINE UP ROI-S057503-113.3.2 Provisioning Setup for SONETIn initial lineup, the “Provisioning” Setup must be performed using LCT.Chart 3-4 Provisioning Setup (SONET)Refer to the NLite E  LCT Operation Manual in Section IV Appendix. for details of the “7. Provisioning Setup”. The Provisioning Setup items to be setup for SONET systems are as follows:Provisioning Setup for SONET system• BER Threshold Setting• Sub Interface *1• SC Assignment• LAN Port Setting *2• OC-3 Setting• TX Power Control*3• Condition for TX/RX SW• Condition for APS• Relay Setting• TCN Threshold(15min)• TCN Threshold(1day)• PMON Select• Others *3Note: *1:For LAN transmission only.*2:For LAN transmission only.*3:Set to required TX power level in MTPC mode when it is going to perform the Antenna Orientation.*4:Optional items
ROI-S05750 INITIAL LINE UP3-123.4 Antenna OrientationAfter the initial setup has been completed, an antenna orientation will be performed between two stations according to the procedures in Chart 3-6.Chart 3-5 Antenna OrientationApparatus :Digital Multimeter with test leads or X0818 NLite E MonitorWrenchHeadset Step Procedure1 Connect the PC to the LCT port on the NLite E  IDU using USB cable, (see Fig. 3-2)2 At each station, set “Maintenance1” from Maintenance in LCT Menu,LCT MENUAlarm/StatusEquipment SetupInventoryAUX I/OMaintenanceProvisioningMeteringPMON(History)Maintenance1Maintenance2 Note: In Maintenance “On” condition, every external Alarm outputs, excluding Maintenance/PS/CPU (IDU) ALM, are masked and remote control can not be performed. 3 Click and select for the following control items in “Maintenance1”, Note: Retain the present status for other control items.Note: When the TX power control mode is set to ATPC, set it to MTPC and required level for the NLite E link on the “Equipment Setup” and “Provisioning”.
INITIAL LINE UP ROI-S057503-13Chart 3-5 (Cont’d)Step Procedure• TX SW Manual Control: Fix No.1 or No.2 (in 1+1 configuration)• RX SW Manual Control: Fix No.1 or No.2 (which is the same side fixed by TX SW in 1+1 configuration)• TX Power Control: MTPC in Equipment Setup(at opposite site) Required level in Provisioning• CW Control: When the Antena Alignment Mode is not(at opposite site) selected, set manually to On. • XPIC Control Local: Fix Forced Reset  in XPIC configuration.• Antenna Alignment Mode: Select On (in 1+0 configuration) (Set No.1 or No.2 which is the same side fixed by TX SW and RX SW in 1+1 configuration)--- Maintenance 1 ---Item Value SettingMaintenace On Off    On SetTX SW Manual Control  No.1 Auto   No.1  No.2 SetRX SW Manual Control  No.1 Auto   No.1  No.2 SetRX SW  Maintenace Mode ManualMTPC Manual Control(No.1)  On Off    On SetMTPC Manual Control(No.2)  On Off    On SetTX Mute Control(No.1)  Off Off    On SetTX Mute Control(No.2)  Off Off    On SetCW Control(No.1)  Off Off    On SetCW Control(No.2) Off Off    On SetIF Loopback (No.1) Off Off    On SetIF Loopback (No.2) Off Off    On SetMain Loopback (Near End) Off Off    On SetMain Loopback (Far End) Off Off    On SetLinearrizer Control(No.1)  Auto Auto    Forced Reset SetLinearrizer  Control(No.2) Auto Auto    Forced Reset SetXPIC Control Local(No.1)  Auto Auto    Forced Reset SetXPIC Control Local(No.2) Auto Auto    Forced Reset SetXPIC Control Remote(No.1)  Auto Auto    Forced Reset SetXPIC Control Remote(No.2) Auto Auto    Forced Reset Set--- Offline Maintenance ---DADE Adjust ... DADE    Offset DADE    DADE Off SetRF SUB Band Select (No.1) ... A SetRF SUB Band Select (No.2) ... A SetAntenna Alignment Mode(No.1)  On  Off    On SetAntenna Alignment Mode(No.2) On  Off    On SetNote: In  Antenna Alignment Mode “On” condition, controls between IDU and ODU are restricted.
ROI-S05750 INITIAL LINE UP3-14Chart 3-5 (Cont’d)Step Procedure4 At receiving station, remove a cap from the RX LEV MON jack, 5 At each station connect the digital multimeter or NLite E Monitor to the RX LEV MON jack on the ODU,Note: In order to measure exact performance of AGC V, it is mandatory required to set Antenna Alignment Mode to ON. The AGC voltage indication is not guaranteed outside Antenna Alignment Mode.It is necessary to set to Antenna Alignment Mode when monitor the RX level with the NLite E Monitor unit.6 At each station, adjust the azimuth and elevation angle of the antenna alternately so that the measured voltage becomes maximum,Note: The relation of the RX INPUT LEVEL versus RX LEVEL MON(V) is shown below. RX LEVEL MON vs RX INPUT LEVEL (Typical)RX INPUT LEVEL [dBm]-80 -70 -60 -50 -40 -30 -200.5011.522.533.544.5RX LEVEL MON [V]
INITIAL LINE UP ROI-S057503-15Chart 3-5 (Cont’d)Step ProcedureRX LEV MON123450VOWNLite E MONITORRX LEV/OW INFGIFLMONRX LEVNotes 1: It is necessary to set to the Antenna Alignment Mode using PC for LCT when monitor the RX level with the NLite E MONITOR unit.2: The RX LEV MON terminal on the ODU (conformed to IEC61169-24).3: The RX LEV MON  terminal must be capped for waterproof.ODUDIGITAL MULTIMETERNLite EFig. 3-3  Antenna Orientation Test SetupNote: The fixed bolts and nuts to be used for the antenna orientation differ with antenna bracket types, refer to antenna bracket shown in Fig. 3-4 (1/4) to (4/4).
ROI-S05750 INITIAL LINE UP3-16Safety Guideline for Microwave Radiation HazardThe Microwave and Millimeter-wave that NLite E series are transmitting is at a very small radiation level and never has been reported to effect human health. Advanced countries concerned about health hazards have started to regulate the radiation levels. The operator should not work near the parabolic antenna during RF transmission. The area in front of and to the side of the antenna show high radiation levels. Please see below figure and calculation sample 1. The front side of antenna presents a high power density in the antenna beam area. Therefore, the user of this system should pay attention not to radiate the beam against humans at any time. (Please refer below calculation sample 2)ODU- 90 to +90 degrees   ANTENNAHazard Area of RadiationIn addition, the Power density and Field strength level is calculated by equation below.                                                  10            × KPower density S (mW/cm2) =                                                      40 ×  π  × R2P+G−3010Where: P = Output power of ODU (dBm), G = Antenna Gain (dBi), (in consideration of the angle from antenna) K = Reflection factor =2.56 (given), R = Distance between Human and Antenna (m)Calculation example 1, (90 degree side of antenna)NLite E = 18 GHz/+23 dBm, Antenna diameter = 0.6 m, 0 degree antenna gain = 39 dBi, 90 degrees side antenna gain =  −24 dBi, (90 degrees attenuation  = −63 dB), Distance = 0.1 mPower density S (mW/cm2) = 0.0016 ≤ 0.01 Calculation example 2, (0 degree, front side of antenna)NLite E = 7 GHz/+27 dBm, Antenna diameter = 1.8 m, 0 degree antenna gain = 40 dBi, Distance = 100 mPower density S (mW/cm2) = 0.01

Navigation menu