NEC of America 58155 NEC NLite E 155 MB 5.8 GHz Digital Microwave Radio User Manual Part 3

NEC Corporation of America NEC NLite E 155 MB 5.8 GHz Digital Microwave Radio Part 3

User Manual Part 3

Download: NEC of America 58155 NEC NLite E 155 MB 5.8 GHz Digital Microwave Radio User Manual Part 3
Mirror Download [FCC.gov]NEC of America 58155 NEC NLite E 155 MB 5.8 GHz Digital Microwave Radio User Manual Part 3
Document ID1070884
Application IDk4yzpkXsQigMCmwGK8Hcxw==
Document DescriptionUser Manual Part 3
Short Term ConfidentialNo
Permanent ConfidentialNo
SupercedeNo
Document TypeUser Manual
Display FormatAdobe Acrobat PDF - pdf
Filesize105.81kB (1322582 bits)
Date Submitted2009-02-20 00:00:00
Date Available2009-02-20 00:00:00
Creation Date2009-02-20 08:38:42
Producing SoftwareAcrobat Distiller 6.0 (Windows)
Document Lastmod2009-02-20 08:39:36
Document TitleUser Manual Part 3
Document CreatorFrameMaker 8.0

INSTALLATION
ROI-S05750
Chart 2-14 (Cont’d)
Step
Procedure
Recheck that the wire position is as shown in step 5 before
crimping the socket contact (see illustration below).
WIRE SIDE
SOCKET CONTACT
WIRE
Wind the metallic shield tape over the braided shield.
METALLIC SHIELD TAPE
Set the cable into the plug case as shown in figure below. Then,
fix the cable using the cable clamper and two screws.
CABLE CLAMPER
PLUG CASE
2-77
INSTALLATION
ROI-S05750
Chart 2-14 (Cont’d)
Step
Procedure
10
Referring to circle A, fix the drain wire with screw.
11
Referring to circle B, insert each wire to the specified position
(Refer Interface Terminals and Jacks for IDU in Section II
OPERATING EQUIPMENT.). Insert the socket contacts into
the upper and lower row positions while taking care that the
socket contacts are inserted the right way.
CIRCLE A
SCREW
DRAIN WIRE
CIRCLE B
2-78
INSTALLATION
ROI-S05750
Chart 2-14 (Cont’d)
Step
12
Procedure
Fix the plug case with two screws, as shown in the figure.
SCREW
PLUG CASE
2-79
INSTALLATION
ROI-S05750
Chart 2-15 Terminating IF Coaxial Cable with TNC-P
Connector (L Angle Type) (HIROSE made)
used for IDU IF IN/OUT
Step
Procedure
Note: It is recommended that TNC (Male) L-angle connector for the
8D-FB IF cable is used to connect it to the IDU. When the N
(Male) straight connector is attached to the 5D-FB or 10D-FB
IF cable, use of the TNC (Male) - N (Female) (NJ-TNCP-LA)
L-angle adapter is needed.
Pass the tightening nut, the washer and the gasket on the cable in
the order shown in the figure.
Then, strip the cable jacket in the diameter shown in the figure.
[Applicable cable : 8D-FB-E]
Note: Be careful of insertion direction for the gasket and the tightening nut.
Note: Be careful not to damage the outer conductor.
Note: Do not reuse the gasket because the clamp deforms it after
tightening.
Insert the clamp to clamp the stripped cable jacket end. Open the
end of the outer conductor a little,
Insert the hood between the plastic tape with aluminium foil and
the outer conductor,
Note: Use the insertion stick to open the hole of about φ9. No gap is
allowed in between the clamp, the outer conductor and the hood.
Clamp
Hood
2-80
INSTALLATION
ROI-S05750
Chart 2-15 (Cont’d)
Step
Procedure
After inserting the hood, cut off the plastic tape with aluminium
foil and the dielectric at A-surface,
Cut off the part of the outer conductor exceeding the clamp rim
with a knife,
Check that distance between the tip of the center conductor and
A-surface is 6 to 7 mm,
If it is more than 7 mm, cut the center conductor to correct
length,
Note: Be careful not to damage the center conductor,
Note: Chamfer at the tip of the center conductor,
Note: There shall be no evidence of deviation or deformation or burr at
the tip of the center conductor.
Clamp
2-81
INSTALLATION
ROI-S05750
Chart 2-15 (Cont’d)
Step
Procedure
Insert the insulation washer over the center conductor, and
engage it with the F/F contact,
Note: No gap is allowed in between the F/F contact, the insulation
washer, and the dielectric.
Note: The assembly unit after the completion of this process is called
“block”.
Combine the convex part of the clamp to the concave part of the
gasket, Then insert this block to the shell,
Note: Insert the hood until it hits the B-surface.
2-82
INSTALLATION
ROI-S05750
Chart 2-15 (Cont’d)
Step
Procedure
Tighten the tightening nut sufficiently until the gasket is cut by
the clamp and the tip of the clamp hits the washer,
Note: Torque for the tightening nut shall be 8 to 30N•m.
Note: When tightening the nut, tighten with wrench at the wrench at the
wrench flat.
Note: Distance between the tightening nut and the LP shell is 1.85 to
2.1 mm for reference.
Tighten the nut sufficiently.
L-type dimension and cutting length of the cable.
Specified length L: Cutting length L−25.
2-83
INSTALLATION
ROI-S05750
Chart 2-16 Terminating Coaxial (IF Signal) with N-P
Connector (L Angle Type) used for ODU IF
IN/OUT (KOMINE made)
Step
Procedure
Note: It is recommended that TNC (Male) L-angle connector for the
8D-FB IF cable is used to connect it to the IDU. When the N
(Male) straight connector is attached to the 5D-FB or 10D-FB
IF cable, use of the TNC (Male) - N (Female) (NJ-TNCP-LA)
L-angle adapter is needed.
First fit the tying metal, washer and gasket on the cable.
GASKET
WASHER
TYING METAL
CABLE
Strip back the cable sheath, taking care not to damage the
braided shield, and fit the clamp.
CLAMP
9 mm
Fold back the braided shield (separating the strands of the braid)
and trim it.
Note: Pay attention not to damage the plait.
Insert the ferrule.
FERRULE
2-84
INSTALLATION
ROI-S05750
Chart 2-16 (Cont’d)
Step
Procedure
Fit the bushing.
BUSH
Cut the aluminium foil and inner insulator away along the
bushing and retain the inner conductor.
Taper the edge of the center conductor using a file as shown in
the enlarged view below.
Note: Pay attention not to let
protrusions and indents to occur.
2-85
INSTALLATION
ROI-S05750
Chart 2-16 (Cont’d)
Step
Procedure
Mount the contact onto the center conductor and mount the
insulator onto the contact.
INSULATOR
10
CONTACT
Insert the cable into the shell.
Tighten the tying metal by wrench using the wrench points.
(Tighten with torque of 4 to 10 N·m)
LESS THAN 0.1 mm
(USUALLY NO GAPS)
WRENCH POINT
2-86
INSTALLATION
ROI-S05750
Chart 2-17 Terminating IF Coaxial Cable with N-P
Connector (L Angle Type) used for the ODU
IF IN/OUT (HIROSE made)
Step
Procedure
Note: It is recommended that TNC (Male) L-angle connector for the
8D-FB IF cable is used to connect it to the IDU. When the N
(Male) straight connector is attached to the 5D-FB or 10D-FB
IF cable, use of the TNC (Male) - N (Female) (NJ-TNCP-LA)
L-angle adapter is needed.
Pass the tightening nut, the washer and the gasket on the cable in
the order shown in the figure.
Then, strip the cable jacket in the diameter shown in the figure.
[Applicable cable : 8D-FB-E]
Note: Be careful of insertion direction for the gasket and the tightening nut.
Note: Be careful not to damage the outer conductor.
Note: Do not reuse the gasket because the clamp deforms it after
tightening.
Insert the clamp to clamp the stripped cable jacket end. Open the
end of the outer conductor a little,
Insert the hood between the plastic tape with aluminium foil and
the outer conductor,
Note: Use the insertion stick to open the hole of about φ9. No gap is
allowed in between the clamp, the outer conductor and the hood.
2-87
INSTALLATION
ROI-S05750
Chart 2-17 (Cont’d)
Step
Procedure
After inserting the hood, cut off the plastic tape with aluminium
foil and the dielectric at A-surface,
Cut off the part of the outer conductor exceeding the clamp rim
with a knife,
Check that distance between the tip of the center conductor and
A-surface is 6 to 7 mm,
If it is more than 7 mm, cut the center conductor to correct
length,
Note: Be careful not to damage the center conductor,
Note: Chamfer at the tip of the center conductor,
Note: There shall be no evidence of deviation or deformation or burr at
the tip of the center conductor.
2-88
INSTALLATION
ROI-S05750
Chart 2-17 (Cont’d)
Step
Procedure
Insert the insulation washer over the center conductor, and
engage it with the F/F contact,
Note: No gap is allowed in between the F/F contact, the insulation
washer, and the dielectric.
Note: The assembly unit after the completion of this process is called
“block”.
Combine the convex part of the clamp to the concave part of the
gasket, Then insert this block to the shell,
Note: Insert the hood until it hits the B-surface.
2-89
INSTALLATION
ROI-S05750
Chart 2-17 (Cont’d)
Step
Procedure
Tighten the tightening nut sufficiently until the gasket is cut by
the clamp and the tip of the clamp hits the washer,
Note: Torque for the tightening nut shall be 8 to 30N•m.
Note: When tightening the nut, tighten with wrench at the wrench at the
wrench flat.
Note: Distance between the tightening nut and the LP shell is 1.85 to
2.1 mm for reference.
Tighten the nut sufficiently.
L-type dimension and cutting length of the cable.
Specified length L: Cutting length L−25.
2-90
INSTALLATION
ROI-S05750
Chart 2-18 Terminating IF Coaxial Cable
with N-P Connector (Straight Type) used for
ODU IF IN/OUT (HIROSE made)
N-type connector is used for the ODU side.
Note: When the N (Male) straight connector is attached to the IF
coaxial cable for the IDU IF IN/OUT, use of the TNC (Male) - N
(Female) (NJ-TNCP-LA) L-angle adapter is needed.
Step
Procedure
First fit the lock nut, washer and gasket on the cable as shown.
LOCK NUT
WASHER
GASKET
CABLE
Strip back the cable sheath, taking care not to damage the
braided shield, and fit clamp A.
CLAMP A
CONNECTOR
CABLE
N260
5D-FB
25 mm
N227
8D-FB
25 mm
N228
10D-FB
27 mm
N229
12D-FB
27 mm
Fold back the braided shield (separating the strands of the braid)
and trim it.
2-91
INSTALLATION
ROI-S05750
Chart 2-18 (Cont’d)
Step
Procedure
Cut away the insulation from the center conductor and fit clamp
B. Be sure not to cut or scratch the conductor while stripping
the insulation.
1.0 mm
CLAMP B
CUT
Cut the center conductor. Taper the end of the center conductor
using a file as shown in the enlarged view below.
12 mm
Mount the center contact onto the center conductor as shown.
Note: Insert the center contact into insulator (1.5 mm).
1.5 mm
CENTER CONTACT
2-92
INSTALLATION
ROI-S05750
Chart 2-18 (Cont’d)
Step
Procedure
Mount the insulator onto the center contact.
TAPERING SIDE
INSULATOR
Insert the cable into the connector shell.
CONNECTOR SHELL
Tighten the lock nut.
Less than 0.5 mm
LOCK NUT
2-93
INSTALLATION
ROI-S05750
Chart 2-19 Terminating IF Coaxial Cable
with N-P Connector (Straight Type) used for
ODU IF IN/OUT (KOMINE made)
N-type connector is used for the ODU side.
Note: When the N (Male) straight connector is attached to the IF
coaxial cable for the IDU IF IN/OUT, use of the TNC (Male) - N
(Female) (NJ-TNCP-LA) L-angle adapter is needed.
Step
Procedure
The clamp nut, the washer and the gasket are inserted in the
cable,
GASKET
WASHER
CLAMP NUT
CABLE
Strip the cable as below and disentangle the braid and insert the
clamp in the cable,
CLAMP
BRAID
25 mm
Do not scratch the braid wire.
Turn the braid on the clamp inserted and cut the braid according
to the paragraph,
FOIL
INSULATOR
2-94
BRAID
PARAGRAPH
INSTALLATION
ROI-S05750
Chart 2-19 (Cont’d)
Step
Procedure
Cut the cable-insulator according to the surface that is turned the
braid and insert the ferrule,
The surface that is turned the braid.
FERRULE
CENTER CONDUCTOR
Do not scratch the center conductor.
Insert the insulator,
INSULATOR
Cut the center-conductor as following size. Process the tip of
center-conductor like a taper with a file. (Do not have a curve
and burr.) Insert the center-contact in the center-conductor and
insert the insulator in the center-contact,
INSULATOR
CENTER CONTACT
12 mm
Processing chart of the
tip of the center-conductor.
2-95
INSTALLATION
ROI-S05750
Chart 2-19 (Cont’d)
Step
Procedure
Connector body is fit to the cable.
Fit in the cable end into the body and screw the clamp nut by
your hand first and tighten it with a torque wrench.
Confirm the space that it is less than 0. 5 mm between the body
and the cramp nut.
BODY
18/2 flats
CLAMP NUT
less than 0.5 mm
Tightening torque is more than 9.8 N•m (100kgf•cm)
Note: Use torque wrench.
2-96
INSTALLATION
ROI-S05750
Chart 2-20 Terminating Power Supply Cables with
Molex Connector
Step
Procedure
Note: Do not bend this part.
Remove 3.0 to 3.5 mm of insulation.
CABLE
AWG#18-24
3.0 to 3.5 mm
POWER SUPPLY CABLE
FOR 48 V, 1A
2-97
INSTALLATION
ROI-S05750
Chart 2-20 (Cont’d)
Step
Procedure
Set the socket contact to position 1 or 2 of the hand crimping
tool.
HAND CRIMPING OUTSIDE DIAMETER SET
TOOL TYPE
OF CABLE
POSITION
57026-5000
57027-5000
HAND CRIMPING TOOL
57026-5000 Molex
or 57027-5000
φ 1.5 to 1.8
φ 1.8 to 2.2
φ 2.3 to 2.6
φ 2.6 to 3.1
Squeeze the handle of the hand crimping tool, insert cable into
socket contact.
The cable should fit, so insulation and bare wire are arranged as
shown.
Squeeze the handle of the hand crimping tool until the ratchet is
released.
INSULATION BARREL
WIRE BARREL
WIRE STRIP LENGTH
2-98
INSTALLATION
ROI-S05750
Chart 2-20 (Cont’d)
Step
Procedure
Twist cables for the power supply,
Note: Twist power cables to suppress inductive interference signals.
Insert the socket contacts into the power connector until they
lock.
−48 V (*1)
POWER CONNECTOR
GND (*2)
Note : For H3040 DC-DC CONV,
(*1):−20 to −60 V (or 0 V)
(*2):0 V (or +20 to +60V)
2-99
INSTALLATION
ROI-S05750
Chart 2-21 BNC Connector for 3C-2V Coaxial Cable
Assembling, Solder Type
The following explains how to assemble BNC solder type as an example.
LOCK NUT
CLAMP 1
CLAMP 2
SHELL
(15.5 mm)*
(39/64”)*
Step 1. Slide the lock nut onto the cable.
Strip the cable sheath, taking care
not to damage the braided shield
wires, and fit CLAMP 1.
Note *:Stripping measurements vary depend on the BNC
trim
Step 2. Fold back the braided shield wire
around the CLAMP 1 (without
separating the strands of the
braid) and trim it.
(7 mm)*
(9/32”)*
Step 3. Cut away the insulator from the
centre conductor and fit CLAMP
2. (Be sure not to cut or scratch
the conductor while stripping the
insulation.)
Note *:Stripping measurements vary depend on the BNC
SOLDERING
Step 4. Solder the pin contact to center
conductor. Use a knife to remove
excess solder.
Step 5. Insert the connectorized cable
into the BNC shell and fasten the
lock nut with a wrench.
2-100
INSTALLATION
ROI-S05750
Chart 2-22 BNC Connector for 3C-2V Coaxial Cable
Assembling, Crimping Type
The following explains how to assemble BNC crimping type as an example.
BNC plug
braid tube
contraction sleeve
ferrule
STRIPPING
insulator
Sheath
BNC shell
pin contact
(15 mm)*
(6.3 mm)*
(4 mm)*
Step 1. Strip coaxial cable as illustrated
left, (taking care not to damage
braided shield wire),
center conductor
dielectric
shield wire
Step 2. Cut braided shield wire (without
unravel the strands of braid) and
trim it,
Note*: Stripping measurements vary depending on the
BNC type.
Step 3. Cut dielectric, (be sure not to cut
or scratch the centre conductor
contraction sleeve ferrule
while stripping the dielectric),
Step 4. Slide contraction sleeve
ferrule onto the cable,
and
Step 5. Fan braided shield wire,
braid tube
insulator
pin contact
Step 6. Slide braid tube and insulator
among braided shield wire and
dielectric,
Step 6. Slide pin contact until it bottoms
against the centre conductor,
2-101
INSTALLATION
ROI-S05750
Chart 2-22 (Cont’d)
Step 7. Crimp pin contact,
crimp
crimping area
crimping tool
pin contact
Step 8. Slide carefully the cable into BNC
shell until insulator butts against
BNC body,
ferrule
Step 9. Slide ferrule over shield wire until
it bounds against the BNC shell
body,
crimp
Step 10.Crimp ferrule as close as possible
to the BNC shell body and trim the
excess of braid,
trim
crimping tool
Crimp ferrule as close as possible.
2-102
use suitable crimping size
INSTALLATION
ROI-S05750
Chart 2-22 (Cont’d)
contraction sleeve
Step 11.Position contraction sleeve over
ferrule and BNC,
heated air
Step 12.Heat contraction sleeve until it
contracts.
2-103
INSTALLATION
ROI-S05750
Chart 2-23 D-Sub High Density Crimp Contacts
Assembly
The following explains how to assemble high density crimp contacts used
for HARTING hand crimp tool as an example.
Crimping/inserting contacts process
Stranded wire
Jacket
Step 1. Strip the jacket for 2.5 −0/+0.5 mm
as shown left and check if stranded wire
is not damaged,
2.5 −0/+0.5 mm
Applicable wire size : 0.14 - 0.22 mm2 (AWG26 - 24),
stranded, maximum insulation: φ1.38 mm
Stamped male contacts : 09 56 000 8175 (Level S4),
High density male connectors : 09 56 300 5601 (#44)
Crimp Tool
(09 88 999 0596)
Step 2. Place the handles in the open
position as shown left,
Note: When the handles are in close position, squeeze handles completely until safety ratchet is
released.
Indication of the part number
Chamber for 0.22 mm2 (AWG 24)
Step 3. Select the suitable chamber for
the selected wire,
Step 4. Insert contact
chamber,
Chamber for 0.14 mm2 (AWG 26)
in
the
selected
Step 5. Insert the prepared wire in the
contact,
Step 6. Squeeze the handles together
completely until the safety ratchet
clicks to open,
Step 7. Take out the crimped contacts
from the chamber. Check if it
should not be scratched or
transformed.
2-104
INSTALLATION
ROI-S05750
Chart 2-23 (Cont’d)
Step 8. After crimping the stranded wire to
the contact using a hand tool, insert
the contact into the contact chamber
with the tool, working from the
wiring side,
Step 9. You can here the contacts snap
home, audible “click”,
Step 10.Check if they are securely in
place with giving the wire a
gentle pull.
Removing crimp contacts
Contact chamber
Wire
Insertion and removal tool
(09 99 000 0513)
Insertion and removal tool
[Removal]
Contact can be removed
together with wire.
[Insertion]
Contact can be inserted
together with wire.
Step 1. Position the tool from the wiring
side as shown left and insert into the
contact chamber. The contact can
then easily be removed from the
wiring side together with itself and
reinserted in a different chamber.
Position the
Insertion and removal tool
Connector
2-105
INSTALLATION
ROI-S05750
2.9 Wiring and Forming
Chart 2-24 Wiring and Forming
Connect cables for, signal interface, power supply, IF IN/OUT
and ground to the proper connector of the IDU.
(1) Connect ground cable to the ground terminal
(2) Connect IF cable to IF IN/OUT connector.
(3) Connect power supply cable to SELV connector.
(4) Connect OC-3 NLite E, Aux. signal cables to proper
connectors.
(5) Connect XIF coaxial cables to opposite IDU. (XPIC
configuration only.)
(6) Connect XPIC CTRL cables to opposite IDU. (XPIC
configuration only.)
Note: When disconnect cables, perform it in revers steps.
Fix the cables using cable binder to the rack as like as indicated
position.
Notes: 1. Do not cross the cables on front of indicators and power
switch used for maintenance.
2. Take suitable bend radius to wiring the IF cable. (e.g.
10D-FB: 70 cm)
3. For the IF cable connection, it is recommended to use
adapter. (Applicable adapters are listed table below).
Table 2-6 IF Cable Adapter
Adapter
IF Cable
TNC(P) - N(J)
2-106
5D-FB
√
8D-FB
√
10D-FB
√
TNC(P) - TNC(J)
√
INSTALLATION
ROI-S05750
Straight Type
Caution
Tighten the TNC-male connector of
IF cable to the IDU with engage
connector nut only using fingers and
holding the cable with another hand.
IDU
IF CABLE
L-Angle Type
IDU
Tighten the engage connector nut
only for the L-angle connector also.
(Tightening Torque : 0.3 to 0.5 N•m
(3 to 5kg•cm))
IF CABLE
L Angle Type
IDU
If rotate other parts of the L-angle
connector as illustrated left, it can
cause connector damage.
IF CABLE
2-107
INSTALLATION
ROI-S05750
NLite E SONET
! IF IN/OUT
XIF IN XIF OUT
PULL
XPIC CTRL
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
XPIC CTRL
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
PWR
XPIC CTRL
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
PWR
XPIC CTRL
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
ALM
PWR
OC-3 OUT
OC-3 IN
ALM
OC-3 OUT
ONLINE
OC-3 IN
ONLINE
FG
! IF IN/OUT
XIF IN XIF OUT
! IF IN/OUT
XIF IN XIF OUT
PROTECT
PULL
LCT
NMS
NE
MAINT
MEMORY
IDU
AUX/ALM
SC IN/OUT
EOW
CALL
MMC
PULL
ALM
OC-3 OUT
OC-3 IN
ALM
OC-3 OUT
ONLINE
OC-3 IN
ONLINE
FG
! IF IN/OUT
XIF IN XIF OUT
PULL
PWR
PROTECT
LCT
NMS
NE
AUX/ALM
FG
NLite E
MAINT
MEMORY
IDU
SC IN/OUT
EOW
CALL
MMC
(1)
Connect XIF cable to between XIF IN (Main Master ) and XIF OUT (Sub
Master), and XIF OUT (Main Master) and XIF IN (Sub Master).
(2)
Connect XPIC CTRL cables to between XPIC CTRL (Main Master) and XPIC
CTRL (Sub Master).
Fig. 2-8 Cable Wiring for the XPIC System
2-108
FG
NLite ES
ROI-S05750
INSTALLATION
2-109
INSTALLATION
ROI-S05750
2.10 SONET OC-3 NLite E Frame Grounding
In mounting the IDU and ODU, perform frame grounding. The location of
the frame grounding in each IDU and ODU is shown in Fig. 2-8, and the
connection for frame grounding is shown in Fig. 2-9.
Note: Connect the Frame Ground (G) terminal on the IDU to the
mounting rack with the earth cable. In addition, connect the
mounting rack to the indoor earth terminal with the earth cable
and connect the G terminal on the ODU to the ground (refer to
Fig. 2-9).
! IF IN/OUT
XPIC CTRL
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
G PULL
ALM
PWR
OC-3 IN
OC-3 OUT
ALM
OC-3 OUT
ONLINE
OC-3 IN
LCT
! IF IN/OUT
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
MAINT
MEMORY
IDU
AUX/ALM
NE
SC IN/OUT
EOW
CALL
ALM
PWR
OC-3 IN
OC-3 OUT
ALM
OC-3 OUT
ONLINE
OC-3 IN
XIF IN XIF OUT
XPIC CTRL
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
PULL
PWR
LCT
NMS
FRAME GROUND TERMINAL
OUT
PWR
ALM
FUSE (250V/8AH)
SELV
CALL
− 43V
PULL
PWR
OUT
STD
MMC
NLite E
RX LEV
MON
IFL
FG
FG
6-38 GHz ODU
Fig. 2-10 Location of Frame Ground
PWR
ALM
DC-DC CONV (Optional)
2-110
EOW
FRAME GROUND TERMINAL
− 43V
STD
SC IN/OUT
1+1 SYSTEM
IDU
FRAME GROUND TERMINAL
NWA-011060-001 DC-DC CONV UNIT
WEIGHT 2.5kg
SER No.
DATE
1+0 System STD Input : 20 60V
3.4A 1.0A Output : − 43V
1.3A
1+1 System STD Input : 20 60V
3.4A 1.0A×2 Output : − 43V
1.3A×2
NEC Corporation TOKYO JAPAN
MADE IN JAPAN
MAINT
MEMORY
IDU
AUX/ALM
NE
ONLINE
NLite E
PROTECT
FUSE (250V/8AH)
SELV
PULL
PWR
! IF IN/OUT
MMC
PULL
XPIC CTRL
NMS
1+0 SYSTEM
FRAME GROUND TERMINAL
XIF IN XIF OUT
NLite E
PROTECT
(Blank)
ONLINE
XIF IN XIF OUT
INSTALLATION
ROI-S05750
LIGHTNING ROD
PROTECT AREA
OUTDOOR EARTH GROUND TERMINAL
(EXISTING OR CUSTOMER SUPPLIED)
30°
30°
EARTH LINE
ODU
COAXIAL CABLE
INDOOR EARTH GROUND TERMINAL
Use a copper grounding conductor to
ground the rack.
The grounding conductor to the CO
GND be connected to the rack.
RACK
IDU
EARTH LINE
This is the buried earth wire.
This type of wire is not an insulated
winding wire and recommends to
make a naked wire.
GROUND
LEVEL
(Grounding Resistance:
less than 10 ohms)
Cautions: 1. Install the ODU within the area protected by lightning rod.
2. To avoid surge currents caused by lightning circulating in the
equipment earth system, connect the equipment earth system
(frame ground) to ground of the lightning rod at ground level.
Note:Frame Ground terminal of the IDU (5 mm square cable (means more
than 2.5 mm diameter cable (AWG #10) is recommended to apply for the
earth grounding. The proper press fix terminal tool shall be used.)
This connection is an example.
Fig. 2-11 Connection for Frame Grounding (1/2)
2-111
INSTALLATION
ROI-S05750
LIGHTNING ROD
TOWER
It lets through the center of the steel
tower as much as possible.
EARTH LINE
ODU
COAXIAL CABLE
FG
EARTH LINE
ISOLATED FROM
TOWER
(Grounding-resistance:
less than 10 ohms)
Grounding cable for ODU should be
connected to the nearest EP of the tower.
EP
EARTH LINE*
(Grounding-resistance:
less than 10 ohms)
The coaxial cable lets through the inside of the steel tower.
The earth between ODU-IDU lets through the inside of the
steel tower.
(Grounding-resistance
of tower: less than
10 ohms)
Use a copper grounding conductor to ground the rack.
The grounding conductor to the CO GND be connected to the rack.
COAXIAL CABLE
INDOOR EARTH
LINE
IDU
This is the buried earth wire.
This type of wire is not an insulated winding wire and
recommends to make a naked wire.
GROUND
LEVEL
Notes:* NEC recommends that frame ground of ODU should be connected to earth line as NEC’s
standard installation.
EP : Earth Ground Point of tower
FG : Frame Ground terminal of the IDU (5 mm square cable (means more than 2.5 mm
diameter cable (AWG #10) is recommended to apply for the earth grounding. The proper
press fix terminal tool shall be used.)
This connection is an example.
Fig. 2-11
2-112
Connection for Frame Grounding (2/2)
INSTALLATION
ROI-S05750
2.11 Waterproof Protection
After cable connection, the following parts should be wrapped by selfbonding tape for waterproof (see Fig. 2-10).
Caution: Before connecting the IF cable between the IDU
and ODU, using the circuit tester, check that the
resistance of the I/F cable between center
conductor and insulation is more than 100 MΩ.
ANT
ANT
POLE
POLE
HYB
ODU
ODU
Note A
Note A
ODU
6/7/8 GHz BAND ODU
Wrap twice the IF IN/OUT connector with
self-bonding tape for waterproofing.
Note A
These parts should be wrapped
the self-bonding tape tightly, twice
or more around the IF cable
connector and IF IN/OUT
connector of the ODU for
waterproof.
self-bonding
tape
stretch
ODU
twice
a half of tape width
Fig. 2-12 Location of Connector for Waterproof (1/2)
2-113
INSTALLATION
ROI-S05750
For 6-52 GHz BAND ODU
This part should be wrapped the
self-bonding tape tightly, twice or
more around the IF cable
connector and IF IN/OUT
connector of the ODU for
waterproof.
ODU
IFL CONNECTOR
Caution: Before connecting the IF cable between the
IDU and ODU, using the circuit tester,
check that the resistance of the I/F cable
between center conductor and insulation is
more than 100 MΩ.
IF CABLE
ODU
Wrap twice the IF IN/OUT connector with
self-bonding tape for waterproofing.
SELF-BONDING TAPE
SELF-BONDING TAPE
self-bonding
tape
ODU
stretch
ODU
6-38 GHz BAND ODU
twice
IF CABLE
a half of tape width
IN CASE OF L−ANGLE
Note: The self-bonding tape should be prepared by customer.
Fig. 2-12 Location of Connector for Waterproof (2/2)
2-114
114 pages
ROI-S05750
INSTALLATION
2-115
INITIAL LINE UP
ROI-S05750
3. INITIAL LINE UP
This NLite E Section explains instructions for the initial lineup of the
equipment. Included is information on start-up, shut-down, IDU and ODU
equipment setting, antenna orientation and lineup test between two
stations.
When the NLite E Monitor is used for RX LEV monitoring, connect the
X0818 NLite E Monitor to the ODU. The NLite E Monitor operates on a
dry battery (6F22/9V).
Notes:
1. Insert the battery with correct polarity.
2. When the NLite E Monitor will not be used for extended
periods of time, remove the battery to avoid damage from
battery leakage and corrosion.
3. When the NLite E Monitor will be connected to the ODU,
control corresponding ODU to Antenna Alignment mode
using LCT in Maintenance ON.
3-1
ROI-S05750
INITIAL LINE UP
3.1 Start-up
The procedure for starting the equipment is shown in Chart 3-1.
Warning: 1. The –48 V DC is superimposed on the centre conductor
of the IF coaxial cable between the MODEM and the
ODU. Connecting test equipment directly to this
terminal may damage it and touching the coaxial cable
core may cause electrical shock.
2. Do not disconnect the IF cable between the MODEM and the
ODU in operating condition, to avoid damaging the NLite E ,
turn the IDU power OFF before connecting/disconnecting
the IF cable.
3. Do not allow open or short circuit of ODU TX output
with the TX power on conditions. Perform the TX Mute
control in the Maintenance mode or turn the PWR switch
off at the IDU before disconnecting cable or feeder from
the ODU TX output.
4. After turning ON the equipment, wait at least 1 minute before
turning it OFF again. Repeatedly turning the power ON and
OFF within a short interval may cause the NLit E to fail.
Caution: 1. In a system using the OPTICAL OC-3 INTFC, do not
stare at the laser beam or look at it directly with optical
instruments. Otherwise, it may hurt your eyes (Class 1
Laser Product).
2. Be careful top surface above MODEM of the IDU is hot in
operation.
3. When replacing the MODEM, OC-3 INTFC or DC-DC CONV
(optional) turn off the PWR switch and disconnect all cables
connected to the module which is to be replaced.
4. When dismounting the ( ) INTFC, turn off the PWR switch on
the MODEM and disconnect all cables connected to the ( )
INTFC.
5. In the SONET XPIC system, the system parameter setup must
be performed at the Master station first, then at the Sub Station.
6. In the SONET XPIC system, the Main Master and Sub
Master channels must be connected to one dual polarized
antenna.
3-2
INITIAL LINE UP
ROI-S05750
Chart 3-1 Start-up
Caution: Do not apply a voltage to the equipment that varies sharply.
The equipment may operate improperly.
Caution: Do not remove/connect the IF cable with the IDU power
ON. Turn the IDU power OFF before connecting/
disconnecting the IF cable, or equipment may be damaged.
Apparatus:
Suitable Screwdriver
Digital Multimeter
Step
Procedure
Notes: 1 The ODU power is supplied from the IDU
1+0 SYSTEM
Check that the IF cable between the MODEM and the ODU is
firmly connected,
Before connecting the power cable connector to the MODEM,
check that the SELV input voltage is −48V (allowable range;
within –40.5 to –57 V) with the digital multimeter, (see Fig. 3-1),
Pull out the PWR switch lever and turn on,
Confirm that the PWR indicator on the MODEM is ON.
1+1 SYSTEM
3-3
Check that the IF cable between the No.1 MODEM and the No.
1 ODU is connected,
Before connecting the power cable connector to the No.1
MODEM, check that the SELV input voltage is −48V
(allowable range, within –40.5 to –57 V) with the digital
multimeter, (see Fig. 3-1),
Pull out the PWR switch lever and turn on, (see Fig. 3-1),
Confirm that the PWR indicator on the No.1 MODEM is ON.
Repeat steps 1 to 3 for No.2 MODEM,
Confirm that PWR indicator on the No.2 MODEM is ON.
INITIAL LINE UP
ROI-S05750
POWER SUPPLY
–48 V
2 1
MODEM
GND
SELV
PWR LED
IDU
! IF IN/OUT
XIF IN XIF OUT
XPIC CTRL
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
1+0 CONFIGURATION
G PULL
ALM
PWR
OC-3 OUT
OC-3 IN
ALM
OC-3 OUT
ONLINE
OC-3 IN
ONLINE
PROTECT
(Blank)
LCT
NMS
NE
NLite E
MAINT
MEMORY
IDU
AUX/ALM
SC IN/OUT
EOW
CALL
MMC
PWR SWITCH
–48 V
GND
–48 V
2 1
GND
2 1
No.1 POWER SUPPLY
No.2 POWER SUPPLY
No.1 MODEM
PWR LED
SELV
! IF IN/OUT
XIF IN XIF OUT
TX
RX
XPIC
RESET
XPIC CTRL
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
PULL
PULL
1+1 CONFIGURATION
ALM
PWR
OC-3 OUT
OC-3 IN
ALM
OC-3 OUT
ONLINE
OC-3 IN
ONLINE
XPIC CTRL
PWR SWITCH
! IF IN/OUT
XIF IN XIF OUT
PWR LED
PWR
ODU
MD/
CBL SELV
SELV
PWR
PROTECT
LCT
NMS
NE
PWR SWITCH
AUX/ALM
NLite E
MAINT
MEMORY
IDU
SC IN/OUT
EOW
CALL
MMC
IDU
No.2 MODEM
Caution: The NLite E operates only negative voltage (–48 V). Therefore, the power supply
system for the existing equipment which is used floating power supply (–20 to –60 V/
+20 to +60 V) must not be connected to the NLite E .
Fig. 3-1 DC Power cable Connection and Power ON/OFF (1/2)
3-4
INITIAL LINE UP
ROI-S05750
Chart 3-1 (Cont’d)
Step
Procedure
Note: 1 The ODU power is supplied from the IDU
DC Power Connection-2 (DC-DC CONV)
1+0 SYSTEM
Check that the IF cable between the MODEM and the ODU is
connected,
Connect the power cable to –43 V/OUT of the DC DC CONV
and SELV of the MODEM as shown in Fig 3-1 (2/2),
Before connecting the power cable connector to the SELV
of the DC-DC CONV, check that the rated input voltage
is −24V/−48V (allowable range; within –20 to –60 V) or
+24V/+48V (allowable range; within +20 to +60 V) with
the digital multimeter, (see Fig. 3-1),
Pull out the PWR switch lever of the DC-DC CONV and turn
on,
Confirm that the PWR indicator on the DC-DC CONV is ON,
Pull out the PWR switch lever of the MODEM and turn on,
Confirm that the PWR indicator on the MODEM is ON.
1+1 SYSTEM
3-5
Check that the IF cable between the No.1 MODEM and the No.
1 ODU, is connected,
Connect the power cable to –43 V/OUT of the No.1 DC DC
CONV and SELV of the No.1 MODEM as shown in Fig 3-1 (2/
2),
Before connecting the power cable connector to the SELV
of the DC-DC CONV, check that the rated input voltage
is −24V/−48V (allowable range; within –20 to –60 V) or
+24V/+48V (allowable range; within +20 to +60 V) with
the digital multimeter, (see Fig. 3-1),
Pull out the PWR switch lever of the No.1 DC-DC CONV and
turn on,
Confirm that the PWR indicator on the No.1 DC-DC CONV is
ON,
INITIAL LINE UP
ROI-S05750
Chart 3-1 (Cont’d)
Step
Procedure
Pull out the PWR switch lever of the No.1 MODEM and turn
on,
Confirm that the PWR indicator on the No.1 MODEM is ON,
Repeat steps 1 to 7 for No.2 MODEM,
Confirm that PWR indicator on the No.2 MODEM is ON.
3-6
INITIAL LINE UP
ROI-S05750
MODEM
SELV
PWR LED
PWR SWITCH (IDU)
IDU
! IF IN/OUT
XPIC CTRL
1+0 CONFIGURATION
G PULL
PWR
ODU
MD/
CBL SELV
ALM
PWR
OC-3 IN
OC-3 OUT
ALM
OC-3 OUT
ONLINE
OC-3 IN
ONLINE
XIF IN XIF OUT
TX
RX
XPIC
RESET
− 43V
STD
OUT
PWR
ALM
PULL
LCT
PWR
SELV
FUSE (250V/8AH)
DC-DC
CONV
–43 V/OUT
NMS
MAINT
MEMORY
IDU
AUX/ALM
NE
SC IN/OUT
EOW
CALL
MMC
POWER SUPPLY
2 1
–20 to –60V/(or 0V)
NLite E
PROTECT
0 V/(or +20 to +60V)
No.1 POWER SUPPLY
No.2 POWER SUPPLY
0 V/(or +20 to +60V)
0 V/(or +20 to +60V)
2 1
–20 to –60V/(or 0V)
2 1
–20 to –60V/(or 0V)
No.2 PWR SWITCH
No.1 SELV
No.1 PWR SWITCH
No.1 –43 V/OUT
DC-DC CONV UNIT
NWA-011060-001 DC-DC CONV UNIT
WEIGHT 2.5kg
SER No.
DATE
1+0 System STD Input : 20 60V
3.4A 1.0A Output : − 43V
1.3A
1+1 System STD Input : 20 60V
3.4A 1.0A×2 Output : − 43V
1.3A×2
NEC Corporation TOKYO JAPAN
MADE IN JAPAN
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
ALM
SELV
FUSE (250V/8AH)
− 43V
PULL
PWR
OUT
STD
PWR
ALM
FUSE (250V/8AH)
PULL
ALM
PWR
XIF IN XIF OUT
XPIC CTRL
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
OC-3 OUT
OC-3 IN
ALM
OC-3 OUT
ONLINE
OC-3 IN
PROTECT
ONLINE
PULL
PWR
LCT
NMS
NE
AUX/ALM
! IF IN/OUT
PULL
PWR
SELV
XPIC CTRL
PWR
OUT
! IF IN/OUT
XIF IN XIF OUT
No.2 –43 V/OUT
− 43V
STD
No.2 SELV
NLite E
MAINT
MEMORY
IDU
SC IN/OUT
EOW
CALL
MMC
No.1 PWR SWITCH
No.2 MODEM
No.1 SELV
No.1 MODEM
No.2 PWR SWITCH
No.2 SELV
Caution: The NLite E operates only negative voltage (–48 V). Therefore, the power supply
system for the existing equipment which uses a floating power supply (–20 to –60 V/
+20 to +60 V) must not be connected to the NLite E .
Fig. 3-1 DC Power cable Connection and Power ON/OFF (2/2)
3-7
INITIAL LINE UP
ROI-S05750
3.2 Shut-down
The shut-down procedures for the equipment is shown in Chart 3-2.
Warning: After turning ON the equipment, wait at least 1 minute
before turning it OFF again. Repeatedly turning the power
ON and OFF with in a short interval may cause the IDU/
ODU to fail.
Chart 3-2 Shut-down
Step
Procedure
1+0 SYSTEM
Pull out the PWR switch lever on the MODEM and turn off the
PWR switch (see Fig. 3-1),
Confirm that all LED indicators on the IDU are OFF.
1+1 SYSTEM
Note: When turn OFF the IDU and ODU in 1+1 configuration,
turn OFF power for standby side first, then working side.
When turn OFF the IDU and ODU in working channel
only, switchover the working to standby channel with TX
and RX SW using LCT. (see Chart 3-8)
Pull out the PWR switch lever on the corresponding MODEM is
to be shut down, then turn off (see Fig. 3-1).
Confirm that the PWR indicator on the MODEM is OFF.
Pull out the PWR switch lever on the other MODEM, then turn
off the PWR switch. (see Fig. 3-1).
Confirm that all LED indicators on the IDU are OFF.
3-8
INITIAL LINE UP
ROI-S05750
3.3 Initial Setting
The initial setup of the IDU/ODU is performed using the PC according to
Table 3-1.
For the details operation of the PC setup for connecting LCT, refer to the
NLite E LCT Operation Manual in Section IV Appendix.
Table 3-1 Initial Setup Items
Setup Order
Setup Item
LCT
1.
Equipment Setup
Chapter 3
2.
Date and Time
Chapter 6.3
3.
Provisioning
Chapter 7
4.
Relay/House Keeping
Chapter 7
Note: The “Equipment Setup” must be set properly every items
before “Provisioning” setup.
The “Provisioning” setup must be performed based on
the “Equipment Setup”.
1+0 CONFIGURATION
! IF IN/OUT
XPIC CTRL
PWR
ODU
MD/
CBL SELV
G PULL
ALM
PWR
OC-3 OUT
OC-3 IN
ALM
OC-3 OUT
ONLINE
OC-3 IN
ONLINE
XIF IN XIF OUT
TX
RX
XPIC
RESET
PROTECT
(Blank)
LCT
NMS
MAINT
MEMORY
IDU
AUX/ALM
NE
NLite E
SC IN/OUT
EOW
CALL
MMC
LCT
1+1 CONFIGURATION
! IF IN/OUT
XPIC CTRL
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
ALM
PWR
OC-3 OUT
OC-3 IN
ALM
OC-3 OUT
ONLINE
OC-3 IN
! IF IN/OUT
XIF IN XIF OUT
XPIC CTRL
TX
RX
XPIC
RESET
PWR
ODU
MD/
CBL SELV
PROTECT
PULL
PWR
LCT
NMS
NE
AUX/ALM
NLite E
MAINT
MEMORY
IDU
SC IN/OUT
EOW
CALL
MMC
LCT Access Cable
USB
PC for LCT
Fig. 3-2 LCT Connection
3-9
ONLINE
XIF IN XIF OUT
G PULL
INITIAL LINE UP
ROI-S05750
3.3.1 Equipment Setup
In initial lineup, the “Equipment Setup” must be performed using LCT.
Chart 3-3 Equipment Setup
Refer to the NLite E LCT Operation Manual in Section IV Appendix. for
the details of “3. Equipment Setup”.
The Equipment Setup items to be setup for the SONET systems are as
follows:
Equipment Setup Items for SONET Systems
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
User Interface
Redundancy Setting
INTFC
INTFC Main (WORK) *1
INTFC SUB (PROT) *1
XPIC Usage *2
APS Function *3
Modulation Scheme
Transmission Capacity
TX RF Frequency
RX RF Frequency *5
Frame ID
TX Power Control
LAN Port Usage *4
LAN Capacity *4
TX Start Frequency
TX Stop Frequency
Frequency Step
Shift Frequency
Upper/Lower
Sub Band
Notes:*1
*2
For SONET only.
When the SONET XPIC is configured, set Main Master and
Sub Master. Set to Not Used in other configurations.
The TX/RX frequency for the Main Master and Sub Master
channels must be set to the same values. The Main Master
and Sub Master channels must be connected to one dual
polarized antenna. The reference local frequency and the
action control of the ATPC/MTPC are applied from the
Main Master channel to the Sub Master channel.
*3 For SONET APS only.
*4 For LAN transmission only.
*5 There is two types ODU for the RX RF Frequency setup
mode.
Type 1.When the transmitting frequency is set, the receiving
frequency is automatically assigned.
Type 2.When the transmitting frequency is set, the receiving
frequency is automatically assigned and assignment of it in
manual is also available.
3-10
INITIAL LINE UP
ROI-S05750
3.3.2 Provisioning Setup for SONET
In initial lineup, the “Provisioning” Setup must be performed using LCT.
Chart 3-4 Provisioning Setup (SONET)
Refer to the NLite E LCT Operation Manual in Section IV Appendix. for
details of the “7. Provisioning Setup”.
The Provisioning Setup items to be setup for SONET systems are as
follows:
•
•
•
•
•
•
•
•
•
•
•
•
•
Provisioning Setup for SONET system
BER Threshold Setting
Sub Interface *1
SC Assignment
LAN Port Setting *2
OC-3 Setting
TX Power Control*3
Condition for TX/RX SW
Condition for APS
Relay Setting
TCN Threshold(15min)
TCN Threshold(1day)
PMON Select
Others *3
Note: *1:For LAN transmission only.
*2:For LAN transmission only.
*3:Set to required TX power level in MTPC mode when it
is going to perform the Antenna Orientation.
*4:Optional items
3-11
INITIAL LINE UP
ROI-S05750
3.4 Antenna Orientation
After the initial setup has been completed, an antenna orientation will be
performed between two stations according to the procedures in Chart 3-6.
Chart 3-5 Antenna Orientation
Apparatus :
Digital Multimeter with test leads or X0818 NLite E Monitor
Wrench
Headset
Step
Procedure
Connect the PC to the LCT port on the NLite E IDU using USB
cable, (see Fig. 3-2)
At each station, set “Maintenance1” from Maintenance in LCT
Menu,
LCT MENU
Alarm/Status
Equipment Setup
Inventory
AUX I/O
Maintenance
Provisioning
Metering
PMON(History)
Maintenance1
Maintenance2
Note: In Maintenance “On” condition, every external Alarm
outputs, excluding Maintenance/PS/CPU (IDU) ALM, are
masked and remote control can not be performed.
Click and select for the following control items in
“Maintenance1”,
Note: Retain the present status for other control items.
Note: When the TX power control mode is set to ATPC, set it to
MTPC and required level for the NLite E link on the
“Equipment Setup” and “Provisioning”.
3-12
INITIAL LINE UP
ROI-S05750
Chart 3-5 (Cont’d)
Step
Procedure
• TX SW Manual Control: Fix No.1 or No.2
(in 1+1 configuration)
• RX SW Manual Control: Fix No.1 or No.2
(which is the same side fixed by TX SW in
1+1 configuration)
• TX Power Control:
(at opposite site)
MTPC in Equipment Setup
Required level in Provisioning
• CW Control:
(at opposite site)
When the Antena Alignment Mode is not
selected, set manually to On.
• XPIC Control Local:
Fix Forced Reset in XPIC configuration.
• Antenna Alignment Mode: Select On (in 1+0 configuration)
(Set No.1 or No.2 which is the same side
fixed by TX SW and RX SW in 1+1
configuration)
--- Maintenance 1 --Item
Maintenace
TX SW Manual Control
RX SW Manual Control
RX SW Maintenace Mode
MTPC Manual Control(No.1)
MTPC Manual Control(No.2)
TX Mute Control(No.1)
TX Mute Control(No.2)
CW Control(No.1)
CW Control(No.2)
IF Loopback (No.1)
IF Loopback (No.2)
Main Loopback (Near End)
Main Loopback (Far End)
Linearrizer Control(No.1)
Linearrizer Control(No.2)
XPIC Control Local(No.1)
XPIC Control Local(No.2)
XPIC Control Remote(No.1)
XPIC Control Remote(No.2)
--- Offline Maintenance --DADE Adjust
RF SUB Band Select (No.1)
RF SUB Band Select (No.2)
Antenna Alignment Mode(No.1)
Antenna Alignment Mode(No.2)
Value
On
No.1
No.1
Manual
On
On
Off
Off
Off
Off
Off
Off
Off
Off
Auto
Auto
Auto
Auto
Auto
Auto
...
...
...
On
On
Setting
Off
Auto
Auto
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Auto
Auto
Auto
Auto
Auto
Auto
On
No.1
No.1
On
On
On
On
On
On
On
On
On
On
Forced Reset
Forced Reset
Forced Reset
Forced Reset
Forced Reset
Forced Reset
DADE
Offset DADE
Off
Off
No.2
No.2
On
On
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
DADE Off Set
Set
Set
Set
Set
Note: In Antenna Alignment Mode “On” condition, controls
between IDU and ODU are restricted.
3-13
INITIAL LINE UP
ROI-S05750
Chart 3-5 (Cont’d)
Step
Procedure
At receiving station, remove a cap from the RX LEV MON
jack,
At each station connect the digital multimeter or NLite E
Monitor to the RX LEV MON jack on the ODU,
Note: In order to measure exact performance of AGC V, it is
mandatory required to set Antenna Alignment Mode to
ON. The AGC voltage indication is not guaranteed
outside Antenna Alignment Mode.
It is necessary to set to Antenna Alignment Mode when
monitor the RX level with the NLite E Monitor unit.
At each station, adjust the azimuth and elevation angle of the
antenna alternately so that the measured voltage becomes
maximum,
Note: The relation of the RX INPUT LEVEL versus RX LEVEL
MON(V) is shown below.
RX LEVEL MON vs RX INPUT LEVEL (Typical)
4.5
3.5
RX LEVEL MON [V]
2.5
1.5
0.5
-80
-70
-60
-50
-40
-30
-20
RX INPUT LEVEL [dBm]
3-14
INITIAL LINE UP
ROI-S05750
Chart 3-5 (Cont’d)
Step
Procedure
NLite E MONITOR
DIGITAL MULTIMETER
OW
NLite E
RX LEV MON
RX LEV
MON
RX LEV/OW IN
IFL
FG
ODU
Notes 1: It is necessary to set to the Antenna Alignment Mode using PC for LCT
when monitor the RX level with the NLite E MONITOR unit.
2: The RX LEV MON terminal on the ODU (conformed to IEC61169-24).
3: The RX LEV MON terminal must be capped for waterproof.
Fig. 3-3 Antenna Orientation Test Setup
Note: The fixed bolts and nuts to be used for the antenna orientation
differ with antenna bracket types, refer to antenna bracket shown
in Fig. 3-4 (1/4) to (4/4).
3-15
INITIAL LINE UP
ROI-S05750
Safety Guideline for Microwave Radiation Hazard
The Microwave and Millimeter-wave that NLite E series are transmitting is at a very small radiation
level and never has been reported to effect human health. Advanced countries concerned about health
hazards have started to regulate the radiation levels. The operator should not work near the parabolic
antenna during RF transmission. The area in front of and to the side of the antenna show high radiation
levels. Please see below figure and calculation sample 1.
The front side of antenna presents a high power density in the antenna beam area. Therefore, the user of
this system should pay attention not to radiate the beam against humans at any time. (Please refer below
calculation sample 2)
ANTENNA
ODU
- 90 to +90
degrees
Hazard Area of Radiation
In addition, the Power density and Field strength level is calculated by equation below.
P+G−30
Power density S
(mW/cm2)
10 10 × K
40 × π × R2
Where:
P = Output power of ODU (dBm),
G = Antenna Gain (dBi),
(in consideration of the angle from antenna)
K = Reflection factor =2.56 (given),
R = Distance between Human and Antenna (m)
Calculation example 1, (90 degree side of antenna)
NLite E = 18 GHz/+23 dBm,
Antenna diameter = 0.6 m,
0 degree antenna gain = 39 dBi,
90 degrees side antenna gain = −24 dBi, (90 degrees attenuation = −63 dB),
Distance = 0.1 m
Power density S (mW/cm2) = 0.0016 ≤ 0.01
Calculation example 2, (0 degree, front side of antenna)
NLite E = 7 GHz/+27 dBm,
Antenna diameter = 1.8 m,
0 degree antenna gain = 40 dBi,
Distance = 100 m
Power density S (mW/cm2) = 0.01
3-16

Source Exif Data:
File Type                       : PDF
File Type Extension             : pdf
MIME Type                       : application/pdf
PDF Version                     : 1.6
Linearized                      : No
Create Date                     : 2009:02:20 08:38:42-05:00
Creator                         : FrameMaker 8.0
Modify Date                     : 2009:02:20 08:39:36-05:00
XMP Toolkit                     : Adobe XMP Core 4.2.1-c041 52.342996, 2008/05/07-20:48:00
Metadata Date                   : 2009:02:20 08:39:36-05:00
Creator Tool                    : FrameMaker 8.0
Format                          : application/pdf
Document ID                     : uuid:75a28726-8920-4f6f-a908-e2d79c5f1917
Instance ID                     : uuid:22941842-3daf-4a7c-8de8-8ffab556b526
Producer                        : Acrobat Distiller 6.0 (Windows)
Page Count                      : 55
EXIF Metadata provided by EXIF.tools
FCC ID Filing: VQL58155

Navigation menu