  SITRANS Radar Transmitters SITRANS LR250 (PROFIBUS PA) Operating Instructions    08/2014 A5E32221386-AC Introduction  1  Safety information  2  Description  3  Installing/mounting  4  Connecting  5  Commissioning  6  Remote operation  7  Parameter reference  8  Service and maintenance  9  Diagnosing and troubleshooting  10  Technical data  11  Dimension drawings  12  Appendix A: Technical reference  A  Appendix B: PROFIBUS PA profile structure  B  Appendix C: Communications via PROFIBUS  C  Appendix D: Certificates and Support  D  List of abbreviations  13  LCD menu structure  14
    Siemens AG Industry Sector Postfach 48 48 90026 NÜRNBERG GERMANY Order number: A5E32221386 Ⓟ 04/2014 Subject to change Copyright © Siemens AG 2014. All rights reserved Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.  DANGER indicates that death or severe personal injury will result if proper precautions are not taken.   WARNING indicates that death or severe personal injury may result if proper precautions are not taken.   CAUTION indicates that minor personal injury can result if proper precautions are not taken.   NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems. Proper use of Siemens products Note the following:  WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed. Trademarks All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.
 SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 3 Table of contents   1  Introduction ............................................................................................................................................. 9 1.1 LR250 PA manual usage ............................................................................................................... 9 1.2 Purpose of this documentation ...................................................................................................... 9 1.3 Document history ........................................................................................................................... 9 1.4 Firmware revision history ............................................................................................................. 10 1.5 Designated use ............................................................................................................................ 11 1.6 Checking the consignment ........................................................................................................... 11 1.7 Transportation and storage .......................................................................................................... 12 1.8 Notes on warranty ........................................................................................................................ 12 2  Safety information ................................................................................................................................. 13 2.1 Preconditions for safe use ........................................................................................................... 13 2.1.1 Safety marking symbols ............................................................................................................... 13 2.1.2 Laws and directives ..................................................................................................................... 13 2.1.3 FCC Conformity ........................................................................................................................... 14 2.1.4 Conformity with European directives ........................................................................................... 15 2.1.5 CE Electromagnetic Compatibility (EMC) Conformity.................................................................. 16 2.2 Improper device modifications ..................................................................................................... 16 2.3 Requirements for special applications ......................................................................................... 17 2.4 Use in hazardous areas ............................................................................................................... 17 3  Description ............................................................................................................................................ 19 3.1 SITRANS LR250 overview ........................................................................................................... 19 3.2 Programming ................................................................................................................................ 20 3.3 Applications .................................................................................................................................. 20 3.4 Approvals and certificates ............................................................................................................ 20 4  Installing/mounting ................................................................................................................................ 21 4.1 Basic safety information ............................................................................................................... 21 4.1.1 Pressure applications ................................................................................................................... 22 4.1.1.1 Pressure Equipment Directive, PED, 97/23/EC ........................................................................... 23 4.2 Installation location requirements ................................................................................................ 24 4.3 Proper mounting........................................................................................................................... 26 4.3.1 Nozzle design ............................................................................................................................... 27
Table of contents      SITRANS LR250 (PROFIBUS PA) 4 Operating Instructions, 08/2014, A5E32221386-AC 4.3.2 Nozzle location ............................................................................................................................ 28 4.3.3 Orientation in a vessel with obstructions ..................................................................................... 31 4.3.4 Mounting on a Stillpipe or Bypass Pipe ...................................................................................... 32 4.3.5 Device orientation ....................................................................................................................... 33 4.4 Installation instructions ................................................................................................................ 34 4.4.1 Threaded versions ...................................................................................................................... 35 4.4.2 Flanged versions ......................................................................................................................... 36 4.4.3 Hygienic versions ........................................................................................................................ 38 4.5 Disassembly ................................................................................................................................ 39 5  Connecting ............................................................................................................................................41 5.1 Basic safety information .............................................................................................................. 41 5.2 Connecting SITRANS LR250 ...................................................................................................... 41 5.3 Wiring setups for hazardous area installations ........................................................................... 45 5.3.1 Intrinsically safe wiring ................................................................................................................ 46 5.3.1.1 Intrinsically safe wiring (FM/CSA) ............................................................................................... 47 5.3.1.2 Intrinsically safe wiring (notes) .................................................................................................... 47 5.3.2 Non-sparking wiring .................................................................................................................... 49 5.3.3 Non-incendive wiring (US/Canada only) ..................................................................................... 49 5.4 Instructions specific to hazardous area installations ................................................................... 50 5.4.1 (Reference European ATEX Directive 94/9/EC, Annex II, 1/0/6) ............................................... 50 6  Commissioning ......................................................................................................................................53 6.1 Basic safety information .............................................................................................................. 53 6.2 Operating via the handheld programmer .................................................................................... 53 6.2.1 Power up ..................................................................................................................................... 54 6.2.2 Handheld programmer functions ................................................................................................. 54 6.2.2.1 The LCD display .......................................................................................................................... 55 6.2.2.2 Handheld programmer (Part No. 7ML1930-1BK) ....................................................................... 57 6.2.3 Programming ............................................................................................................................... 58 6.2.3.1 Quick Start Wizard via the handheld programmer ...................................................................... 63 6.2.3.2 Auto False Echo Suppression ..................................................................................................... 65 6.2.3.3 Requesting an Echo Profile ........................................................................................................ 66 6.2.3.4 Device address ........................................................................................................................... 67 6.3 Application examples .................................................................................................................. 67 6.3.1 Liquid resin in storage vessel, level measurement ..................................................................... 68 6.3.2 Horizontal vessel with volume measurement.............................................................................. 69 6.3.3 Application with stillpipe .............................................................................................................. 71 7  Remote operation ..................................................................................................................................75 7.1 Operating via SIMATIC PDM ...................................................................................................... 75 7.1.1 Functions in SIMATIC PDM ........................................................................................................ 75 7.1.1.1 Features of SIMATIC PDM Rev. 6.0, SP4 or higher ................................................................... 76 7.1.1.2 Features of SIMATIC PDM Rev. 5.2, SP1 .................................................................................. 76
 Table of contents   SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 5 7.1.1.3 SIMATIC PDM Version ................................................................................................................ 76 7.1.2 Electronic Device Description (EDD) ........................................................................................... 76 7.1.2.1 Updating the Electronic Device Description (EDD) ...................................................................... 76 7.1.2.2 Configuring a new device ............................................................................................................. 77 7.1.3 Quick start wizard via SIMATIC PDM .......................................................................................... 78 7.1.4 Changing parameter settings using SIMATIC PDM .................................................................... 83 7.1.5 Parameters accessed via pull-down menus ................................................................................ 83 7.1.5.1 Echo profile utilities ...................................................................................................................... 84 7.1.5.2 Auto false echo suppression ........................................................................................................ 88 7.1.5.3 Echo setup ................................................................................................................................... 91 7.1.5.4 Maintenance ................................................................................................................................. 91 7.1.5.5 Acknowledge Faults ..................................................................................................................... 93 7.1.5.6 Wear ............................................................................................................................................. 93 7.1.5.7 Simulation .................................................................................................................................... 93 7.1.5.8 Write locking ................................................................................................................................. 96 7.1.5.9 Master reset ................................................................................................................................. 97 7.1.5.10 Factory defaults............................................................................................................................ 97 7.1.5.11 Diagnostics ................................................................................................................................... 98 7.2 Operating via FDT ...................................................................................................................... 105 7.2.1 Device Type Manager (DTM) ..................................................................................................... 105 7.2.2 SITRANS DTM ........................................................................................................................... 105 7.2.3 The device EDD ......................................................................................................................... 106 7.2.4 Configuring a new device via FDT ............................................................................................. 106 8  Parameter reference ........................................................................................................................... 107 8.1 Alphabetical parameter list ......................................................................................................... 167 9  Service and maintenance .................................................................................................................... 173 9.1 Basic safety information ............................................................................................................. 173 9.2 Cleaning ..................................................................................................................................... 173 9.3 Maintenance and repair work ..................................................................................................... 174 9.3.1 Unit repair and excluded liability ................................................................................................ 175 9.3.2 Part replacement ........................................................................................................................ 175 9.4 Disposal ..................................................................................................................................... 177 10 Diagnosing and troubleshooting .......................................................................................................... 179 10.1 Communication troubleshooting ................................................................................................ 179 10.2 Device status icons .................................................................................................................... 180 10.3 General fault codes .................................................................................................................... 181 10.4 Operation troubleshooting .......................................................................................................... 184 11 Technical data .................................................................................................................................... 187 11.1 Power ......................................................................................................................................... 187 11.2  Performance ............................................................................................................................... 187
Table of contents      SITRANS LR250 (PROFIBUS PA) 6 Operating Instructions, 08/2014, A5E32221386-AC 11.3 Interface .................................................................................................................................... 189 11.4 Mechanical ................................................................................................................................ 189 11.5 Environmental ........................................................................................................................... 192 11.6 Process ..................................................................................................................................... 192 11.7 Approvals .................................................................................................................................. 193 11.8 Programmer (infrared keypad) .................................................................................................. 194 12 Dimension drawings ............................................................................................................................. 195 12.1 Threaded horn antenna............................................................................................................. 195 12.2 Threaded horn antenna with extension ..................................................................................... 198 12.3 Flanged horn antenna ............................................................................................................... 200 12.4 Flanged horn antenna with extension ....................................................................................... 202 12.5 Flanged encapsulated antenna (2"/DN50/50A sizes only) ....................................................... 204 12.6 Flanged encapsulated antenna (3"/DN80/80A sizes and larger) .............................................. 206 12.7 Hygienic encapsulated antenna (2" ISO 2852 sanitary clamp) ................................................ 208 12.8 Hygienic encapsulated antenna (3" ISO 2852 sanitary clamp) ................................................ 209 12.9 Hygienic encapsulated antenna (4" ISO 2852 sanitary clamp) ................................................ 210 12.10 Hygienic encapsulated antenna (DN 50 nozzle/slotted nut to DIN 11851) ............................... 211 12.11 Hygienic encapsulated antenna (DN 80 nozzle/slotted nut to DIN 11851) ............................... 212 12.12 Hygienic encapsulated antenna (DN 100 nozzle/slotted nut to DIN 11851) ............................. 213 12.13 Hygienic encapsulated antenna (DN 50 aseptic slotted nut to DIN 11864-1) .......................... 214 12.14 Hygienic encapsulated antenna (DN 80 aseptic slotted nut to DIN 11864-1) .......................... 215 12.15 Hygienic encapsulated antenna (DN 100 aseptic slotted nut to DIN 11864- 1) ....................... 216 12.16 Hygienic encapsulated antenna (DN 50 aseptic flange to DIN 11864-2) ................................. 217 12.17 Hygienic encapsulated antenna (DN 80 aseptic flange to DIN 11864-2) ................................. 218 12.18 Hygienic encapsulated antenna (DN 100 aseptic flange to DIN 11864-2) ............................... 219 12.19 Hygienic encapsulated antenna (DN 50 aseptic clamp to DIN 11864-3) ................................. 220 12.20 Hygienic encapsulated antenna (DN 80 aseptic clamp to DIN 11864-3) ................................. 222 12.21 Hygienic encapsulated antenna (DN 100 aseptic clamp to DIN 11864-3) ............................... 223 12.22 Hygienic encapsulated antenna (Tuchenhagen Type N).......................................................... 224 12.23 Hygienic encapsulated antenna (Tuchenhagen Type F) .......................................................... 225 12.24 Threaded PVDF antenna .......................................................................................................... 226 12.25 Threaded connection markings ................................................................................................. 227
 Table of contents   SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 7 12.26 Raised-Face flange per EN 1092-1 for flanged horn antenna ................................................... 228 12.27 Raised-Face flange per EN 1092-1 for flanged encapsulated antenna..................................... 230 12.28 Flat-Face flange ......................................................................................................................... 233 12.29 Aseptic/hygienic flange DN50, DN80, DN100 for DIN 11864-2 ................................................. 236 12.30 Process connection tag (pressure rated versions) .................................................................... 239 A  Appendix A: Technical reference ......................................................................................................... 241 A.1 Principles of operation ............................................................................................................... 241 A.2 Echo processing......................................................................................................................... 242 A.2.1 Process Intelligence ................................................................................................................... 242 A.2.2 Echo Selection ........................................................................................................................... 242 A.2.3 CLEF Range .............................................................................................................................. 245 A.2.4 Echo Threshold .......................................................................................................................... 246 A.2.5 Echo Lock .................................................................................................................................. 246 A.2.6 Auto False Echo Suppression .................................................................................................... 246 A.2.7 Measurement Range ................................................................................................................. 248 A.2.8 Measurement Response ............................................................................................................ 249 A.2.9 Damping ..................................................................................................................................... 249 A.2.10 Loss of Echo (LOE) .................................................................................................................... 250 A.2.10.1 LOE Timer .................................................................................................................................. 250 A.2.10.2 Fail-safe Behavior ...................................................................................................................... 250 A.3 Maximum Process Temperature Chart ...................................................................................... 251 A.4 Process Pressure/Temperature Derating Curves ...................................................................... 253 A.4.1 Horn antenna ............................................................................................................................. 254 A.4.2 Flanged horn antenna ................................................................................................................ 255 A.4.3 Flanged encapsulated antenna .................................................................................................. 260 A.4.4 PVDF antenna............................................................................................................................ 262 A.4.5 Hygienic encapsulated antenna ................................................................................................. 263 B  Appendix B: PROFIBUS PA profile structure ....................................................................................... 266 B.1 PROFIBUS Level Device Design ............................................................................................... 266 B.2 Block Model ................................................................................................................................ 266 B.2.1 Description of the blocks ............................................................................................................ 267 B.2.1.1 Transducer Block function groups ............................................................................................. 267 B.2.1.2 How the transducer block works: ............................................................................................... 268 B.2.1.3 Analog Input Function Blocks 1 and 2 ....................................................................................... 270 C  Appendix C: Communications via PROFIBUS ..................................................................................... 275 C.1 Device configuration .................................................................................................................. 275 C.1.1 SIMATIC PDM ............................................................................................................................ 275 C.1.1.1 Electronic Device Description .................................................................................................... 275 C.2 Network configuration ................................................................................................................ 275 C.2.1 The GSD file ............................................................................................................................... 275
Table of contents      SITRANS LR250 (PROFIBUS PA) 8 Operating Instructions, 08/2014, A5E32221386-AC C.3 Bus termination ......................................................................................................................... 276 C.4 Power demands ........................................................................................................................ 276 C.5 PROFIBUS address .................................................................................................................. 276 C.6 Operating as a profile device .................................................................................................... 277 C.6.1 Configuring a new device .......................................................................................................... 277 C.6.2 Configuring PROFIBUS PA with an S7-300/ 400 PLC ............................................................. 278 C.7 Cyclic versus acyclic data ......................................................................................................... 278 C.7.1 Cyclic data ................................................................................................................................. 279 C.8 Status byte ................................................................................................................................ 280 C.9 Condensed status ..................................................................................................................... 281 C.10 Diagnostics ................................................................................................................................ 283 C.10.1 Diagnosis reply (available cyclically) ......................................................................................... 283 C.10.2 Diagnosis object (available cyclically or acyclically) ................................................................. 284 C.10.3 Extended mode diagnosis ......................................................................................................... 284 C.10.4 Condensed mode diagnosis ..................................................................................................... 285 C.10.5 Acyclic extended diagnostics (general fault codes) .................................................................. 286 C.10.6 Acyclic data ............................................................................................................................... 289 D  Appendix D: Certificates and Support ................................................................................................... 291 D.1 Certificates ................................................................................................................................ 291 D.2 Technical support ...................................................................................................................... 291 13 List of abbreviations ............................................................................................................................. 293 14 LCD menu structure ............................................................................................................................. 295  Glossary .............................................................................................................................................. 301  Index ................................................................................................................................................... 307
 SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 9  Introduction 1 1.1 LR250 PA manual usage   Note This manual applies to the SITRANS LR250 (PROFIBUS PA) only.  Follow these operating instructions for quick, trouble-free installation, and maximum accuracy and reliability of your device.  We always welcome suggestions and comments about manual content, design, and accessibility. Please direct your comments to: Technical publications (mailto:techpubs.smpi@siemens.com)  1.2 Purpose of this documentation These instructions contain all information required to commission and use the device. It is your responsibility to read the instructions carefully prior to installation and commissioning. In order to use the device correctly, first review its principle of operation. The instructions are aimed at persons mechanically installing the device, connecting it electronically, configuring the parameters and commissioning it, as well as service and maintenance engineers. 1.3 Document history The following table notes major changes in the documentation compared to the previous edition.  Edition Remark January 2014 • Flanged encapsulated antenna version added. August 2014 • Hygienic encapsulated antenna version added.
Introduction   1.4 Firmware revision history  SITRANS LR250 (PROFIBUS PA) 10 Operating Instructions, 08/2014, A5E32221386-AC 1.4 Firmware revision history This history establishes the correlation between the current documentation and the valid firmware of the device. The documentation of this edition is applicable for the following firmware:   Firmware rev. EDD rev. Date Changes 1.00.04 1.00.05 12 Jun 2007 • Initial release. 1.01.00 1.01.00 23 Aug 2007 • EDD a)/SIMATIC PDM: improved rendering of the echo profile and TVT. 1.01.01 1.01.01 26 Sep 2007 • PNO certification release. 1.01.02 1.01.02 10 Jun 2008 • Maintenance release for firmware and EDDa) 1.01.02 1.01.03 17 Jun 2008 • The internal EDD revision has been incremented. 1.02.00 1.02.00 27 May 2009 • Harmonization of menu structures and parameter names across products. • Display indicates progress towards first measurement. 1.02.01  1.02.00 7 June 2010 • Display contrast improvement. • Antenna type parameter cannot be modified. 1.02.02  1.02.00 24 May 2011 • Threaded PVDF antenna supported. 1.02.03 1.02.01 31 Oct 2012 • Antenna parameter removed. • Quickstart on local display enhancements. a) Electronic Device Description
 Introduction  1.5 Designated use SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 11 1.5 Designated use Use the device to measure process media in accordance with the information in the operating instructions.   Note Use in a domestic environment This is a Class A Group 1 equipment intended for use in industrial areas.  In a domestic environment this device may cause radio interference.  1.6 Checking the consignment 1. Check the packaging and the device for visible damage caused by inappropriate handling during shipping. 2. Report any claims for damages immediately to the shipping company. 3. Retain damaged parts for clarification. 4. Check the scope of delivery by comparing your order to the shipping documents for correctness and completeness.     WARNING Using a damaged or incomplete device Danger of explosion in hazardous areas. • Do not use damaged or incomplete devices.
Introduction   1.7 Transportation and storage  SITRANS LR250 (PROFIBUS PA) 12 Operating Instructions, 08/2014, A5E32221386-AC 1.7 Transportation and storage To guarantee sufficient protection during transport and storage, observe the following: ● Keep the original packaging for subsequent transportation. ● Devices/replacement parts should be returned in their original packaging. ● If the original packaging is no longer available, ensure that all shipments are properly packaged to provide sufficient protection during transport. Siemens cannot assume liability for any costs associated with transportation damages.    CAUTION Insufficient protection during storage The packaging only provides limited protection against moisture and infiltration. • Provide additional packaging as necessary.  1.8 Notes on warranty The contents of this manual shall not become part of or modify any prior or existing agreement, commitment or legal relationship. The sales contract contains all obligations on the part of Siemens as well as the complete and solely applicable warranty conditions. Any statements regarding device versions described in the manual do not create new warranties or modify the existing warranty. The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development.
 SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 13  Safety information 2 2.1 Preconditions for safe use This device left the factory in good working condition. In order to maintain this status and to ensure safe operation of the device, observe these instructions and all the specifications relevant to safety. Observe the information and symbols on the device. Do not remove any information or symbols from the device. Always keep the information and symbols in a completely legible state. 2.1.1 Safety marking symbols  In manual On product Description   (Label on product: yellow background.)  WARNING: refer to accompanying documents (manual) for details.  2.1.2 Laws and directives Observe the test certification, provisions and laws applicable in your country during connection, assembly and operation.
Safety information   2.1 Preconditions for safe use  SITRANS LR250 (PROFIBUS PA) 14 Operating Instructions, 08/2014, A5E32221386-AC 2.1.3 FCC Conformity US Installations only: Federal Communications Commission (FCC) rules   WARNING Improper device modifications Danger to personnel, system and environment can result from improper modifications to the device.  • Changes or modifications not expressly approved by Siemens could void the user’s authority to operate the equipment.   Note • This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. • This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the operating instructions, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference to radio communications, in which case the user will be required to correct the interference at his own expense.
 Safety information  2.1 Preconditions for safe use SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 15 2.1.4 Conformity with European directives The CE marking on the device symbolizes the conformity with the following European directives:  Electromagnetic compatibility EMC  2004/108/EC Directive of the European Parliament and of the Council on the approximation of the laws of the Member States relating to electromagnetic compatibility and repealing Directive 89/336/EEC. Low voltage directive LVD  2006/95/EC Directive of the European Parliament and of the Council on the harmonisation of the laws of Member States relating to electrical equipment designed for use within certain voltage limits. Atmosphère explosible ATEX  94/9/EC Directive of the European Parliament and the Council on the approximation of the laws of the Member States concerning equipment and protective systems intended for use in potentially explosive atmospheres.  Radio and telecommunications terminal equipment R&TTE  1999/5/EC Directive of the European Parliament and of the Council on radio equipment and telecommunications terminal equipment and the mutual recognition of their conformity. The applicable directives can be found in the EC conformity declaration of the specific device.
Safety information   2.2 Improper device modifications  SITRANS LR250 (PROFIBUS PA) 16 Operating Instructions, 08/2014, A5E32221386-AC 2.1.5 CE Electromagnetic Compatibility (EMC) Conformity This equipment has been tested and found to comply with the following EMC Standards:  EMC Standard Title CISPR 11:2009 + A1:2010/EN 55011:2009 + A1:2010, CLASS A Limits and methods of measurements of radio disturbance characteristics of industrial, scientific, and medical (ISM) radio-frequency equipment. EN 61326:2013 (IEC 61326:2012) Electrical Equipment for Measurement, Control and Laboratory Use – Electromagnetic Compatibility. EN61000-4-2:2009 Electromagnetic Compatibility (EMC) Part 4-2: Testing and measurement techniques – Electrostatic discharge immunity test. EN61000-4-3:2006 + A1:2008 + A2:2010 Electromagnetic Compatibility (EMC) Part 4-3: Testing and measurement techniques – Radiated, radio-frequency, electromagnetic field immunity test 2006 + A1:2008 + A2:2010. EN61000-4-4:2004  + A1:2010 Electromagnetic Compatibility (EMC) Part 4-4: Testing and measurement techniques – Electrical fast transient/burst immunity test. EN61000-4-5:2006 Electromagnetic Compatibility (EMC) Part 4-5: Testing and measurement techniques – Surge immunity test. EN61000-4-6:2010 Electromagnetic Compatibility (EMC) Part 4-6: Testing and measurement techniques – Immunity to conducted disturbances, induced by radio-frequency fields. EN61000-4-8:2010 Electromagnetic Compatibility (EMC) Part 4-8: Testing and measurement techniques – Power frequency magnetic field immunity test.   2.2 Improper device modifications   WARNING Improper device modifications    Danger to personnel, system and environment can result from modifications to the device, particularly in hazardous areas. • Only carry out modifications that are described in the instructions for the device. Failure to observe this requirement cancels the manufacturer's warranty and the product approvals.
 Safety information  2.3 Requirements for special applications SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 17 2.3 Requirements for special applications Due to the large number of possible applications, each detail of the described device versions for each possible scenario during commissioning, operation, maintenance or operation in systems cannot be considered in the instructions. If you need additional information not covered by these instructions, contact your local Siemens office or company representative.    Note Operation under special ambient conditions We highly recommend that you contact your Siemens representative or our application department before you operate the device under special ambient conditions as can be encountered in nuclear power plants or when the device is used for research and development purposes.  2.4 Use in hazardous areas Qualified personnel for hazardous area applications Persons who install, connect, commission, operate, and service the device in a hazardous area must have the following specific qualifications:  ● They are authorized, trained or instructed in operating and maintaining devices and systems according to the safety regulations for electrical circuits, high pressures, aggressive, and hazardous media. ● They are authorized, trained, or instructed in carrying out work on electrical circuits for hazardous systems. ● They are trained or instructed in maintenance and use of appropriate safety equipment according to the pertinent safety regulations.   WARNING Loss of safety of device with type of protection "Intrinsic safety Ex i" If the device has already been operated in non-intrinsically safe circuits or the electrical specifications have not been observed, the safety of the device is no longer ensured for use in hazardous areas. There is a danger of explosion. • Connect the device with type of protection "Intrinsic safety" solely to an intrinsically safe circuit. • Observe the specifications for the electrical data on the certificate.
Safety information   2.4 Use in hazardous areas  SITRANS LR250 (PROFIBUS PA) 18 Operating Instructions, 08/2014, A5E32221386-AC
 SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 19  Description 3 3.1 SITRANS LR250 overview   WARNING Loss of protection Danger to personnel, system and environment can result from improper use of the device. • SITRANS LR250 is to be used only in the manner outlined in this manual, otherwise protection provided by the device may be impaired.  SITRANS LR250 is a 2-wire 25 GHz pulse radar level transmitter for continuous monitoring of liquids and slurries in storage vessels including high pressure and high temperature, to a range of 20 meters (66 feet). It is ideal for small vessels, material such as chemicals, food, beverages, solvents (including those of corrosive or aggressive nature), and low dielectric media.  The device consists of an electronic circuit coupled to an antenna and either a threaded or flange type process connection. This device supports PROFIBUS PA communication protocol, and SIMATIC PDM software. Signals are processed using Process Intelligence which has been field-proven in over 1,000,000 applications worldwide (ultrasonic and radar). This device supports acyclic communications from both a PROFIBUS Class I and Class II master.
Description   3.2 Programming  SITRANS LR250 (PROFIBUS PA) 20 Operating Instructions, 08/2014, A5E32221386-AC 3.2 Programming This device is very easy to install and configure via a graphical local user interface (LUI). You can modify the built in parameters either locally via the Siemens infrared handheld programmer, or from a remote location using one of the following options:  ● SIMATIC PDM ● FDT/DTM platform (such as PACTware™ or FieldCare) 3.3 Applications ● liquids and slurries ● bulk storage vessels ● simple process vessels ● corrosive and aggressive ● hygienic/sanitary 3.4 Approvals and certificates   Note For further details see Approvals (Page 193).  SITRANS LR250 is available with approvals for General purpose, sanitary or hygienic and for hazardous areas. In all cases, check the nameplate on your device, and confirm the approval rating. Process Connections A wide range of process connections and antenna options are available to suit virtually any vessel configuration.
 SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 21  Installing/mounting 4 4.1 Basic safety information   Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.    WARNING Unsuitable connecting parts Danger of injury or poisoning.  In case of improper mounting hot, toxic and corrosive process media could be released at the connections. • Ensure that connecting parts (such as flange gaskets and bolts) are suitable for connection and process media.    WARNING Exceeded maximum ambient or process media temperature Danger of explosion in hazardous areas. Device damage. • Make sure that the maximum permissible ambient and process media temperatures of the device are not exceeded.    WARNING Open cable inlet or incorrect cable gland Danger of explosion in hazardous areas. • Close the cable inlets for the electrical connections. Only use cable glands or plugs which are approved for the relevant type of protection.
Installing/mounting   4.1 Basic safety information  SITRANS LR250 (PROFIBUS PA) 22 Operating Instructions, 08/2014, A5E32221386-AC   WARNING Incorrect conduit system Danger of explosion in hazardous areas as result of open cable inlet or incorrect conduit system. • In the case of a conduit system, mount a spark barrier at a defined distance from the device input. Observe national regulations and the requirements stated in the relevant approvals.  4.1.1 Pressure applications   DANGER Pressure applications Danger to personnel, system and environment will result from improper disassembly. • Never attempt to loosen, remove, or disassemble process connection while vessel contents are under pressure.    WARNING Pressure applications Danger to personnel, system and environment can result from improper installation. • Improper installation may result in loss of process pressure.    WARNING Exceeded maximum permissible operating pressure Danger of injury or poisoning. The maximum permissible operating pressure depends on the device version. The device can be damaged if the operating pressure is exceeded. Hot, toxic and corrosive process media could be released. • Make sure that the device is suitable for the maximum permissible operating pressure of your system.
 Installing/mounting  4.1 Basic safety information SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 23   Note • The process connection tag shall remain with the process pressure boundary assembly. (The process pressure boundary assembly comprises the components that act as a barrier against pressure loss from the process vessel: that is, the combination of process connection body and emitter, but normally excluding the electrical enclosure). In the event the device package is replaced, the process connection tag shall be transferred to the replacement unit. • SITRANS LR250 units are hydrostatically tested, meeting or exceeding the requirement of the ASME Boiler and Pressure Vessel Code and the European Pressure Equipment Directive.     Note • The serial numbers stamped in each process connection body, (flange, threaded, or sanitary), provide a unique identification number indicating date of manufacture.  Example: MMDDYY – XXX (where MM = month, DD = day, YY = year, and XXX= sequential unit produced) • Further markings (space permitting) indicate flange configuration, size, pressure class, material, and material heat code.  4.1.1.1 Pressure Equipment Directive, PED, 97/23/EC Siemens Level Transmitters with flanged, threaded, or sanitary clamp type process mounts have no pressure-bearing housing of their own and, therefore, do not come under the Pressure Equipment Directive as pressure or safety accessories (see EU Commission Guideline 1/8 and 1/20).
Installing/mounting   4.2 Installation location requirements  SITRANS LR250 (PROFIBUS PA) 24 Operating Instructions, 08/2014, A5E32221386-AC 4.2 Installation location requirements   WARNING Aggressive atmospheres Danger to personnel, system and environment can result from unsuitable environment. • Provide an environment suitable to the housing rating and materials of construction.     CAUTION Direct sunlight Device damage.  The device can overheat or materials become brittle due to UV exposure. • Protect the device from direct sunlight. • Make sure that the maximum permissible ambient temperature is not exceeded. Refer to the information in Chapter "Technical data".
 Installing/mounting  4.2 Installation location requirements SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 25  ① Ambient temperature ② Device nameplate ③ Device tag ④ Process temperature (at process connection) ⑤ Process connection tag (contains process connection related information)  Antenna ① ③ Horn  -40 to +80 °C (-40 to +176 °F) with FKM O-ring:-40 to +200 °C (-40 to 392 °F) with FFKM O-ring:-20 to +200 °C (-4 to +392 °F) PVDF  -40 to +80 °C (-40 to +176 °F) -40 to +80 °C (-40 to +176 °F) Flanged encapsulated  -40 to +80 °C (-40 to +176 °F) -40 to +170 °C (-40 to +338 °F) Hygienic encapsulated  -40 to +80 °C (-40 to +176 °F) -40 to +170 °C (-40 to +338 °F) with FKM seals used on process connection:  -20 to +170 °C (-4 to +338 °F) with EPDM seals used on process connection:  -40 to +120 °C (-40 to +248 °F)    Note Details about the process connection, process temperature and materials are laser etched into the body of the flanged and hygienic versions. All other SITRANS LR250 versions have details listed on a tag.
Installing/mounting   4.3 Proper mounting  SITRANS LR250 (PROFIBUS PA) 26 Operating Instructions, 08/2014, A5E32221386-AC 4.3 Proper mounting   Note • Correct location is key to a successful application. • Avoid reflective interference from vessel walls and obstructions by following guidelines in this chapter.    NOTICE Incorrect mounting The device can be damaged, destroyed, or its functionality impaired through improper mounting. • Before installing ensure there is no visible damage to the device. • Make sure that process connectors are clean, and suitable gaskets and glands are used. • Mount the device using suitable tools. Refer to the information in Installation instructions (Page 34) for installation torque requirements.    Note • On devices with a removable head, there is no limit to the number of times a device can be rotated without damage. • When mounting, orient the front or back of the device towards the closest vessel wall or obstruction. • Do not rotate the enclosure after programming and vessel calibration, otherwise an error may occur, caused by a polarity shift of the transmit pulse.
 Installing/mounting  4.3 Proper mounting SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 27 4.3.1 Nozzle design  Threaded PVDF antenna Stainless steel horn antenna   Flanged encapsulated antenna (FEA) Hygienic encapsulated antenna (HEA)   ① Minimum clearance: 10 mm (0.4") ② Minimum diameter: 50 mm (2") ③ Maximum nozzle length ④ Maximum length/diameter ratio 1:1 ● The end of the antenna must protrude a minimum of 10 mm (0.4") to avoid false echoes being reflected from the nozzle1). ● Minimum recommended nozzle diameter for the threaded PVDF antenna is 50 mm (2"). ● An antenna extension (100 mm/3.93") is available for the horn antenna only. ● The maximum nozzle length for the FEA is 500 mm (19.68") when the nozzle diameter is DN150 (6"). Only shorter lengths are recommended for smaller diameters. ● When installing the SITRANS LR250 with hygienic process connection, it is good hygienic practice to install the antenna in a nozzle that has a maximum length/diameter ratio of 1:1. For example, 2" (DN50) diameter nozzle should be no longer than 2" (50 mm). ● When removing any sanitary/hygienic clamp version of the HEA to clean the lens, ensure it is re-installed in the exact position it was removed from, to avoid re-commissioning the device. 1) Not applicable for FEA or HEA
Installing/mounting   4.3 Proper mounting  SITRANS LR250 (PROFIBUS PA) 28 Operating Instructions, 08/2014, A5E32221386-AC 4.3.2 Nozzle location ● Avoid central locations on tall, narrow vessels ● Nozzle must be vertical and clear of imperfections    Preferred  Undesirable Beam angle   Note • Beam width depends on antenna size and is approximate: see below. • For details on avoiding false echoes, see Auto False Echo Suppression.  ● Beam angle is the width of the cone where the energy density is half of the peak energy density. ● The peak energy density is directly in front of and in line with the antenna. ● There is a signal transmitted outside the beam angle, therefore false targets may be detected.
 Installing/mounting  4.3 Proper mounting SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 29  Horn antenna Flanged encapsulated antenna   Threaded PVDF antenna Hygienic encapsulated antenna   ① Emission cone   ② Beam angle
Installing/mounting   4.3 Proper mounting  SITRANS LR250 (PROFIBUS PA) 30 Operating Instructions, 08/2014, A5E32221386-AC Emission cone type and beam angle   Antenna type Antenna size Beam angle Horn 1.5"  19° 2" 15° 3" 10° 4" 8° Threaded PVDF    19°  Process connection size Process connection type   Flanged encapsulated 2" Class 150 ASME B16.5  12.8° 3, 4, 6" Class 150 ASME B16.5  9.6° 50A 10K JIS B 2220 12.8° 80A/100A/150A 10K JIS B 2220 9.6° DN50 PN10/16 EN1092-1  12.8° DN80/DN100/DN150 PN10/16 EN1092-1  9.6° Hygienic encapsulated 2"  Sanitary Clamp according to ISO 2852 12.8° 3, 4" 9.6° DN50  Aseptic/Hygienic nozzle/slotted nut according to DIN 11864-1 [Form A] 12.8° DN80/DN100 9.6° DN50  Aseptic/Hygienic flanged according to DIN 11864-2 [Form A] 12.8° DN80/DN100   9.6° DN50  Aseptic/Hygienic Clamp according to DIN 11864-3 [Form A] 12.8° DN80/DN100  9.6° DN50  Hygienic nozzle/slotted nut according to DIN 11851 12.8° DN80/DN100 9.6° Type F (50 mm) and Type N (68 mm) Tuchenhagen Varivent 12.8° Emission cone ● Keep emission cone free of interference from obstructions such as ladders, pipes, I-beams, or filling streams. Access for programming ● Provide easy access for viewing the display and programming via the handheld programmer.
 Installing/mounting  4.3 Proper mounting SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 31 4.3.3 Orientation in a vessel with obstructions Polarization reference point For best results on a vessel with obstructions, or a stillpipe with openings, orient the front or back of the device toward the obstructions. For an illustration, see Device orientation (Page 33).   ① Polarization axis ② Polarization reference point ③ Display
Installing/mounting   4.3 Proper mounting  SITRANS LR250 (PROFIBUS PA) 32 Operating Instructions, 08/2014, A5E32221386-AC 4.3.4 Mounting on a Stillpipe or Bypass Pipe A stillpipe or bypass pipe is used for products with a low dK, or when vortex or extremely turbulent conditions exist. It can also be used to provide optimum signal conditions on foaming materials. See Dielectric constant of material measured in Performance (Page 187) for more information. ● The pipe diameter must be matched with the antenna size. Use the largest antenna size that will fit the stillpipe/bypass pipe1). See Threaded Horn dimensions (Page 195), Raised-Face Flange per EN 1092-1 (Page 230), Flanged encapsulated dimensions or Hygienic encapsulated dimensions. ● One continuous length of metallic pipe is preferred, without joints. ● Any false reflections created by joints/welds/imperfections will lead to inaccuracies of the measurement. ● Joints (if unavoidable) must be machined to ± 0.25 mm (± 0.010") and must have welded connecting sleeve on the outside. ● If using any hygienic process connections in conjunction with a stillpipe/bypass, please ensure that the antenna/lens are cleanable in accordance with the applicable approval. 1) Mounting in a pipe greater than 100 mm (4") can cause large errors, and therefore is not recommended.  Suitable pipe diameters: Horn antenna 40 to 100 mm (1.5 to 4") PVDF antenna 50 mm (2") only Flanged encapsulated antenna 50 to 100 mm (2 to 4") Hygienic encapsulated antenna 50 to 100 mm (2 to 4") Not recommended: > 100 mm (4") Bypass vent: Required at the upper end of the bypass 1)  1)  To equalize pressure and keep the liquid level in the bypass constant with the liquid level in the vessel.
 Installing/mounting  4.3 Proper mounting SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 33 4.3.5 Device orientation  Bypass pipe installation   Stillpipe installation      ① Vent    ① Align front or back of device with stillpipe slots1) ② Align front or back of device with vents1)  ② Slots 1) Horn antenna version shown as example
Installing/mounting   4.4 Installation instructions  SITRANS LR250 (PROFIBUS PA) 34 Operating Instructions, 08/2014, A5E32221386-AC 4.4 Installation instructions   WARNING Pressure applications Danger to personnel, system and environment can result from improper installation. • Improper installation may result in loss of process pressure.    WARNING Improper installation Danger to personnel, system and environment can result from improper installation. • Installation shall only be performed by qualified personnel and in accordance with local governing regulations.   NOTICE Device handling Damage to device may result from improper handling. • Handle the device using the enclosure, not the process connection or tag, to avoid damage. • Take special care when handling the threaded PVDF and Hygienic or Flanged encapsulated antennas. Any damage to the antenna surface, particularly to the tip/lens, could affect performance. (For example, do not sit device on its lens antenna.)   Note • For European Union and member countries, installation must be according to ETSI EN 302372. • Refer to the device nameplate for approval information.    Note The outer part of the lens on the flanged encapsulated antenna version may not appear to lie flush before installation and this is normal. This will flatten after installation and will not impact the performance of the device.
 Installing/mounting  4.4 Installation instructions SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 35   WARNING Pressure applications Danger of injury or poisoning. It will be necessary to use PTFE tape or other appropriate thread sealing compound, and to tighten the process connection beyond hand-tight. (The maximum recommended torque for Threaded versions is 40 N-m (30 ft.lbs.) See Flanged versions (Page 36) for FEA recommended torque values.)    Note • On devices with a removable head, there is no limit to the number of times a device can be rotated without damage. • When mounting, orient the front or back of the device towards the closest vessel wall or obstruction. • Do not rotate the enclosure after programming and vessel calibration, otherwise an error may occur, caused by a polarity shift of the transmit pulse.  4.4.1 Threaded versions   WARNING Pressure applications Danger of injury or poisoning. It may be necessary to use PTFE tape or other appropriate thread sealing compound, and to tighten the process connection beyond hand-tight. (The maximum recommended torque for Threaded versions is 40 N-m (30 ft.lbs.)  1. Before inserting the device into its mounting connection, check to ensure the threads are matching, to avoid damaging them. 2. Simply screw the device into the process connection, and hand tighten, or use a wrench.
Installing/mounting   4.4 Installation instructions  SITRANS LR250 (PROFIBUS PA) 36 Operating Instructions, 08/2014, A5E32221386-AC 4.4.2 Flanged versions   NOTICE Improper materials The user is responsible for the selection of bolting and gasket materials (except for Flanged encapsulated antenna) which will fall within the limits of the process connection and its intended use, and which are suitable for the service conditions.  Special Instructions for Flanged encapsulated antenna only    Note • Use spring washers • Lens assembly acts as integral gasket, no other required • Use recommended torque values for tightening bolts  Flange bolting: recommended torque  Pressure class Nominal pipe size (NPS) Number of bolts Recommended torque (Nm) ASME B16.5, Class 150 2"  4  30 – 50 3" 50 – 70 4"  8  40 – 60 6" 70 – 90 EN1092-1, PN16 /  JIS B 2220, 10K DN50/50A  4  30 – 50 DN80/80A  8 DN100/100A DN150/150A 60 – 80
 Installing/mounting  4.4 Installation instructions SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 37  Flange bolting instructions: 1. Use cross-pattern sequence as shown. 2. Check uniformity of the flange gap. 3. Apply adjustments by selective tightening if required. 4. Torque incrementally until desired value is reached. 5. Check/re-torque after 4 to 6 hours. Recommendations for flange bolting: ● Check bolts periodically, re-torque as required. ● Use new lens, O-ring and spring washers after removal from installation.  For instructions on replacing the lens, see Part replacement (Page 175). See Flanged Horn with extension (Page 200), Raised-Face Flange per EN 1092-1 (Page 230), Flat-Face Flange (Page 233), and Flanged encapsulated antenna (3"/DN80/80A sizes and larger) (Page 206) for dimensions.
Installing/mounting   4.4 Installation instructions  SITRANS LR250 (PROFIBUS PA) 38 Operating Instructions, 08/2014, A5E32221386-AC 4.4.3 Hygienic versions   WARNING Loss of sanitary approvals Loss of sanitary approvals can result from improper installation/mounting. • Take special care when installing in hygienic or sanitary applications. Comply with installation/mounting guidelines to ensure cleanliness and the ability to keep the wetted parts in a position to be readily cleanable. (See relevant EHEDG/3A documentation - not supplied).   NOTICE Loss of sanitary approvals • For 3-A Sanitary Approved device installation where the customer tank process connection exists, a leak detection port of minimum 2.4 mm diameter must be provided at the lowest point in the process connection where leakage can occur. • If leakage is detected at any time while the device is installed, then the device process connection parts must be disassembled and thoroughly cleaned prior to gasket replacement and reassembly.   Note • For Hygienic encapsulated antenna, the lens acts as a gasket/seal and should be used in conjunction with a cleanable seal as required by the specific process connections (for example, DIN 11864-3).  Hygienic encapsulated antenna leak detection port    ① Orientation mark for leak detection port ② Leak detection port
 Installing/mounting  4.5 Disassembly SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 39 4.5 Disassembly   DANGER Pressure applications Danger to personnel, system and environment will result from improper disassembly. • Never attempt to loosen, remove, or disassemble process connection while vessel contents are under pressure.    WARNING Incorrect disassembly The following dangers may result through incorrect disassembly:  - Injury through electric shock - Danger through emerging media when connected to the process - Danger of explosion in hazardous area In order to disassemble correctly, observe the following: • Before starting work, make sure that you have switched off all physical variables such as pressure, temperature, electricity etc. or that they have a harmless value. • If the device contains dangerous media, it must be emptied prior to disassembly. Make sure that no environmentally hazardous media are released. • Secure the remaining connections so that no damage can result if the process is started unintentionally.
Installing/mounting   4.5 Disassembly  SITRANS LR250 (PROFIBUS PA) 40 Operating Instructions, 08/2014, A5E32221386-AC
 SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 41  Connecting 5 5.1 Basic safety information   NOTICE Condensation in the device Damage to device through formation of condensation if the temperature difference between transportation or storage and the mounting location exceeds 20 °C (68°F). • Before taking the device into operation let the device adapt for several hours in the new environment.    WARNING Missing PE/ground connection Danger of electric shock. Depending on the device version, connect the power supply as follows: • Power plug: Ensure that the used socket has a PE/ground conductor connection. Check that the PE/ground conductor connection of the socket and power plug match each other. • Connecting terminals: Connect the terminals according to the terminal connection diagram. First connect the PE/ground conductor.  5.2 Connecting SITRANS LR250   WARNING Incorrect connection to power source Danger to personnel, system and environment can result from improper power connection. • The DC input terminals shall be supplied from a source providing electrical isolation between the input and output, in order to meet the applicable safety requirements of IEC 61010-1. • All field wiring must have insulation suitable for rated voltages.
Connecting   5.2 Connecting SITRANS LR250  SITRANS LR250 (PROFIBUS PA) 42 Operating Instructions, 08/2014, A5E32221386-AC   WARNING Loss of protection Loss of approvals can result from improper installation. • Check the nameplate on your device, to verify the approval rating. • Use appropriate conduit seals to maintain IP or NEMA rating. • See Wiring setups for hazardous area installations (Page 45).    NOTICE Improper cables and conduit • Separate cables and conduits may be required to conform to standard instrumentation wiring practices or electrical codes.
 Connecting  5.2 Connecting SITRANS LR250 SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 43      ① Use a 2 mm Allen key to loosen the lid-lock set screw c) ④ Cable shield ② Plug (IP68) ⑤ Ground terminal ③ Optional cable glanda) b)(or NPT cable entry)b)     a)May be shipped with the device. b)If cable is routed through conduit, use only approved suitable-size hubs for waterproof applications. c)Not applicable to 3-A Sanitary approved device. Wiring instructions 1. Strip the cable jacket for approximately 70 mm (2.75") from the end of the cable, and thread the wires through the gland. (If cable is routed through conduit, use only approved suitable-size hubs for waterproof applications.) 2. Connect the wires to the terminals as shown: SITRANS LR250 (PROFIBUS PA) is not polarity sensitive. 3. Ground the device according to local regulations. 4. Tighten the gland to form a good seal. 5. Close the lid and secure the locking screw before programming and device configuration.   Note Lid-lock set screw not applicable to 3-A Sanitary approved device.
Connecting   5.2 Connecting SITRANS LR250  SITRANS LR250 (PROFIBUS PA) 44 Operating Instructions, 08/2014, A5E32221386-AC   Note • PROFIBUS PA cable shield must be terminated at both ends of the cable for it to work properly. • If a Weidmüller or other current limiting junction box is connected to this device, please ensure that the current limit is set to 40 mA or higher. • Please refer to the PROFIBUS PA User and Installation Guidelines (order number 2.092) for information on installing PROFIBUS devices at: PROFIBUS PA (http://www.profibus.com/)  Basic PLC configuration with PROFIBUS PA  ① Active PLC ④ DP/PA coupler ② PROFIBUS DP ⑤ PROFIBUS PA ③ PC/laptop ⑥ SITRANS LR250 (PROFIBUS PA)
 Connecting  5.3 Wiring setups for hazardous area installations SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 45 5.3 Wiring setups for hazardous area installations There are three wiring options for hazardous area installations: ● Intrinsically safe wiring (Page 46) ● Non-sparking wiring (Page 49) ● Non-incendive wiring (US/Canada only) (Page 49) In all cases, check the nameplate on your device, confirm the approval rating, and perform installation and wiring according to your local safety codes.  PLC configuration with PROFIBUS PA for hazardous areas  ① PLC (active) ② PC/laptop ③ Ex ia type DP/PA coupler ④ Ex ia device
Connecting   5.3 Wiring setups for hazardous area installations  SITRANS LR250 (PROFIBUS PA) 46 Operating Instructions, 08/2014, A5E32221386-AC 5.3.1 Intrinsically safe wiring Device nameplate (ATEX/IECEx/INMETRO/RCM)  ① ATEX certificate The ATEX and INMETRO certificates listed on the nameplate can be downloaded from our website: Product page (http://www.siemens.com/LR250) Go to Support > Approvals / Certificates.  The IECEx certificate listed on the nameplate can be viewed on the IECEx website. Go to: IECEx (http://iecex.iec.ch/)  Click on Certified Equipment and enter the certificate number IECEx SIR 05.0031X.
 Connecting  5.3 Wiring setups for hazardous area installations SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 47 5.3.1.1 Intrinsically safe wiring (FM/CSA) Device nameplate (FM/CSA)  ① Connection drawing number The FM/CSA Intrinsically Safe connection drawing number 23650675 can be downloaded from our website at: Product page (http://www.siemens.com/LR250) Go to Support > Installation Drawings > Level Measurement > SITRANS LR250. 5.3.1.2 Intrinsically safe wiring (notes) ● For wiring requirements: follow local regulations. ● Approved dust-tight and water-tight conduit seals are required for outdoor NEMA 4X / type 4X / NEMA 6, IP67, IP68 locations. ● Refer to Instructions specific to hazardous area installations (Page 50). Entity concept:  The Entity Concept allows interconnection of intrinsically safe apparatus to associated apparatus not specifically examined in such combination. The criteria for interconnection is that the voltage and current which intrinsically safe apparatus can receive and remain intrinsically safe, considering faults, must be equal to or greater than the output voltage (Uo) and output current (Io) levels which can be delivered by the associated apparatus, considering faults and applicable factors. In addition, the maximum unprotected capacitance (Ci) and Inductance (Li) of the intrinsically safe apparatus, including interconnecting wiring, must be equal to or less than the capacitance and inductance which can be safely connected to associated apparatus. Under the entity evaluation concept, SITRANS LR250 has the following characteristics:  (input voltage) Ui = 24 V (input current) Ii = 250 mA (input power) Pi = 1.2 W (internal capacitance) Ci = 0 (internal inductance) Li = 0
Connecting   5.3 Wiring setups for hazardous area installations  SITRANS LR250 (PROFIBUS PA) 48 Operating Instructions, 08/2014, A5E32221386-AC FISCO Concept   Note For complete details and instructions regarding the FISCO Concept The FM/CSA connection drawing number A5E02358161 can be downloaded from our website at: Product page (http://www.siemens.com/LR250) Go to Support > Installation Drawings > Level Measurement > SITRANS LR250.  The FISCO Concept allows interconnection of intrinsically safe apparatus to associated apparatus not specifically examined in such combination. The criteria for interconnection is that the voltage (Ui or Vmax), the current (Ii, or Imax) and the power (Pi, or Pmax) which intrinsically safe apparatus can receive and remain intrinsically safe, considering faults, must be equal to or greater than the voltage (Uo or Voc or Vi), the current (lo or Isc or li), and the power (Po or Pmax) levels which can be delivered by the associated apparatus, considering faults and applicable factors. In addition, the maximum unprotected capacitance (Ci) and inductance (Li) of each apparatus (other than the termination) connected to the fieldbus must be less than or equal to 5 nF and 10 μH respectively. In each segment only one active device, normally the associated apparatus, is allowed to provide the necessary energy for the fieldbus system. The allowed voltage Uo (or Voc or Vt) of the associated apparatus is limited to the range of 14V dc to 24V dc. All other equipment connected to the bus cable has to be passive, meaning that they are not allowed to provide energy to the system, except for a leakage current of 50 μA for each connected device. Separately powered equipment needs a galvanic isolation to assure that the Intrinsically Safe fieldbus circuit remains passive. Under the FISCO evaluation concept, SITRANS LR250 has the following characteristics:  (input voltage) Ui = 17.5 V (input current) Ii = 380 mA (input power) Pi = 5.32 W (internal capacitance) Ci = 0 (internal inductance) Li = 0
 Connecting  5.4 Instructions specific to hazardous area installations SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 49 5.3.2 Non-sparking wiring  ① ATEX certificate The ATEX certificate listed on the nameplate can be downloaded from our website:  Product page (http://www.siemens.com/LR250)  5.3.3 Non-incendive wiring (US/Canada only)  FM/CSA Class 1, Div 2 connection drawing number 23650673 can be downloaded from our website:  Product page (http://www.siemens.com/LR250)  Go to Support > Installation Drawings > Level Measurement > SITRANS LR250. ● For wiring requirements: follow local regulations. ● Approved dust-tight and water-tight conduit seals are required for outdoor NEMA 4X / type 4X / NEMA 6, IP67, IP68 locations. ● Refer to Instructions specific to hazardous area installations (Page 50).
Connecting   5.4 Instructions specific to hazardous area installations  SITRANS LR250 (PROFIBUS PA) 50 Operating Instructions, 08/2014, A5E32221386-AC 5.4 Instructions specific to hazardous area installations 5.4.1 (Reference European ATEX Directive 94/9/EC, Annex II, 1/0/6) The following instructions apply to equipment covered by certificate number SIRA 06ATEX2359X and SIRA 09ATEX4154X: 1. For use and assembly, refer to the main instructions. 2. The equipment is certified for use as Category 1GD equipment per SIRA 06ATEX2359X, and Category 3G equipment per SIRA 09ATEX4154X. 3. The equipment may be used with flammable gases and vapors with apparatus group IIC, IIB and IIA and temperature classes T1, T2, T3 andT4. 4. The equipment has a degree of ingress protection of IP67 and a temperature class of T100 oC and may be used with flammable dusts. 5. The equipment is certified for use in an ambient temperature range of –40 oC to +80 oC. 6. The equipment has not been assessed as a safety related device (as referred to by Directive 94/9/EC Annex II, clause 1.5). 7. Installation and inspection of this equipment shall be carried out by suitably trained personnel in accordance with the applicable code of practice (EN 60079-14 and EN 60079-17 in Europe). 8. The equipment is non-repairable. 9. The certificate numbers have an ’X’ suffix, which indicates that special conditions for safe use apply. Those installing or inspecting this equipment must have access to the certificates. 10.If the equipment is likely to come into contact with aggressive substances, then it is the responsibility of the user to take suitable precautions that prevent it from being adversely affected, thus ensuring that the type of protection is not compromised. – Aggressive substances: e.g. acidic liquids or gases that may attack metals, or solvents that may affect polymeric materials. – Suitable precautions: e.g. establishing from the material’s data sheet that it is resistant to specific chemicals.
 Connecting  5.4 Instructions specific to hazardous area installations SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 51 Special conditions for safe use (denoted by X after the certificate number) ● Parts of the enclosure may be non-conducting and may generate an ignition-capable level of electrostatic charge under certain extreme conditions. The user should ensure that the equipment is not installed in a location where it may be subjected to external conditions (such as high-pressure steam), which might cause a build-up of electrostatic charge on non-conducting surfaces. ● Aluminium, magnesium, titanium or zirconium may be used at the accessible surface of the equipment. In the event of rare incidents, ignition sources due to impact and friction sparks could occur. This shall be considered when the SITRANS LR250 PROFIBUS PA is being installed in locations that specifically require Equipment Protection level  Ga or Da. ● The equipment shall be infallibly bonded according to the relevant code of practice. ● The end use must ensure that the explosion protection and ingress protection of IP64 is maintained at each entry to the enclosure by use of a blanking element or cable entry device that meets the requirements of the protection concepts type 'n' or increased safety 'e' or flameproof 'd'.
Connecting   5.4 Instructions specific to hazardous area installations  SITRANS LR250 (PROFIBUS PA) 52 Operating Instructions, 08/2014, A5E32221386-AC
 SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 53  Commissioning 6 6.1 Basic safety information   WARNING Loss of explosion protection Danger of explosion when device is not properly commissioned If opening device • Isolate from power. - or - • Ensure that the atmosphere is explosion-free (hot work permit). Ensure device is properly closed before returning to operation.  6.2 Operating via the handheld programmer The handheld programmer used with this device contains lithium batteries that are non-replaceable. Lithium batteries are primary power sources with high energy content designed to provide the highest possible degree of safety.    WARNING Potential hazard Lithium batteries may present a potential hazard if they are abused electrically or mechanically. Observe the following precautions when handling and using lithium batteries: • Do not short-circuit, recharge or connect with false polarity. • Do not expose to temperatures beyond the specified temperature range. • Do not incinerate. • Do not crush, puncture or open cells or disassemble. • Do not weld or solder to the battery’s body. • Do not expose contents to water.
Commissioning   6.2 Operating via the handheld programmer  SITRANS LR250 (PROFIBUS PA) 54 Operating Instructions, 08/2014, A5E32221386-AC 6.2.1 Power up Power up the device. A transition screen showing first the Siemens logo and then the current firmware revision is displayed while the first measurement is being processed.  Press Mode  to toggle between Measurement and Program mode. 6.2.2 Handheld programmer functions The radar device carries out its level measurement tasks according to settings made via parameters. The settings can be modified locally via the Local User Interface (LUI) which consists of an LCD display and a handheld programmer.  A Quick Start Wizard provides an easy step-by-step procedure to configure the device for a simple application. Access the wizards: ● locally [see Quick Start Wizard via the handheld programmer (Page 63)] ● or from a remote location [see Quick Start Wizard via SIMATIC PDM (Page 78)] For more complex setups see Application Examples (Page 67), and for the complete range of parameters see Parameter Reference (Page 107).
 Commissioning  6.2 Operating via the handheld programmer SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 55 6.2.2.1 The LCD display Measurement mode display  Normal operation  ① Toggle indicator a) for analog input function blocks (AIFB 1 or AIFB 2) ⑤ Bar graph indicates level ② Identifies which AIFB is source of displayed value ⑥ Secondary region indicates on request b) electronics temperature, echo confidence, or distance ③ Measured value (level, space, distance, or volume) ⑦ Text area displays status messages ④ Units ⑧ Device status indicator, see Device status icons (Page 180) a) Press UP and DOWN arrow to switch. b) In response to a key press request. For details, see Handheld programmer (Part No. 7ML1930-1BK) (Page 57) for key functions in Measurement mode. Fault present  ① Device status indicator, see Device status icons (Page 180) ② Text area displays a fault code and a status message
Commissioning   6.2 Operating via the handheld programmer  SITRANS LR250 (PROFIBUS PA) 56 Operating Instructions, 08/2014, A5E32221386-AC Program mode display  Navigation view  ① Item band ④ Current item number ② Menu bar ⑤ Current item ③ Current menu     ● A visible menu bar indicates the menu list is too long to display all items. ● A band halfway down the menu bar indicates the current item is halfway down the list. ● The depth and relative position of the item band on the menu bar indicates the length of the menu list, and approximate position of the current item in the list. ● A deeper band indicates fewer items.  Parameter view Edit view     ① Parameter name ② Parameter number ③ Parameter value/selection
 Commissioning  6.2 Operating via the handheld programmer SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 57 6.2.2.2 Handheld programmer (Part No. 7ML1930-1BK) The programmer is ordered separately.  Key functions in measurement mode  Key Function Result  Updates internal enclosure temperature reading. New value is displayed in LCD secondary region.  Updates echo confidence value.  Updates distance measurement  Mode opens PROGRAM mode Opens the menu level last displayed in this power cycle, unless power has been cycled since exiting PROGRAM mode or more than 2 minutes have elapsed since PROGRAM mode was used. Then top level menu will be displayed.  RIGHT arrow opens PROGRAM mode Opens the top level menu.   UP or DOWN arrow toggles between AIFB 1 and AIFB 2. Identifies which AIFB is the source of the displayed value.
Commissioning   6.2 Operating via the handheld programmer  SITRANS LR250 (PROFIBUS PA) 58 Operating Instructions, 08/2014, A5E32221386-AC 6.2.3 Programming   Note • While the device is in PROGRAM mode the output remains active and continues to respond to changes in the device. • The device automatically returns to Measurement mode after a period of inactivity in PROGRAM mode (between 15 seconds and 2 minutes, depending on the menu level).  Change parameter settings and set operating conditions to suit your specific application. For remote operation see Operating via SIMATIC PDM (Page 75). Parameters menu   Note For the complete list of parameters with instructions, see Parameter Reference (Page 107).  Parameters are identified by name and organized into function groups. See LCD menu structure (Page 295).   1. QUICK START 2. SETUP  2.1. IDENTIFICATION  ............ 2.4. LINEARIZATION      2.4.1. VOLUME        2.4.1.1. VESSEL SHAPE
 Commissioning  6.2 Operating via the handheld programmer SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 59 1. Enter PROGRAM mode ● Point the programmer at the display from a maximum distance of 300 mm (1 ft). ● RIGHT arrow   activates PROGRAM mode and opens menu level 1. ● Mode  opens the menu level last displayed in PROGRAM mode within the last 30 minutes, or menu level 1 if power has been cycled since then.  ① Handheld programmer ② Display ③ Maximum distance: 300 mm (1 ft) 2. Navigating: key functions in Navigation mode   Note • In navigation mode ARROW keys move to the next menu item in the direction of the arrow. • For Quick Access to parameters via the handheld programmer, press Home , then enter the menu number, for example: (2.4.1.) Volume.
Commissioning   6.2 Operating via the handheld programmer  SITRANS LR250 (PROFIBUS PA) 60 Operating Instructions, 08/2014, A5E32221386-AC  Key Name Menu level Function   UP or DOWN arrow  menu or parameter Scroll to previous or next menu or parameter.  RIGHT arrow menu Go to first parameter in the selected menu, or open next menu. parameter Open Edit mode.  LEFT arrow menu or parameter Open parent menu.  Mode menu or parameter Change to MEASUREMENT mode.  Home menu or parameter Open top level menu: menu 1. 3. Editing in PROGRAM mode ● Navigate to the desired parameter. ● Press RIGHT arrow  to open parameter view. ● Press RIGHT arrow   again to open Edit mode. The current selection is highlighted. Scroll to a new selection. ● Press RIGHT arrow  to accept it. The LCD returns to parameter view and displays the new selection.      ① Parameter name ② Parameter number ③ Current selection
 Commissioning  6.2 Operating via the handheld programmer SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 61 4. Changing a numeric value ● Navigate to the desired parameter. ● Press RIGHT arrow   to open parameter view. The current value is displayed. ● Press RIGHT arrow   again to open Edit mode. The current value is highlighted. ● Key in a new value. ● Press RIGHT arrow   to accept it. The LCD returns to parameter view and displays the new selection.       ① Parameter name ② Parameter number ③ Current value
Commissioning   6.2 Operating via the handheld programmer  SITRANS LR250 (PROFIBUS PA) 62 Operating Instructions, 08/2014, A5E32221386-AC Key functions in edit mode  Key Name Function     UP or DOWN arrow Selecting options Scrolls to item. Numeric editing • Increments or decrements digits • Toggles plus and minus sign  RIGHT arrow Selecting options • Accepts the data (writes the parameter) • Changes from Edit to Navigation mode Numeric editing • Moves cursor one space to the right • or, with cursor on Enter sign, accepts the data and changes from Edit to Navigation mode  LEFT arrow: Selecting options Cancels Edit mode without changing the parameter. Numeric editing • Moves cursor to plus/minus sign if this is the first key pressed • or moves cursor one space to the left  Clear Numeric editing Erases the display.  Decimal point Numeric editing Enters a decimal point.  Plus or minus sign Numeric editing Changes the sign of the entered value.  to  Numeral Numeric editing Enters the corresponding character.
 Commissioning  6.2 Operating via the handheld programmer SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 63 6.2.3.1 Quick Start Wizard via the handheld programmer   Note • A reset to factory defaults should be performed before running the Quick Start Wizard if the device has been used in a previous application. See Master Reset (4.1.). • The Quick Start wizard settings are inter-related and changes apply only after you select YES in (1.8) Apply? (Apply changes) in the Wizard Complete step. • Do not use the Quick Start wizard to modify parameters: see instead Parameter reference (Page 107). (Perform customization for your application only after the Quick Start has been completed). • Default settings in the parameter tables are indicated with an asterisk (*).  1. Quick Start ● Point the programmer at the display from a maximum distance of 300 mm (1 ft), then press RIGHT arrow   to activate PROGRAM mode and open menu level 1. ● Press RIGHT arrow   twice to navigate to menu item 1.1 and open parameter view. ● Press RIGHT arrow   to open Edit mode or DOWN arrow  to accept default values and move directly to the next item. ● To change a setting, scroll to the desired item or key in a new value. ● After modifying a value, press RIGHT arrow   to accept it and press DOWN arrow  to move to the next item. ● Quick Start settings take effect only after you select Yes to Apply changes from previous steps.  1.1 Language Selects the language to be used on the LCD and takes effect immediately.  Options English, Deutsch, Français, Español 1.2 Material Selects the appropriate echo processing algorithms for the material [see Position Detect (2.5.7.2.) for more detail].  Options  *  LIQUID     LIQUID LOW DK a) (low dielectric liquid – CLEF algorithm enabled)  a) dK < 3.0
Commissioning   6.2 Operating via the handheld programmer  SITRANS LR250 (PROFIBUS PA) 64 Operating Instructions, 08/2014, A5E32221386-AC 1.3 Response Rate Sets the reaction speed of the device to measurement changes in the target range. Use a setting just faster than the maximum filling or emptying rate (whichever is greater).  Options Response Rate (2.3.8.1.) Fill rate (2.3.8.2.)/Empty rate per Minute (2.3.8.3.) SLOW 0.1 m/min (0.32 ft/min) MED 1.0 m/min (3.28 ft/min) FAST  10.0 m/min (32.8 ft/min) 1.4 Units Sensor measurement units.  Options m, cm, mm, ft, in. 1.5 Operating mode  Operation Description NO SERVICE Measurement and associated loop current are not updated, and the device defaults to Fail-safe mode a). LEVEL  Distance to material surface referenced from Low Calibration Point SPACE  Distance to material surface referenced from High Calibration Point DISTANCE Distance to material surface referenced from Sensor reference point  a)  See Material Level (2.5.1.) for more detail.  ① Space ④ High Calibration Point (process full level) ② Level ⑤ Sensor reference point a) ③ Distance ⑥ Low Calibration Point (process empty level) a) The point from which High and Low Calibration points are referenced: see Dimension Drawings.
 Commissioning  6.2 Operating via the handheld programmer SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 65 1.6 Low Calibration Point Distance from Sensor Reference to Low Calibration Point: usually process empty level. (See Operating mode for an illustration.)  Values Range: 0.00 to 20.00 m 1.7 High Calibration Point Distance from Sensor reference point to High Calibration Point: usually process full level. (See Operating mode for an illustration.)  Values Range: 0.00 to 20.00 m 1.8 Apply? (Apply changes)  Options YES, NO, DONE (Display shows DONE when Quick Start is successfully completed.) Press Mode   to return to Measurement mode. SITRANS LR250 is now ready to operate. 6.2.3.2 Auto False Echo Suppression If you have a vessel with known obstructions, we recommend using Auto False Echo Suppression to prevent false echo detection. See (2.5.10.) TVT setup for instructions. This feature can also be used if the display shows a false high level, or the reading is fluctuating between the correct level and a false high level.
Commissioning   6.2 Operating via the handheld programmer  SITRANS LR250 (PROFIBUS PA) 66 Operating Instructions, 08/2014, A5E32221386-AC 6.2.3.3 Requesting an Echo Profile  • In PROGRAM mode, navigate to: Level Meter > (3.) > Diagnostics > (3.1.) > Echo Profile • Press RIGHT arrow  to request a profile.  • Use UP   or DOWN   arrow to scroll to an icon. When an icon is highlighted, that feature becomes active. • To move a cross-hair, press RIGHT   arrow to increase the value, LEFT  arrow to decrease. • To Zoom into an area, position the intersection of the cross-hairs at the center of that area, select Zoom, and press RIGHT   arrow. Press LEFT   arrow to Zoom out. • To update the profile, select Measure and press RIGHT   arrow. • To return to the previous menu, select Exit then press RIGHT   arrow.                         ① confidence ⑥ measure ② algorithm: tF (trueFrist) ⑦ exit ③ distance ⑧ exit icon selected/highlighted ④ TVT ⑨ exit icon deselected ⑤ echo
 Commissioning  6.3 Application examples SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 67 6.2.3.4 Device address   Note See Master Reset (Page 97) to reset Device Address to 126.  The unique address of the device on the network (also called PROFIBUS address).  Values 0 - 126. Default: 126 1. In PROGRAM mode, navigate to: Level Meter > (5.) Communication > (5.1.) Device Address. 2. Press RIGHT arrow , RIGHT arrow , to open parameter view and enable Edit mode. 3. If required, key in a new value and press RIGHT arrow   to accept it. The LCD displays the new value. 4. Press Mode   to return to Measurement mode. 6.3 Application examples   Note In the applications illustrated below, values are for example purposes only.  You can use these examples as setup references. Enter the values in the parameter tables to select the corresponding functions. Configure the basic settings using the Quick Start wizard parameters. (These parameters are inter-related, and changes take effect only after you select YES to apply changes in the final step.) In each example, after performing a Quick Start, navigate to the other required parameters either via the handheld programmer or via SIMATIC PDM and enter the appropriate values.
Commissioning   6.3 Application examples  SITRANS LR250 (PROFIBUS PA) 68 Operating Instructions, 08/2014, A5E32221386-AC 6.3.1 Liquid resin in storage vessel, level measurement   Note Minimum distance from flange face to target is limited by Near Range (2.5.1.).  To obtain level measurement proportional to resin levels: ● Low Calibration Pt. = 5 m (16.4 ft) from sensor reference point ● High Calibration Pt.= 0.5 m (1.64 ft) from sensor reference point ● Max.fill/empty rate = 0.2 m/min (0.65 ft/min) In the event of a loss of echo:  ● SITRANS LR250 is to report a user-defined value of 4.5 m (14.76 ft) after 2 minutes.       ① Sensor reference point ⑤ 5 m ② High calibration point ⑥ Low calibration point ③ 0.5 m ⑦ 0% level ④ 100% level
 Commissioning  6.3 Application examples SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 69  Parameter type Parameter No. /Name Options/ Values Function Quick Start Wizard parameters Material (1.2.) LIQUID   Response Rate (1.3.) MED Medium =1 m/minute Units (1.4.) M meters Operating mode (1.5.) LEVEL Level Low Calibration Point (1.6.) 5 5 m (16.4 ft) High Calibration Point (1.7.) 0.5 0.5 m (1.64 ft) Apply? (Apply changes) (1.8.) YES Transfers Quick Start settings to device. Independent parameters LOE Timer (2.3.6.) 2 2 minutes Mode (2.6.9.1.) Substitute value User-defined value to be used. Value (2.6.9.2) 4.5 4.5 m (14.76 ft) Press Mode   to return to Measurement mode. .  6.3.2 Horizontal vessel with volume measurement   Note The minimum distance from the flange face to the target is limited by Near Range (2.5.1.).  To obtain level measurement proportional to vessel volume in a chemical vessel: ● Low Calibration Point = 3.5 m (11.48 ft) from sensor reference point ● High Calibration Point = 0.5 m (1.64 ft) from sensor reference point ● Max. fill/empty rate = 0.2 m/min (0.65 ft/min) Select vessel shape, Parabolic Ends, and enter values for A and L, to obtain a volume reading instead of level. In the event of a loss of echo: SITRANS LR250 is to report a user-defined value of 4.5 m (14.76 ft) after 2 minutes.
Commissioning   6.3 Application examples  SITRANS LR250 (PROFIBUS PA) 70 Operating Instructions, 08/2014, A5E32221386-AC  ① Sensor reference point ⑥ A = 0.8 m ② 0.5 m ⑦ L = 6 m ③ High calibration point ⑧ 100% = 8000 L ④ 3.5. m  ⑨ Volume reading ⑤ Low calibration point    Parameter type Parameter No./Name Options/ Values Function Quick Start Wizard parameters Material (1.2.) LIQUID   Response Rate (1.3.) MED Medium =1 m/minute Units (1.4.) M meters Operating Mode (1.5.) LEVEL Level is reported as Volume when a vessel shape is selected. Low Calibration Point (1.6.) 3.5 3.5 m (11.48 ft) High Calibration Point (1.7.) 0.5 0.5 m (1.64 ft) Apply? (Apply changes) (1.8) YES Transfers Quick Start settings to device. Independent parameters Vessel Shape (2.4.1.1.) PARABOLIC ENDS Defines vessel shape. Maximum Volume (2.4.1.2.) 8000 8000 liters Vessel Dimension A (2.4.1.3.) 0.8 0.8 m (2.62 ft) Vessel Dimension L (2.4.1.4.) 6 6 m (19.68 ft) LOE Timer (2.3.6.) 2 2 minutes Mode (2.6.9.1.) Substitute value User-defined value to be used. Value (2.6.9.2.) 4.5 4.5 m (14.76 ft) Return to Measurement: press Mode  to start normal operation.
 Commissioning  6.3 Application examples SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 71 6.3.3 Application with stillpipe A stillpipe is recommended for products with a dK of less than 3, or if extremely turbulent or vortex conditions exist. This mounting arrangement can also be used to provide optimum signal conditions on foaming materials.   Note • Near Range (2.5.1.) (Blanking) will be set at the factory. Check the process connection tag for specific values. • Suitable pipe diameters are 40 mm (1.5") to 100 mm (4"). • The pipe diameter must be matched with the antenna size. Use the largest antenna size that will fit the stillpipe/bypass pipe. See Dimension drawings (Page 195). • See Mounting on a Stillpipe or Bypass Pipe (Page 32) for installation guidelines.  This application is to obtain a level measurement and corresponding 4 to 20 mA output proportional to the oil level in a fuel storage vessel. ● Low Calibration Pt. is 5 m (16.4 ft) from the sensor reference point. ● High Calibration Pt. is 0.5 m (1.64 ft) from the sensor reference point. ● The stillpipe inside diameter is 50 mm (1.96"). ● The maximum rate of filling or emptying is about 0.1 m (4")/min.      ① Sensor reference point ⑤ 5 m ② High calibration point ⑥ 50 mm I.D. ③ 0.5 m ⑦ Low calibration point ④ Vent hole
Commissioning   6.3 Application examples  SITRANS LR250 (PROFIBUS PA) 72 Operating Instructions, 08/2014, A5E32221386-AC  Parameter type Parameter No./Name Options/Values Function Quick Start Wizard parameters Introduction NEXT  Continue with Wizard. Language (1.1) NEXT Continue with current language. Material (1.2) LIQUID LOW DK   Response Rate (1.3) MED Medium =1 m/minute Units (1.4) M meters Operating mode (1.5) LEVEL Level is reported as Volume when a vessel shape is selected. Low Calibration Point (1.6) 5 5 m (16.4 ft) High Calibration Point (1.7) 0.5 0.5 m (1.64 ft) Apply? (Apply changes) (1.8) YES Transfers Quick Start settings to device. Independent parameters Propagation Factor (2.5.3.)a) 0.988 P.F. for a 50 mm (1.96") I.D. stillpipe Position Detect (2.5.7.2.) HYBRID   CLEF Range (2.5.7.4.)a) 4.3 Low calibration point - 0.7 m = 4.3 m (14.1 ft)  a) The recommended values for the propagation factor and for CLEF range are dependent on the stillpipe diameter. See Propagation Factor/Stillpipe Diameter for values.  ① sensor reference point ③ low calibration point ② air gap ④ CLEF range 2.5.7.4.  A 700 or 1000 mm (see CLEF Range settings in table below)
 Commissioning  6.3 Application examples SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 73 Propagation Factor/Stillpipe Diameter  Values Range 0.3 to 1.0 depending on pipe size Default 1.0000 Nominal Pipe Size a) 40 mm (1.5") 50 mm (2") 80 mm (3") 100 mm (4") Propagation Factor 0.9844 0.988 0.9935 0.9965 CLEF Range (2.5.7.4.) settings Low calibration point - 700 mm (2.29 ft)b) Low calibration point - 700 mm (2.29 ft)b) Low calibration point - 1000 mm (3.28 ft)b) Low calibration point - 1000 mm (3.28 ft)b)  a) Since pipe dimensions may vary slightly, the propagation factor may also vary. b) CLEF range covers the whole measurement range except first 700 or 1000 mm from sensor reference point    Note Flanged and Hygienic encapsulated antenna  For Flanged encapsulated antenna (7ML5432) and Hygienic encapsulated antenna (7ML5433) match the process connection size to the pipe diameter. For example, DN80/3" flange to DN80/3" pipe.
Commissioning   6.3 Application examples  SITRANS LR250 (PROFIBUS PA) 74 Operating Instructions, 08/2014, A5E32221386-AC
 SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 75  Remote operation 7 7.1 Operating via SIMATIC PDM SIMATIC PDM is a software package used to commission and maintain process devices. Please consult the operating instructions or online help for details on using SIMATIC PDM. You can find more information on versions and compatibility at our website: SIMATIC PDM (www.siemens.com/simatic-pdm). 7.1.1 Functions in SIMATIC PDM   Note • For a complete list of parameters see Parameter Reference (Page 107). • While the device is in PROGRAM mode the output remains active and continues to respond to changes in the device.  SIMATIC PDM monitors the process values, alarms and status signals of the device. It allows you to display, compare, adjust, verify, and simulate process device data; also to set schedules for calibration and maintenance. Parameters are identified by name and organized into function groups. See LCD menu structure (Page 295) for a chart and Changing parameter settings using SIMATIC PDM (Page 83) for more details. The menu structure for SIMATIC PDM is almost identical to that for the LCD. See Parameters accessed via pull-down menus (Page 83) for parameters that do not appear in the menu structure in SIMATIC PDM.
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 76 Operating Instructions, 08/2014, A5E32221386-AC 7.1.1.1 Features of SIMATIC PDM Rev. 6.0, SP4 or higher The graphic interface in the device makes monitoring and adjustments easy.  Feature Function Quick Start (Page 78)  Device configuration for simple applications Echo Profile Utilities (Page 84)  Easy access to echo profile viewing/comparison, TVT shaping, auto false echo suppression and echo setup Auto False Echo Suppression (Page 88)  Screen out false echoes TVT Shaper (Page 86)  Manual TVT adjustment Process Variables (Page 98)  Monitor process variables and level trend Security (Page 104)  Protect security and communication parameters from modification by the maintenance user 7.1.1.2 Features of SIMATIC PDM Rev. 5.2, SP1 SIMATIC PDM Rev. 5.2 SP1 is supported only for basic configuration and troubleshooting. For advanced features such as the Quick Start wizard, Rev. 6.0 SP3 HF2 or higher is required. 7.1.1.3 SIMATIC PDM Version Check the support page of our website to make sure you have the latest version of SIMATIC PDM, the most recent Service Pack (SP) and the most recent hot fix (HF): SIMATIC PDM Version (https://support.automation.siemens.com). Browse to Product Information > Automation Technology > Process control systems > SIMATIC PCS 7 > System components > SIMATIC PDM. 7.1.2 Electronic Device Description (EDD) 7.1.2.1 Updating the Electronic Device Description (EDD) You can locate the EDD in Device Catalog, under Sensors/Level/Echo/SiemensMilltronics/SITRANS LR250. The EDD revision must match the Firmware revision in the device.
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 77 To install a new EDD:  1. Download the most current EDD from our website: Product page (http://www.siemens.com/LR250) 2. Save files to your computer, and extract the zipped file to an easily accessed location. 3. Launch SIMATIC PDM – Manage Device Catalog, browse to the unzipped EDD file and select it. 7.1.2.2 Configuring a new device   Note • Clicking on Cancel during an upload from device to SIMATIC PDM will result in some parameters being updated. • Application Guides for setting up PROFIBUS PA devices with SIMATIC PDM can be downloaded from our website:  Product page (http://www.siemens.com/LR250).  1. Check that you have the most recent EDD, and if necessary update it. [See Updating the Electronic Device Description (EDD) (Page 76)]. 2. Set Address via handheld programmer (default for PROFIBUS PA is 126). [See Device Address (5.1.) to use SIMATIC PDM.] – In PROGRAM mode, navigate to: Level Meter > Communication (5.) > Device Address (5.1.). – Press RIGHT arrow , RIGHT arrow , to open parameter view and enable Edit mode. – If required, key in a new value and press RIGHT   arrow to accept it. The LCD displays the new value. – Press Mode   to return to Measurement mode. 3. Launch SIMATIC Manager and create a new project for the device. 4. Open the menu Device – Master Reset and click on Factory Defaults. 5. After the reset is complete click on Close, then upload parameters to the PC/PG. 6. Configure the device via the Quick Start wizard.
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 78 Operating Instructions, 08/2014, A5E32221386-AC 7.1.3 Quick start wizard via SIMATIC PDM The graphic Quick Start Wizard provides an easy step-by-step procedure that configures the device for a simple application. Please consult the operating instructions or online help for details on using SIMATIC PDM. 1. If you have not already done so, check that you have the most up-to-date Electronic Device Description (EDD) for your device. [See Configuring a new device (Page 77).] 2. Launch SIMATIC Manager and create a new project. Application Guides for setting up HART and PROFIBUS PA devices with SIMATIC PDM can be downloaded from the product page of our website:  Product page (http://www.siemens.com/LR250) Quick start   Note • A reset to Factory Defaults should be performed before running the Quick Start Wizard if device has been used in a previous application. See Master Reset via SIMATIC PDM (Page 97). • The Quick Start wizard settings are inter-related and changes apply only after you click on FINISH AND DOWNLOAD at the end of the last step to save settings offline and transfer them to the device. • Do not use the Quick Start Wizard to modify individual parameters: for quick access to echo profile parameters, see Echo Profile via SIMATIC PDM (Page 85) or see Parameter Reference (Page 107) for a complete list. (Perform customization only after the Quick Start has been completed.) • Click on BACK to return and revise settings or CANCEL to exit the Quick Start. • For a vessel with obstructions see Auto False Echo Suppression via SIMATIC PDM (Page 88).  Launch SIMATIC PDM, open the menu Device – Wizard - Quick Start, and follow steps 1 to 5.  ① Quick Start
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 79 Step 1 – Identification   Note • The layout of the dialog boxes shown may vary according to the resolution setting for your computer monitor. • SITRANS PDM limits the TAG field to a maximum of 24 characters.  1. Click on Read Data from Device to upload Quick Start parameter settings from the device to the PC/PG and ensure PDM is synchronized with the device. 2. If required, change the language for the local user interface. 3. Click on NEXT to accept the default values. (Description, Message, and Installation Date fields can be left blank.)
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 80 Operating Instructions, 08/2014, A5E32221386-AC Step 2 – Application Select the application type (level or volume) and the material, then click on NEXT. See Application with Stillpipe (Page 71) for a Low Dielectric Liquid application.
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 81 Step 3 – Vessel Shape  The vessel shapes shown are predefined.   For a vessel with obstructions, see Auto False Echo Suppression via SIMATIC PDM (Page 88).  Select the vessel shape, and click on NEXT.
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 82 Operating Instructions, 08/2014, A5E32221386-AC Step 4 – Ranges Set the parameters, and click on NEXT.  Step 5 – Summary Check parameter settings, and click on BACK to return and revise values, FINISH to save settings offline, or FINISH AND DOWNLOAD to save settings offline and transfer them to the device.   The message Quick Start was successful will appear. Click on OK.
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 83 7.1.4 Changing parameter settings using SIMATIC PDM   Note • For a complete list of parameters, see Parameter Reference (Page 107). • Clicking on Cancel during an upload from device to SIMATIC PDM will result in some parameters being updated.  Many parameters are accessed via pull-down menus in PDM. See Parameters accessed via pull-down menus (Page 83) for others. 1. Launch SIMATIC PDM, connect to device, and upload data from device. 2. Adjust parameter values in the parameter value field then Enter. The status fields read Changed. 3. Open the Device menu, click on Download to device, then use File - Save to save settings offline. The status fields are cleared.  ① value fields 7.1.5 Parameters accessed via pull-down menus Click on Device or View to open the associated pull-down menus.
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 84 Operating Instructions, 08/2014, A5E32221386-AC Pull-down menus  Device menus View menus Communication path Process Variables (Page 98) Download to device Upload to PC/PG Update Diagnostic Status Device Diagnostics Toolbar Status bar Wizard - Quick Start (Page 78)  Update Echo Profile Utilities (Page 84) Maintenance (Page 91) Acknowledge Faults (Page 93) Wear (Page 93) Simulation (Page 93) Write Locking (Page 96) Master Reset (Page 97) 7.1.5.1 Echo profile utilities Open the menu Device – Echo Profile Utilities and click on the appropriate tab for easy access to: ● Echo profile (Page 85)  ● View Saved Echo Profiles (Page 86) ● TVT Shaper (Page 86)  ● Auto False Echo Suppression (Page 88)  ● Echo Setup (Page 91)
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 85 Echo profile   Note • Double click on each axis to see the Xscale and Data Scale values. • To zoom in to a section of the profile, left-click and drag a marquee around it. Right click inside the window to zoom out. • Expand or compress the x and/or y axes: – Left-click on the axis and drag in either direction to reposition the low end of the scale. – Right-click on the axis and drag in either direction to reposition the high end of the scale. • After saving a profile click on OK, not the x button, to close the Echo Profile Utilities window, otherwise the profile will not be saved.  ● In the Echo Profile Utilities window click the Echo Profile tab. ● Initial profile graph is blank upon entry to dialog. Click Measure to update the profile. ● It is recommended to use the Detailed resolution view of the echo profile for troubleshooting. For faster and more coarse views, the Standard resolution may be used. ● Click Save and in the new window enter a name and click OK. ● Click OK to exit.  ① Resolution ② Echo Profile Time Based Storage
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 86 Operating Instructions, 08/2014, A5E32221386-AC View saved echo profiles To view a saved profile, click on the tab View Saved Echo Profiles. Echo profile data logging You can store up to 60 profiles at a selected interval (maximum 60 minutes). Inside Echo Profile Utilities, in the Echo Profile Time Based Storage window: ● Enter the desired interval between stored profiles. ● Enter the maximum number of profiles to be stored (maximum 60). ● Click on Start. A message appears warning of the time delay and warning that all previous saved profiles will be overwritten. Click on OK to proceed. The new profiles will be saved with their date and time. ● Click on the tab View Saved Echo Profiles to view the stored profiles. TVT Shaper   Note Double click on each axis to see the X scale and data scale values. Right-click or Left-click on the axis and drag to reposition the scale.  This feature allows you to manually adjust the TVT to avoid false echoes caused by obstructions. For an explanation see Auto False Echo Suppression (Page 246).  Open the menu Device – Echo Profile Utilities and click the tab TVT Shaper.
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 87  ①  TVT ② Cursor ③ Echo profile ● Initial profile graph is blank upon entry to dialog. Click on Measure to view and upload the current TVT from device. ● Change the position of the cursor on the TVT using the Point+ and Point– buttons: raise and lower the TVT using Offset+ and Offset-. ● Alternatively, enter values for Point and Offset directly into the dialog boxes. ● Click on Transfer to Device.
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 88 Operating Instructions, 08/2014, A5E32221386-AC 7.1.5.2 Auto false echo suppression   Note • Ensure material level is below all known obstructions when using Auto False Echo Suppression to learn the echo profile. An empty or almost empty vessel is recommended. • Note the distance to material level when learning the echo profile, and set Auto False Echo Suppression Range to a shorter distance to avoid the material echo being screened out. • Set Auto False Echo Suppression and Auto False Echo Suppression Range during startup, if possible. • If the vessel contains an agitator it should be running. • Before adjusting these parameters, rotate the device for best signal (lower false-echo amplitude).  If you have a vessel with known obstructions, use Auto False Echo Suppression to prevent false echo detection. This feature can also be used if the device displays a false high level, or the reading is fluctuating between the correct level and a false high level. The device learns the echo profile over the whole measurement range and the TVT is shaped around all echoes present at that moment. See Auto False Echo Suppression (Page 246) for a more detailed explanation.
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 89 The learned TVT will be applied over a specified range. The default TVT is applied over the remainder of the measurement range.  1. Make sure the material level is below all known obstructions. 2. Determine Auto False Echo Suppression Range. Measure the actual distance from the sensor reference point to the material surface using a rope or tape measure. Subtract 0.5 m (20") from this distance, and use the resulting value. 3. Open the menu Device – Echo Profile Utilities and click on the tab Auto False Echo Suppression. 4. Make sure Auto False Echo Suppression Range is On. 5. Enter the value for Auto False Echo Suppression Range. 6. Click Learn. The message appears: 'This will learn a new echo profile. Once done it cannot be undone'. Click OK. 7. Once Auto TVT is complete click Transfer to Device. To exit click Close. Auto TVT is enabled and the learned TVT will be used. 8. To turn Auto False Echo Suppression off or on, reopen the Auto False Echo Suppression window, change the Auto False Echo Suppression to Off or On, click on Transfer to Device.
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 90 Operating Instructions, 08/2014, A5E32221386-AC Before Auto False Echo Suppression  ① TVT Hover Level ④ Echo marker ② Default TVT ⑤ Material level ③ False echo     After Auto False Echo Suppression  ① False echo ④ Material level ② Learned TVT ⑤ Default TVT ③ Auto False Echo Suppression Range ⑥ Echo marker
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 91 7.1.5.3 Echo setup Provides quick access to echo selection, filtering, and response rate parameters. Open the menu Device – Echo Profile Utilities and click on Echo Setup.  7.1.5.4 Maintenance You can set schedules and reminders for: ● device maintenance based on its projected lifetime ● sensor maintenance based on its projected lifetime ● service ● calibration
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 92 Operating Instructions, 08/2014, A5E32221386-AC  To set Device/Sensor Maintenance schedules: 1. Open the menu Device – Maintenance, and click on the Remaining Device/Sensor Lifetime tab. 2. Modify desired values, and if desired, set reminders for either or both of Reminder 1 before Lifetime (Required)/Reminder 2 before Lifetime (Demanded). 3. Click Write. 4. Click Read, to see the effects of your modification. 5. Click Snooze to add a year to the Total Expected Device Life. To set Service/Calibration schedules: 1. Open the menu Device – Maintenance, and click on the Service/Calibration Schedule tab. 2. Modify desired values and if desired, set reminders for either or both of Reminder 1 before Lifetime (Required)/Reminder 2 before Lifetime (Demanded). 3. Click Write. 4. Click Read, to see the effects of your modification. 5. Click Service/Calibration Performed to reset the schedule.
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 93 7.1.5.5 Acknowledge Faults Open the menu Device – Acknowledge Faults, select the appropriate item from the Extended Diagnostics pull-down menu, and click on Transfer. 7.1.5.6 Wear Reports the number of hours the device has been operating, and the number of times it has been powered up. Open the menu Device – Wear to view: ● Powered Hours ● Power-on Resets 7.1.5.7 Simulation   Note The Simulation parameter influences output to the control system.  Two options enable you to test the functioning of the Analog Input Function Blocks or the functioning of everything between the Transducer Block and Output. For more details see Analog Input Function Blocks 1 and 2 (Page 270). Simulate analog input to AIFB1 or AIFB2 Allows you to input a simulated measured value, status, and quality, in order to test the functioning of an Analog Input Function Block.
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 94 Operating Instructions, 08/2014, A5E32221386-AC 1. Open the menu Device – Simulation, and select the desired function block. 2. Click on the tab Simulation (Measured value).  3. Enable simulation, enter a percentage value, set the desired quality and status, and click on Transfer. See Status Byte (Page 280) for more information on status and quality. 4. The Output value from the desired function block is displayed in PDM, and the LCD displays the substitute value. See Simulate Output below, to set the output mode.  5. After simulation is complete, disable simulation and click on Transfer.
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 95 Simulate output 1. Open the menu Device – Simulation, select function block 1 or 2, and click on the tab Simulation (Output). 2. Select Manual Mode (from options AUTO, Manual, or Out of Service) and click on Transfer.  3. Enter simulated value and click on Transfer. 4. After simulation is complete, return to Simulate Output, reselect AUTO mode, and click on Transfer.
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 96 Operating Instructions, 08/2014, A5E32221386-AC Simulate input 1. Open the menu Device – Simulation, and select Simulation (Input).  2. To enable simulation select Fixed or Ramp. 3. If you select Ramp, enter the step length and number of steps. 4. Enter the simulated value and click on Transfer. 5. After simulation is complete, disable simulation and click on Transfer. 7.1.5.8 Write locking Prevents any changes to parameters via PDM or the hand-held programmer. If Write Locking is enabled, the data can be viewed but not modified. To enable/disable Write Locking 1. Open the menu Device – Write Locking and turn Write Protection On or Off. 2. Click on Transfer.
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 97 7.1.5.9 Master reset  Options Result Factory defaults Resets all parameters to the manufacturer’s default settings, with certain exceptions: see Factory defaults (Page 97). Standard defaults Resets all resettable parameters excluding device addresses to the PROFIBUS default settings. Informational Resets Tag parameter. Functional Resets parameters that control device behavior, such as Low Calibration Pt. Warm start Has the same effect as recycling power to the device. Reset address to 126 Resets the PROFIBUS device address to 126.  If the address lock was on, will disable the lock. 7.1.5.10 Factory defaults Factory Defaults resets all user parameters to the default settings, with certain exceptions. The list of exceptions includes, but is not limited to: ● Tag ● Message ● Descriptor ● Installation Data ● Device Address ● Write Protection ● Auto False Echo Suppression Range ● Learned TVT To perform a reset to Factory Defaults: 1. Open the menu Device – Master Reset, and click on Factory Defaults. 2. After the reset is complete click on Close, then upload parameters to the PC/PG. (If you are performing a reset after replacing the device with a different instrument, do not upload parameters to the PC/PG.) Resetting the PROFIBUS address to 126 1. Open the menu Device – Master Reset and click on Reset Address to 126. 2. Click on OK: the address will be reset to 126, and if the address lock was on, it will be disabled.
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 98 Operating Instructions, 08/2014, A5E32221386-AC 7.1.5.11 Diagnostics You can monitor level/volume trends, function blocks, electronics temperature, and device status. Process variables To compare outputs in real time open the menu View – Process Variables.   Note To view peak sensor values, peak FB1 and FB2 values, or peak electronics temperatures, see Device Diagnostics (Page 101).  ● Sensor Value and simulation setting ● Electronics temperature ● Measured Value (level, volume, and distance) together with quality and status.
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 99 Function blocks Open the menu View – Process Variables and click on Function Blocks to view the channel (level, volume, space, or distance), operating mode (Auto, Manual, or Out of Service), quality, status, simulation setting, and summary of alarms.
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 100 Operating Instructions, 08/2014, A5E32221386-AC Trend view Open the menu View – Process Variables and click on Trend View to monitor Sensor Value and values for AIFB1 and AIFB2.  ① trend line ② trend lines
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 101 Device diagnostics Device status Open the menu View – Device Diagnostics and go to Device Status to view Diagnostics, Device Status, Extended Diagnostics, and Maintenance. Diagnostics In the Device Status window, click on the Diagnostics tab, then on the Update diagnostics button, to update diagnostic information and refresh linked icons.  ① Update diagnostics
Remote operation   7.1 Operating via SIMATIC PDM  SITRANS LR250 (PROFIBUS PA) 102 Operating Instructions, 08/2014, A5E32221386-AC Device Status Click on the Device Status tab to view peak sensor values, peak FB1 and FB2 values, and peak electronics temperatures.
 Remote operation  7.1 Operating via SIMATIC PDM SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 103 Analog Input 1/Analog Input 2 Open the menu View – Device Diagnostics and go to Analog Input 1/Analog Input 2. Click on the tab Overview to see the status of all warnings and alarms. Click on the tab Alarms and Warnings for details.  Update Open the menu View – Update to refresh the screen.
Remote operation   7.2 Operating via FDT  SITRANS LR250 (PROFIBUS PA) 104 Operating Instructions, 08/2014, A5E32221386-AC Security A password option protects security and communication control parameters from modification by a maintenance user. When you open a project the User dialog window provides two options: maintenance or specialist. If a password has been set it will not be possible to open the project as a specialist without it. A maintenance user will be able to open the project without a password but will not have access to security and communication control parameters. 1. Open a project, double-click on the device icon, and in the User window select Specialist. 2. Open the menu Options – Settings and click on the Password tab. 3. Enter a new password and re-enter it in the Confirmation window. Click on OK.
 Remote operation  7.2 Operating via FDT SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 105 7.2 Operating via FDT FDT is a standard used in several software packages designed to commission and maintain field devices. Two commercially available FDTs are PACTware and Fieldcare. Functionally FDT is very similar to PDM. See Operating via SIMATIC PDM (Page 75) for more detail. ● To configure a field device via FDT you need the DTM (Device Type Manager) for the device. ● To configure a field device via SIMATIC PDM, you need the EDD (Electronic Data Description) for the device. 7.2.1 Device Type Manager (DTM) A DTM is a type of software that ’plugs into’ FDT. It contains the same information as an EDD but an EDD is independent of the operating system. 7.2.2 SITRANS DTM ● SITRANS DTM is an EDDL interpreter developed by Siemens to interpret the EDD for that device. ● To use SITRANS DTM to connect to a device, you must first install SITRANS DTM on your system and then install the device EDD written for SITRANS DTM. ● You can download SITRANS DTM from the Siemens service and support website. Go to Service & Support (http://www.siemens.com/automation/service&support), click on Product Support, and drill down to Product Information/Automation Technology/Sensor systems/Process Instrumentation/Software & Communications.
Remote operation   7.2 Operating via FDT  SITRANS LR250 (PROFIBUS PA) 106 Operating Instructions, 08/2014, A5E32221386-AC 7.2.3 The device EDD The SITRANS LR250 PROFIBUS PA EDD for SITRANS DTM can be downloaded from our website:  Product page (http://www.siemens.com/LR250).  Go to Support > Software Downloads.  7.2.4 Configuring a new device via FDT The full process to configure a field device via FDT is outlined in an Application Guide which can be downloaded from our website under Support > Application Guides.  Product page (http://www.siemens.com/LR250)
 SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 107  Parameter reference 8    Note • Parameter names and menu structure are almost identical for SIMATIC PDM and the local user interface (LUI). • Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. • Mode   toggles between PROGRAM and Measurement Modes. • For Quick Access to parameters via the handheld programmer, press Home , then enter the menu number, for example: 2.2.1. • In Navigation mode, ARROW keys (    ) navigate the menu in the direction of the arrow. • Press RIGHT arrow   to open Edit Mode, or to save a modification.  Parameters are identified by name and organized into function groups. See LCD menu structure (Page 295) for a chart.  Parameters accessible via the handheld programmer are followed by the device menu number in parenthesis. Parameters not followed by a number are accessible only via remote operation. For more details see: ● Operating via SIMATIC PDM (Page 75) The Quick Start wizard provides an easy step-by-step procedure to configure the device for a simple application. Quick Start (1.)   Note • Do not use the Quick Start wizard to modify individual parameters. (Perform customization only after the Quick Start has been completed.) • For access via remote operation see Quick Start Wizard via SIMATIC PDM (Page 78). • For detailed instructions see Quick Start Wizard via the handheld programmer (Page 63).
Parameter reference    SITRANS LR250 (PROFIBUS PA) 108 Operating Instructions, 08/2014, A5E32221386-AC Language (1.1.)  Material (1.2.)  Response Rate (1.3.)  Units (1.4.)  Operating Mode (1.5.)  Low Calibration Point (1.6.)   High Calibration Point (1.7.)  Apply? (Apply changes) (1.8.)  Setup (2.)   Note • Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. • Values shown in the following tables can be entered via the handheld programmer.  Identification (2.1.)
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 109 Tag (2.1.1.)   Note SITRANS PDM limits the TAG field to a maximum of 24 characters.  Text that can be used in any way. A recommended use is as a unique label for a field device in a plant. Limited to 32 ASCII characters. Descriptor (2.1.2.) Text that can be used in any way. Limited to 32 ASCII characters. No specific recommended use. Message (2.1.3.) Text that can be used in any way. Limited to 32 ASCII characters. No specific recommended use.  Device (2.2.)  Hardware Revision (2.2.1.) Read only. Corresponds to the electronics hardware of the Field Device. Firmware Revision (2.2.2.) Read only. Corresponds to the software or firmware that is embedded in the Field Device. Loader Revision (2.2.3.) Read only. Corresponds to the software used to update the Field Device. Order Option (2.2.4.) Read only. Displays the device type. Sensor (2.3.)
Parameter reference    SITRANS LR250 (PROFIBUS PA) 110 Operating Instructions, 08/2014, A5E32221386-AC Unit (2.3.1) Sensor measurement unit.  Values m, cm, mm, ft, in Default: m  Level Unit (2.3.2.) Select engineering units for Level.  Options    m, cm, mm, ft, in, % *  % PV Units (volume/level) (2.3.3.)   Note • A greater selection of volume units is available via SIMATIC PDM. • Default unit of AIFB1 or 2 is percent. • You can select a different unit for your application. • PV (Primary Value): the output from the Level Transducer Block. See Transducer Block function groups (Page 267) and How the Transducer Block works (Page 268) for more details.  Select units for either volume or level.  Level values    m, cm, mm, ft, in Volume values    liter, gal Percent value  *  % Temperature Units (2.3.4.) Selects the engineering unit to be displayed with the value representing temperature.  Options    DEG C, DEG F, RANKINE, KELVIN *  DEG C
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 111 Material (2.3.5.) Automatically configures the device to operate in the chosen application type, by changing one or more of the following parameters: Propagation Factor (2.5.3.), Position Detect (2.5.7.2.), and/or CLEF Range (2.5.7.4.).  Options  *  LIQUID  LIQUID LOW DK a) (low dielectric liquid - CLEF algorithm enabled) Related parameters Propagation Factor (2.5.3.) Position Detect (2.5.7.2.) CLEF Range (2.5.7.4.)  a) dK < 3.0  You can configure each of the related parameters, to suit your particular application. LOE Timer (2.3.6.)   Note When a Loss of Echo occurs Value (2.6.9.2.) determines the material level to be reported when LOE Timer expires. See Loss of Echo (LOE) (Page 250) for more detail.  Sets the time to elapse since the last valid reading, before the Fail-safe material level is reported.  Values Range: 0 to 720 seconds Default: 100 s Calibration (2.3.7)   Note We recommend using the Quick Start wizard to configure the device.  Low Calibration Pt. (2.3.7.1.) Distance from sensor reference point to Low Calibration Point (corresponding to Low Level Point). Units are defined in Unit (2.3.1.).
Parameter reference    SITRANS LR250 (PROFIBUS PA) 112 Operating Instructions, 08/2014, A5E32221386-AC  ① High level point (default: 100%) ⑥ Level offset (if used) ② Low level point (default: 0%) ⑦ Low calibration point a) ③ Sensor value ⑧ Sensor reference point ④ High calibration point ⑨ Far range ⑤ Level   a) Sensor reference point is the point from which level measurement is referenced. See Threaded Horn Antenna with extension (Page 195), Flanged Horn with extension (Page 200), and Flanged encapsulated antenna (3"/DN80/80A sizes and larger). (Page 206)  Values Range: 0 to 20 m. Default 20.00 m Related parameters Unit (2.3.1.), Far Range (2.5.2.) High Calibration Pt. (2.3.7.2.) Distance from sensor reference point 1) to High Calibration Point (corresponding to High Level Point). Units are defined in Unit (2.3.1.).  Values Range: 0 to 20 m. Default 0.00 m Related parameters Unit (2.3.1.), Near Range (2.5.1.) When setting the High Calibration Point value, note that echoes are ignored within Near Range (2.5.1.). 1) The value produced by the echo processing which represents the distance from sensor reference point to the target. [see Threaded Horn Antenna with extension, (Page 198) Flanged Horn with extension (Page 202), and Flanged encapsulated antenna (3"/DN80/80A sizes and larger) (Page 206)].
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 113 Sensor Offset (2.3.7.3.) A constant offset that can be added to or subtracted from the sensor value to compensate for a shifted sensor reference point. (For example, when adding a thicker gasket or reducing the standoff/nozzle height.) Sensor value is the value produced by the echo processing which represents the distance from sensor reference point to the target. (see Calibration (2.3.7.) for an illustration).The units are defined in Unit (2.3.1.).  Values Range: -99.999 to 99.999. Default: 0.00 m Related parameters Units (2.3.1.) Low Level Point (2.3.7.4.) The level when the material is at Low Calibration Point. The unit is defined in Level units.  Values Range: -999999.00 to 999999.00. Default: 0% High Level Point (2.3.7.5.) The level when the material is at High Calibration Point. The unit is defined in Level units.  Values Range: -999999.00 to 999999.00. Default: 100% Level Offset (2.3.7.6.) A constant offset that can be added to Level. The unit is defined in Level units.  Values Range: -999999.00 to 999999.00. Default: 0% Rate (2.3.8.)   Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 114 Operating Instructions, 08/2014, A5E32221386-AC Response Rate (2.3.8.1.)   Note Changing Response Rate resets Fill Rate (2.3.8.2), Empty rate (2.3.8.3), and Filter Time Constant (2.6.8.1.).  Sets the reaction speed of the device to measurement changes.  Response Rate (2.3.8.1.) Fill Rate (2.3.8.2.) Empty rate (2.3.8.3.) Filter Time Constant (2.6.8.1.) *  Slow  0.1 m/min (0.32 ft/min) 10 s  Medium 1.0 m/min (3.28 ft/min) 10 s  Fast 10.0 m/min (32.8 ft/min) 0 s Use a setting just faster than the maximum filling or emptying rate (whichever is faster). Fill Rate (2.3.8.2.) Defines the maximum rate at which the reported sensor value is allowed to decrease. Allows you to adjust the SITRANS LR250 response to decreases in the actual material level. Fill Rate is automatically updated whenever Response rate (2.3.8.1.) is altered.  Options Range: 0 to 99999 m / min. Response rate (2.3.8.1.) Fill rate *  Slow  0.1 m/min (0.32 ft/min)  Medium 1.0 m/min (3.28 ft/min)  Fast 10.0 m/min (32.8 ft/min) Altered by: Response rate (2.3.8.1.) Related parameters Level unit (2.3.2.) Enter a value slightly greater than the maximum vessel-filling rate, in units per minute.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 115 Empty Rate (2.3.8.3) Defines the maximum rate at which the reported sensor value is allowed to increase. Adjusts the SITRANS LR250 response to increases in the actual material level. Empty Rate is automatically updated whenever Response Rate (2.3.8.1.) is altered.  Options Range: 0 to 999999 m / min. Response Rate (2.3.8.1.) Empty Rate *  Slow  0.1 m/min (0.32 ft/min)  Medium 1.0 m/min (3.28 ft/min)  Fast 10.0 m/min (32.8 ft/min) Altered by: Response Rate (2.3.8.1) Related parameters Level Unit (2.3.2.) Enter a value slightly greater than the vessel’s maximum emptying rate, in units per minute. Linearization (2.4.)  Volume (2.4.1.) Carries out a volume conversion from a level value.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 116 Operating Instructions, 08/2014, A5E32221386-AC Vessel Shape (2.4.1.1.) Defines the vessel shape and allows the LR250 to calculate volume instead of level. If None is selected, no volume conversion is performed. Select the vessel shape matching the monitored vessel or reservoir.   Vessel Shape LCD DISPLAY/ Description Also required *  None NONE/ No volume calculation required N/A   CYLINDER/ Flat end horizontal cylinder Maximum volume   SPHERE/ Sphere Maximum volume     LINEAR/ Upright, linear (flat bottom) Maximum volume   CONICAL BOT/ Conical or pyramidal bottom Maximum volume, dimension A     PARABOLIC BOT/Parabolic bottom Maximum volume, dimension A     HALF SPHERE BOT/ Half-sphere bottom Maximum volume, dimension A
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 117  Vessel Shape LCD DISPLAY/ Description Also required     FLAT SLOPED BOT/ Flat sloped bottom Maximum volume, dimension A     PARABOLIC ENDS/ Parabolic end horizontal cylinder Maximum volume, dimension A, dimension L     LINEAR TABLE a) / Linearization table (level/volume breakpoints) Maximum volume, tables 1-32 level and volume breakpoints  a)  Linearization Table must be selected in order for level/volume values [see XY index (2.4.1.5.)] to be transferred.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 118 Operating Instructions, 08/2014, A5E32221386-AC Maximum Volume (2.4.1.2.) The maximum volume of the vessel. Units are defined in PV Units (volume/ level) (2.3.3.). Enter the vessel volume corresponding to High Calibration Point. The volume calculation is based on the maximum volume and scaled according to the vessel shape selected. If no vessel shape is entered, the default is 100, and the reading will be a percentage value.  Values Range: 0.0000 to 999999 Default: 100.0 Related Parameters Low Calibration Pt. (2.3.7.1.) High Calibration Pt. (2.3.7.2.) Vessel Shape (2.4.1.1.) For readings in volumetric units instead of percentage values: 1. Select a volumetric unit from PV Units (volume/level) (2.3.3.). 2. Enter the vessel volume corresponding to High Calibration Point. Dimension A (2.4.1.3.) The height of the vessel bottom in Level Units when the bottom is conical, pyramidal, parabolic, spherical, or flat -sloped. If the vessel is horizontal with parabolic ends, the depth of the end. See Vessel Shape (2.4.1.1.) for an illustration.  Values Range: 0.0000 to 999999 in Level Units Default: 0.0 Related Parameters Vessel Shape (2.4.1.1.) Dimension L (2.4.1.4.) Length of the cylindrical section of a horizontal parabolic end vessel, in Level Units. See Vessel Shape (2.4.1.1.) for an illustration.  Values  Range: 0.0000 to 999999 in Level Units Default: 0.0 Related Parameters Vessel Shape (2.4.1.1.)
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 119 XY index (2.4.1.5.) Level/Volume breakpoints allow you to define a complex vessel shape as a series of segments. A value is assigned to each level breakpoint and a corresponding value is assigned to each volume breakpoint.  Volume values are defined in volume units and can be percent or volumetric; level values are defined in level units, and can be percent or linear. See Level Unit (2.3.2.) and PV Units (volume/level) (2.3.3.).  Level values Range: -999999.00 to 999999.00 (m, cm, mm, ft, in, %) Default: 0.0 Volume values Range: -999999.00 to 999999.00 (% or volumetric units) Default: 0.0 Enter up to 32 level breakpoints, where the corresponding volume is known. The values corresponding to 100% and 0% levels must be entered. The breakpoints can be ordered from top to bottom, or the reverse.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 120 Operating Instructions, 08/2014, A5E32221386-AC Example (values are for example purposes only)   Breakpoint Number Level value (m) Volume value (l) 1  0  0 2  5  500 3  9  3000 4  19.5 8000 Entering breakpoints via the hand-held programmer: 1. The default for level values is percent: if you want to select units instead, navigate to Setup (2.) > Sensor (2.3.) > Level Unit (2.3.2.), and select the desired unit. 2. Navigate to Setup (2.) > Sensor (2.3.) > PV Units (volume/level) (2.3.3.), and select the desired volume units. 3. Go to XY index (2.4.1.5.) and enter the number of the breakpoint you wish to adjust: for example, for breakpoint 1 enter 1. 4. Go to X value (2.4.1.6.) and enter the level value for the breakpoint just identified. 5. Go to Y value (2.4.1.7.) and enter the volume value for the breakpoint just identified. 6. Repeat steps 3 to 5 until values have been entered for all required breakpoints. X value (2.4.1.6.)  Y value (2.4.1.7.)
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 121 Signal Processing (2.5.)   Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated.  Near Range (2.5.1.) The range in front of the device (measured from the sensor reference point) within which any echoes will be ignored. (This is sometimes referred to as blanking or a dead zone.) The factory setting is 50 mm (2") past the end of the antenna, and the default is dependent on the antenna type and process connection. [See Dimension drawings (Page 195) for antenna heights.]  Values Range: 0 to 20 m (0 to 65.6 ft) Default depends on antenna type and process connection.  Examples: 1.5" threaded horn 185.3 mm (7.3") 4" horn with stainless steel flange 100 mm (4") extension 373.3 mm (14.7") Related parameters Units (2.3.1.)  Far Range (2.5.2.)   Note Far Range can extend beyond the bottom of the vessel.  Allows the material level to drop below Low Calibration Point without generating a Loss of Echo (LOE) state. See Low Calibration Pt. (2.3.7.1.) for an illustration.  Values Range: Min. = Low Calibration Pt. Max. = 23 m (75.45 ft) Default: Value for Low Calibration Pt. + 1 m (3.28 ft) Related parameters Units (2.3.1.) Use this feature if the measured surface can drop below the Low calibration point in normal operation.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 122 Operating Instructions, 08/2014, A5E32221386-AC Propogation Factor (2.5.3.)   Note • When operating in a stillpipe, values for CLEF Range (2.5.7.4.), and for the propagation factor, should be set according to the pipe size. See the table below. • For reliable results, the antenna size must be close to the pipe size.  Compensates for the change in microwave velocity due to propagation within a metal stillpipe instead of in free space.  Values Range:  0.3 to 1.0 depending on pipe size. Default:  1.0000 Nominal Pipe Sizea) 40 mm (1.5") 50 mm (2") 80 mm (3") 100 mm (4") Propagation Factor 0.9844 0.988 0.9935 0.9965 CLEF Range (2.5.7.4.) Low calibration point - 700 mm (2.29 ft)b) Low calibration point - 700 mm (2.29 ft)b) Low calibration point - 1000 mm (3.28 ft)b) Low calibration point - 1000 mm (3.28 ft)b) a) Since pipe dimensions may vary slightly, the propagation factor may also vary. b) CLEF range covers the whole measurement range except first 700 or 1000 mm from unit reference point (see A in graphic below)
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 123   ① sensor reference point ③ low calibration point ② air gap ④ CLEF range 2.5.7.4. A 700 or 1000 mm   Note Flanged encapsulated antenna For Flanged encapsulated antenna (7ML5432) match the process connection size to the pipe diameter whenever possible (for example, mount a DN80/3" flange on DN80/3" pipe).  Minimum Sensor Value (2.5.4.) The minimum recorded Sensor value in units defined in Unit (2.3.1.). 1. Open the menu View – Device Diagnostics, select Device Status, and click on the Device Status tab. 2. Check Sensor Peak Values. Maximum Sensor Value (2.5.5.) The maximum recorded Sensor value in units defined in Unit (2.3.1.). 1. Open the menu View – Device Diagnostics, select Device Status, and click on the Device Status tab. 2. Check Sensor Peak Values.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 124 Operating Instructions, 08/2014, A5E32221386-AC Shots (2.5.6.) The number of echo profile samples averaged to produce a measurement.  Values Range: 1 to 25 Default: 25 Echo Select (2.5.7.)  Algorithm (2.5.7.1.) Selects the algorithm to be applied to the echo profile to extract the true echo.  Options  * tF True First echo  L Largest echo  BLF Best of Largest and First echo Position Detect (2.5.7.2.)   Note If a stillpipe is used, the setting for CLEF range is determined by the horn size: see CLEF Range (2.5.7.4.) for a table of values.  Defines where on the echo the distance measurement is determined.  Options    Center *  Hybrid (Center and CLEF)  CLEF (Constrained Leading Edge Fit) Related parameters    CLEF Range (2.5.7.4.) If the vessel bottom is being reported as the level instead of the actual material level (at low level conditions), or if the dielectric constant of the liquid to be monitored is less than 3, we recommend setting Position Detect to Hybrid and CLEF Range (2.5.7.4.) to 0.5 m (1.64 ft).
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 125 Echo Threshold (2.5.7.3.) Sets the minimum echo confidence that the echo must meet in order to prevent a Loss of Echo condition and the expiration of the Fail-safe (LOE) timer. When Confidence (2.5.9.1.) exceeds Echo Threshold (2.5.7.3.), the echo is accepted as a valid echo and is evaluated.  Values Range: 0 to 99 Default: 5 Related Parameters Timer (2.3.6.) Use this feature when an incorrect material level is reported. CLEF Range (2.5.7.4.)   Note CLEF Range is referenced from Low Calibration Point (process empty level).  The CLEF algorithm is used mainly to allow correct level reporting for low dK materials which may otherwise cause an incorrect reading in an empty or almost empty vessel. It is used from Low Calibration Point (process empty level ) up to the level defined by CLEF Range (see illustration below). Above that point the Center algorithm is used. For more detail see CLEF Range (Page 245).  Values Range: 0 to 20 m (0 to 65.6 ft) Default: 0.0 m Related parameters Position Detect (2.5.7.2.)  ① CLEF Range ② Sensor reference point ③ Low calibration point (process empty level) In applications with low dK materials we recommend setting CLEF Range to 0.5 m (1.64 ft) and Position Detect (2.5.7.2.) to Hybrid.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 126 Operating Instructions, 08/2014, A5E32221386-AC Sampling (2.5.8.) Provides a method of checking the reliability of a new echo before accepting it as the valid reading, based on numbers of samples above or below the currently selected echo. Echo Lock (2.5.8.1.)   Note Ensure the agitator is always running while SITRANS LR250 is monitoring the vessel, to avoid stationary blade detection.  Selects the measurement verification process. See Echo Lock (2.5.8.1.) for more details.  Options    Lock Off (no verification)  Maximum Verification (not recommended for radar) *  Material Agitator  Total Lock (not recommended for radar) Related parameters    Fill Rate (2.3.8.2.) Empty rate (2.3.8.3.) Sampling up (2.5.8.2.) Sampling down (2.5.8.3.) For radar applications, Material Agitator is the most often-used setting, to avoid agitator blade detection. Sampling Up (2.5.8.2.) Specifies the number of consecutive echoes that must appear above the echo currently selected, before the measurement is accepted as valid.  Values Range: 1 to 50 Default: 5 Sampling Down (2.5.8.3.) Specifies the number of consecutive echoes that must appear below the echo currently selected, before the measurement is accepted as valid.  Values Range: 1 to 50 Default: 2 Echo Quality (2.5.9.)
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 127 Confidence (2.5.9.1.) Indicates echo reliability: higher values represent better echo quality. The display shows the echo confidence of the last measurement. Echo Threshold (2.5.7.3.) defines the minimum criterion for echo confidence.  Values  (view only) 0 to 99  ----  Shot not used Related Parameters Echo Threshold (2.5.7.3.) Open the menu Device – Echo Profile Utilities and click on the tab Echo Profile. Echo Strength (2.5.9.2.) Displays the absolute strength (in dB above 1 μV rms) of the echo selected as the measurement echo.  Values  (view only) -22 to 99 Open the menu Device – Echo Profile Utilities and click on the tab Echo Profile. TVT Setup (2.5.10.)   Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 128 Operating Instructions, 08/2014, A5E32221386-AC Auto False Echo Suppression (2.5.10.1.) Used together with Auto False Echo Suppression Range (2.5.10.2.) to screen out false echoes in a vessel with known obstructions. A ’learned TVT’ (time varying threshold) replaces the default TVT over a specified range. See Auto False Echo Suppression (Page 242) for a more detailed explanation.   Note • Make sure material level is below all known obstructions when Auto False Echo Suppression is used to learn the echo profile. (An empty or almost empty vessel is recommended.) • Note the distance to material level when Auto False Echo learns the environment. Set Auto False Echo Suppression Range to a shorter distance to avoid the material echo being screened out. • Set Auto False Echo Suppression and Auto False Echo Suppression Range during startup, if possible. • If the vessel contains an agitator it should be running. • Before adjusting these parameters, rotate the device for best signal (lower false-echo amplitude).  Before Auto False Echo Suppression  ① TVT Hover Level ④ echo marker ② default TVT ⑤ material level ③ false echo
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 129 After Auto False Echo Suppression   ① false echo ④ material level ② learned TVT  ⑤ default TVT ③ Auto False Echo Suppression Range ⑥ echo marker To set Auto False Echo Suppression via SIMATIC PDM: Open the menu Device – Echo Profile Utilities and click on the tab Auto False Echo Suppression. For more detailed instructions see Auto False Echo Suppression via SIMATIC PDM (Page 246).
Parameter reference    SITRANS LR250 (PROFIBUS PA) 130 Operating Instructions, 08/2014, A5E32221386-AC To set Auto False Echo Suppression via the handheld programmer:   Options    OFF Default TVT will be used. *  ON ’Learned’ TVT will be used.   LEARN  ’Learn’ the TVT. 1. Determine Auto False Echo Suppression Range. Measure the actual distance from the sensor reference point to the material surface using a rope or tape measure. 2. Subtract 0.5 m (20") from this distance, and use the resulting value. 3. Go to Auto False Echo Suppression Range (2.5.10.2.) and enter the value calculated in step 2. 4. Go to Auto False Echo Suppression (2.5.10.1.) and press RIGHT arrow to open Edit Mode. 5. Select Learn. The device will automatically revert to On (Use Learned TVT) after a few seconds. Auto False Echo Suppression Range (2.5.10.2.) Defines the endpoint of the Learned TVT distance. Units are defined in Unit (2.3.1.).  Values Range: 0.00 to 20.00 m Default: 1.00 m 1. Press RIGHT arrow to open Edit mode. 2. Enter the new value and press RIGHT arrow to accept it. 3. Set Auto False Echo Suppression (2.5.10.1.). Hover Level (2.5.10.3.) Defines how high the TVT (Time Varying Threshold) is placed above the noise floor of the echo profile, as a percentage of the difference between the peak of the largest echo in the profile and the noise floor. See Auto False Echo Suppression (2.5.10.1.) for an illustration.  Values Range: 0 to 100% Default: 40% When the device is located in the center of the vessel, the TVT hover level may be lowered to increase the confidence level of the largest echo.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 131 Shaper Mode (2.5.10.4.) Enables/disables TVT shaper (2.5.11.)  Options    ON *  OFF TVT shaper (2.5.11.)   Note • The range is –50 to 50 dB. • Shaper Mode (2.5.10.4.) must be turned ON in order for TVT shaper points to be transferred.  Adjusts the TVT (Time Varying Threshold) at a specified range (breakpoint on the TVT). This allows you to reshape the TVT to avoid unwanted echoes. There are 40 breakpoints arranged in 5 groups. (We recommend using SIMATIC PDM to access this feature.) To use TVT shaper via SIMATIC PDM: 1. Go to Level Meter > Setup > Signal Processing > TVT setup > Shaper Mode and select On. 2. Open the menu Device – Echo Profile Utilities and click on TVT Shaper. For more detail see TVT Shaper via SIMATIC PDM (Page 86). To use TVT shaper via LUI (local user interface):  1. Go to Shaper Mode (2.5.10.4.) and select ON. 2. In TVT shaper, go to Breakpoints 1-9 (2.5.11.1.). 3. Open Breakpoint 1 and enter the TVT Offset value (between –50 and 50 dB). 4. Go to the next Breakpoint and repeat step 3 until all desired breakpoint values have been entered. Breakpoint 1-9 (2.5.11.1.)  Values Range: –50 to 50 dB Default: 0 dB
Parameter reference    SITRANS LR250 (PROFIBUS PA) 132 Operating Instructions, 08/2014, A5E32221386-AC Breakpoint 10-18 (2.5.11.2.)  Values Range: –50 to 50 dB Default: 0 dB Breakpoint 19-27 (2.5.11.3.)  Values Range: –50 to 50 dB Default: 0 dB Breakpoint 28-36 (2.5.11.4.)  Values Range: –50 to 50 dB Default: 0 dB Breakpoint 37-40 (2.5.11.5.)  Values Range: –50 to 50 dB Default: 0 dB AIFB1 (2.6.)   Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated.  Static Revision No. (2.6.1.) The revision level of the static data associated with Analog Input Function Block 1. The Static Revision No. is updated whenever a configuration parameter is changed. Actual mode (2.6.2.) Used to request an operating mode from the Analog Input Function Block.  Options  *  Auto Mode (AUTO)  Manual Mode (MAN)  Out of Service (O/S)
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 133 Allows you to put the SITRANS LR250 into Out of Service Mode and then reset it to Auto Mode. Manual Mode is used in conjunction with Simulation. See Simulation (Page 93). It should be used only with SIMATIC PDM in order to benefit from all the features available. Channel (2.6.3.) Used to select between the different Level Transducer Block outputs.  Options    Level/Volume, Level, Distance *  Level/Volume Label (2.6.4.) User defined label. Input Scaling (2.6.5.)
Parameter reference    SITRANS LR250 (PROFIBUS PA) 134 Operating Instructions, 08/2014, A5E32221386-AC Upper Value (2.6.5.1.) Defines the operational upper range value of the input value (Process Value Scale) in PV (volume/level) Units. Process Value Scale normalizes the input value to a customer-defined range.  Values Range: -999999 to 999999 Default: 100%        Provides Output values (Out) to AIFB1 or AIFB2 Lower Value (2.6.5.2.) Defines the operational lower range value of the input value (Process Value Scale) in PV (volume/level) Units. Process Value Scale normalizes the input value to a customer-defined range.  Values Range: -999999 to 999999 Default: 0% Output Scaling (2.6.6.) Scales the Process Variable. The function block parameter OUT SCALE contains the values of the lower limit and upper limit effective range in AIFB1 units. Upper Value (2.6.6.1.) Defines the operational upper range value of the output value in AIFB1 units.  Values Range: -999999 to 999999 Default: 100%
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 135 Lower Value (2.6.6.2.) Defines the operational lower range value of the output value in AIFB1 units.  Values Range: -999999 to 999999 Default: 0% Alarms and Warnings (2.6.7.)  Upper Limit Alarm (2.6.7.1.) The setting for the upper alarm limit in AIFB1 units.  Values Range: -999999 to 999999 Default: 999999 Upper Limit Warning (2.6.7.2.) The setting for the upper warning limit in AIFB1 units.  Values Range: -999999 to 999999 Default: 999999 Lower Limit Warning (2.6.7.3.) The setting for the lower warning limit in AIFB1 units.  Values Range: -999999 to 999999 Default: -999999 Lower Limit Alarm (2.6.7.4.) The setting for the lower alarm limit in AIFB1 units.  Values Range: -999999 to 999999 Default: -999999
Parameter reference    SITRANS LR250 (PROFIBUS PA) 136 Operating Instructions, 08/2014, A5E32221386-AC Limit Hysteresis (2.6.7.5.) Hysteresis is used to adjust the sensitivity of the trigger for alarm messages. It is used to compensate when a process variable fluctuates around the same value as a limit. A high level alarm occurs when a value exceeds an upper limit. The alarm’s status remains true until the value drops below the limit minus the alarm hysteresis. The directions are reversed for low limit detection.  Values Range: -999999 to 999999 Default: 0.50 Enter a value for the hysteresis here, to be used for all warnings and alarms. The units are the same as the Output scale, i.e. AIFB1 units. Display (2.6.8.)  Filter Time Constant (2.6.8.1.) The time constant for the damping filter. The damping filter smooths out the response to a sudden change in level. This is an exponential filter and the engineering unit is always in seconds. See Damping (Page 249) for more detail.  Values Range: 0 to 600 s Default: 10 s Unit (2.6.8.2.)   Note Additional units are available in SIMATIC PDM.  Engineering unit to be displayed with the output value.  Values    m, cm, mm, ft, in, cu m, L, HL, cu in, cu ft, cu yd, gal, imp gal, bushels, Bbl, Bbl liquid, percent, PA, Follow out unit *  percent Out Unit Text (2.6.8.3.) If the desired unit is not listed in Unit (2.6.8.2.) you can define it in Out Unit Text (2.6.8.3.).
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 137 Decimal point (2.6.8.4.) The number of digits to display after the decimal point. (The LCD is limited to displaying two decimal places in Measurement mode. In SIMATIC PDM up to seven decimal places may be used to display measured values.)  Options Range: 0, 1, 2, 3, 4, 5, 6, 7 Default: 2 Fail-safe Mode (2.6.9.)  Mode (2.6.9.1.) Fail-safe Mode occurs if the status of the input value is bad, or if the device has been put into Fail-safe mode using Simulation. Mode defines the material level to be reported when the LOE (Loss of Echo) timer expires.  Options   SUB VALUE Substitute value. Value (2.6.9.2.) used as output value. * LAST VALUE Last value. (Store last valid output value).  USE BAD VALUE Use bad value. (Calculated output value is incorrect). Value (2.6.9.2.)   Note Fail-safe Mode (2.6.9.) must be set to Substitute Value before Value (2.6.9.2.) can be defined.  User-defined default for the Output Value, if sensor or sensor electronic fault is detected. Units are defined in Unit (2.6.8.2.).  Values Range: -999999 to 999999 Default: 0 AIFB2 (2.7.) See AIFB1 (2.6.): the parameters for AIFB2 are identical.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 138 Operating Instructions, 08/2014, A5E32221386-AC Measured Values (2.8.) Read only. Allows you to view measured values for diagnostic purposes. In SIMATIC PDM, open the menu View – Process Variables. Main Output (PV - Primary Value) (2.8.1.) The value for level, or volume (if volume conversion is selected). Output, no linearization (SV1 - Secondary Value 1) (2.8.2.) The value for level. Output, no level offset (SV2 - Secondary Value 2) (2.8.3.) The value for distance. Diagnostics (3.)
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 139 Echo Profile (3.1.) To request a profile via SIMATIC PDM: Open the menu Device – Echo Profile Utilities. [See Echo Profile Utilities via SIMATIC PDM (Page 84) for more detail.] To request a profile via the handheld programmer:                     ① Echo confidence value ⑥ Measure icon, deselected ② Algorithm selection (tFirst echo) ⑦ Exit icon, selected ③ Distance value ⑧ Measure icon, selected ④ TVT curve ⑨ Exit icon, deselected ⑤ Material level     1. Navigate to Level Meter > Diagnostics (3.) > Echo Profile (3.1.). 2. Press RIGHT arrow   to request a profile. [See Requesting an Echo Profile (Page 66) for more details.]
Parameter reference    SITRANS LR250 (PROFIBUS PA) 140 Operating Instructions, 08/2014, A5E32221386-AC Fault Reset (3.2.) Clears the following faults:  Fault code Description S3 Device Lifetime Reminder 1 (Maintenance Required) S4 Device Lifetime Reminder 2 (Maintenance Demanded) S6 Sensor Lifetime Reminder 1 (Maintenance Required) S7 Sensor Lifetime Reminder 2 (Maintenance Demanded) S8 Device Service Reminder 1 (Maintenance Required) S9 Device Service Reminder 2 (Maintenance Demanded) S12 Internal Temperature High S17 Calibration Schedule Reminder 1 (Maintenance Required) S18 Calibration Schedule Reminder 2 (Maintenance Demanded) To clear a fault using the handheld programmer: ● Enter the fault code number then press RIGHT arrow. To clear a fault via SIMATIC PDM: 1. Open the menu Device – Acknowledge Faults. 2. Select the fault to be cleared from the pull-down menu in Extended Diagnostics. 3. Click on Transfer to clear the fault. Electronics Temperature (3.3.)  Minimum Value (3.3.1.) The minimum recorded internal electronics temperature of the SITRANS LR250. Maximum Value (3.3.2.) The maximum recorded internal electronics temperature of the SITRANS LR250.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 141 Condensed Status (3.4.) When Enable (3.4.1.) is enabled, you can select the level of severity of errors, and tailor a device response appropriate for your particular process. ● In Event Index (3.5.1.) you can select a particular event or error by means of its index number. ● In Event Status (3.5.2.) you can assign a status to the selected event. ● In Event Diagnosis (3.5.3.) you can assign a diagnosis to the selected event. Enable (3.4.1.)   Note When cyclic communication is in progress, Condensed Status Mode cannot be changed.    Options    NO (disabled) *  YES (enabled) Select Yes or No to enable/disable Condensed Mode. Features supported (3.4.2.) Read only. Features supported are: ● Condensed Diagnostics ● Extended Diagnostics ● Application Relationships Features enabled (view only) (3.4.3.) Read only. Lists those features that have been enabled. Allocation (3.5.)
Parameter reference    SITRANS LR250 (PROFIBUS PA) 142 Operating Instructions, 08/2014, A5E32221386-AC Event Index (3.5.1.) The numeric component of the Event Code for a Condensed Status event. Use the index number to identify a particular event in the list below.  Event index Event code Event descriptiona) 0 S0 Loss of Echo 2 S2 No Tech Power 10 S10 Level Transducer Block (LTB) Scale 11 S11 Internal Temperature Sensor 12 S12 Internal Temperature High 14 S14 AIFB1 PV Range 15 S15 AIFB2 PV Range 28 S28 Memory RAM 29 S29 Memory EEPROM 30 S30 Memory EEPROM Flags 31 S31 Memory Flash 33 S33 Internal Temperature Calibration 34 S34 Velocity Calibration 35 S35 Receiver Init Calibration 36 S36 Receiver Calibration 37 S37 Technology Module Calibration 38 S38 Technology Module Ramp a) See General Fault Codes (Page 181) for the meaning of each event. For example:   Event Code for Loss of Echo  =  S0 Event Index  =  0 To select a particular event via the handheld programmer: 1. Go to Enable (3.4.1.) and select Yes to enable Condensed Mode. 2. Go to Event Index (3.5.1.) and enter the event index number corresponding to the event. To select a particular event via SIMATIC PDM: 1. Go to Diagnostics > Condensed Status Setup > Condensed Status Mode and select Yes to enable Condensed Mode. 2. Go to Diagnostics > Condensed Status. 3. For each event, you can select either the Status or the Diagnosis line, then choose a Status or Diagnosis option from the associated pull-down menu.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 143 Event Status (3.5.2.) Event Status allows you to assign one of the status options listed below, to any of the events listed in Event Index (3.5.1.). This allows you to tailor a device response appropriate for your particular process. (Event status affects Condensed status). See Condensed Status (Page 281) for more details.  Event Status options  Good  Good: maintenance required  Good: maintenance demanded  Uncertain: maintenance demanded *  Bad: maintenance alarm  Uncertain: process related, no maintenance  Bad: process related, no maintenance  Bad: function check/local override  Good: function check To assign a status to a particular event via the handheld programmer: 1. Go to Enable (3.4.1.) and select Yes to enable Condensed Mode. 2. Go to Event Index (3.5.1.) and enter the event index number corresponding to a particular event. 3. Go to Event Status (3.5.2.) and choose a Status option from the table above. To assign a status to a particular event via SIMATIC PDM: 1. Go to Level Meter > Diagnostics > Condensed Status Setup, select Yes to enable Condensed Status Mode. 2. Go to Level Meter > Diagnostics > Condensed Status. 3. Select the Status line for the selected Event, then choose a Status option from the associated pull-down menu.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 144 Operating Instructions, 08/2014, A5E32221386-AC Event Diagnosis (3.5.3.) Allows you to assign one of the diagnostic options listed below to any of the events listed in Event Index (3.5.1.). This allows you to tailor a device response appropriate for your particular process.(Event Diagnosis affects Condensed Acyclic Diagnostics and Cyclic Extended Diagnostics). See Condensed Mode Diagnosis (Page 285) for more detail.    Event Diagnosis Options  Status OK  Maintenance Required  Maintenance Demanded *  Maintenance alarm  Invalid process conditions  Function check or simulation To assign a diagnosis to a particular event via the handheld programmer: 1. Go to Enable (3.4.1.) and select Yes to enable Condensed Mode. 2. Go to Event Index (3.5.1.) and enter the event index number corresponding to a particular event. 3. Go to Event Diagnosis (3.5.3.) and choose a Diagnosis option from the table above. To assign a status to a particular event via SIMATIC PDM: 1. Go to Level Meter > Diagnostics > Condensed Status Setup, and select Yes to enable Condensed Status Mode. 2. Go to Level Meter > Diagnostics > Condensed Status. 3. Select the Diagnosis line for the selected Event, then choose a Diagnosis option from the associated pull-down menu. Peak Values (3.6.) To view via SIMATIC PDM: Open the menu View – Device Diagnostics, select Device Status, and click on the tab Device Status. For more details see Device Diagnostics (Page 101). Min. Measured Value (3.6.1.) The minimum recorded Sensor value, reported in units defined in Unit (2.3.1.). Max. Measured Value (3.6.2.) The maximum recorded Sensor value, reported in units defined in Unit (2.3.1.).
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 145 Minimum Output Value - AIFB1 (3.6.3.) The minimum recorded Output Value from the Analog Input Function Block 1. Maximum Output Value - AIFB1 (3.6.4.) The maximum recorded Output Value from the Analog Input Function Block 1. Minimum Output Value - AIFB2 (3.6.5.) The minimum recorded Output Value from the Analog Input Function Block 2. Maximum Output Value - AIFB2 (3.6.6.) The maximum recorded Output Value from the Analog Input Function Block 2. Service (4.)   Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 146 Operating Instructions, 08/2014, A5E32221386-AC Master Reset (4.1.)   Note Following a Factory Reset, some degree of reprogramming may be required, depending on the option chosen below.    Reset options Result Factory Defaults Resets all user parameters to the manufacturer’s default settings, with certain exceptions. The list of exceptions includes, but is not limited to: • Tag • Message • Descriptor • Installation Data • Device Address • Write Protection • Auto False Echo Suppression Range • learned TVT Standard Defaults Resets all resettable parameters excluding device addresses to the PROFIBUS standard default settings. Informational Resets Tag parameter. Functional Resets parameters that control device behavior and functionality (such as calibration points) Warm Start Has the same effect as recycling power to the device Reset Address to 126 Resets the PROFIBUS device address to 126  If the address lock was on, will disable the lock. To access via SIMATIC PDM: Open the menu Device – Master Reset. For more detail see Master Reset (Page 97).  To perform a reset via the handheld programmer: 1. Press RIGHT Arrow to open Edit Mode then scroll down to the desired Reset option and press RIGHT Arrow to select it. 2. Press LEFT Arrow to exit.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 147 Remaining Device Lifetime (4.2.)   Note • Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. • Four sets of parameters allow you to monitor the Device/Sensor Lifetimes and set up Service/Calibration schedules, based on operating hours instead of a calendar-based schedule. See also Remaining Sensor Lifetime (4.3.), Service Schedule (4.4.), and Calibration Schedule (4.5.). • Performing a reset to Factory Defaults will reset all the Maintenance Schedule parameters to their factory defaults. • The device operates in years. To view Remaining Device Lifetime parameters in hours or days (via SIMATIC PDM only) see Lifetime Expected (4.2.1.).  The device tracks itself based on operating hours and monitors its predicted lifetime. You can modify the expected device lifetime, set up schedules for maintenance reminders, and acknowledge them. The maintenance warnings and alarms are communicated via the Status byte. This information can be integrated into an Asset Management system. For optimal use, we recommend that you use SIMATIC PCS7 Asset Management Software in conjunction with SIMATIC PDM.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 148 Operating Instructions, 08/2014, A5E32221386-AC To access these parameters via SIMATIC PDM:  ● Open the menu Device – Maintenance and select the Remaining Device Lifetime tab. ● After modifying values/units as required, click on Write to accept the change, and Read to view the effect of the change. ● Click on Snooze to add a year to the Total Expected Device Life. Time Units  Options a) Hours; days; years Default: years  a) Selectable only via SIMATIC PDM.  Lifetime Expected (4.2.1.)   Note Note: The device always operates in years. Changing the units affects only the parameter view of the Remaining Device Lifetime parameters in SIMATIC PDM.  Allows you to override the factory default.  Values Units a): hours, days, years  Range: 0 to 20 years  Default: 10.00 years  a) Units are selectable only via SIMATIC PDM. Time in Operation (4.2.2.) Read only. The amount of time the device has been operating. Remaining Lifetime (4.2.3.) Read only. Lifetime Expected (4.2.1.) less Time in Operation (4.2.2.). Reminder Activation (4.2.4.)   Note To modify this parameter via SIMATIC PDM it must be accessed via the pull-down menu Device – Maintenance.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 149 Allows you to enable a maintenance reminder.   Values    Reminder 1 (Maintenance Required)  Reminder 2 (Maintenance Demanded)  Reminders 1 and 2 *  OFF 1. First set the values in Reminder 1 (Required) (4.2.5.)/Reminder 2 (Demanded) (4.2.6.). 2. Select the desired Reminder Activation option. Reminder 1 (Required) (4.2.5.) If Remaining Lifetime (4.2.3.) is equal to or less than this value, the device generates a Maintenance Required reminder.  Values Range: 0 to 20 years Default: 0.164 years 1. Modify values as required. 2. Set Reminder Activation (4.2.4.) to the desired option. Reminder 2 (Demanded) (4.2.6.) If Remaining Lifetime (4.2.3.) is equal to or less than this value, the device generates a Maintenance Demanded reminder.  Values Range: 0 to 20 years Default: 0.019 years 1. Modify limit values as required. 2. Set Reminder Activation (4.2.4.) to the desired option.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 150 Operating Instructions, 08/2014, A5E32221386-AC Maintenance Status (4.2.7.) Indicates which level of maintenance reminder is active. In SIMATIC PDM, open the menu View – Device Diagnostics, select Device Status, click on the Maintenance tab, and check the Device Lifetime Status window. Acknowledge Status (4.2.8.) Indicates which level of maintenance reminder has been acknowledged.  In SIMATIC PDM, open the menu View – Device Diagnostics, select Device Status, click on the Maintenance tab, and check the Device Lifetime Status window. Acknowledge (4.2.9.) Acknowledges the current maintenance reminder. To acknowledge a reminder via SIMATIC PDM: 1. Open the menu View – Device Diagnostics, select Device Status and click on the Maintenance tab. 2. In the Device Lifetime section, click on Acknowledge Warnings. To acknowledge a reminder via the handheld programmer: 1. Press RIGHT arrow  twice to open parameter view and activate Edit Mode. 2. Press RIGHT arrow   to acknowledge the reminder.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 151 Remaining Sensor Lifetime (4.3.)   Note • Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. • Four sets of parameters allow you to monitor the Device/Sensor Lifetimes and set up Maintenance/Service schedules, based on operating hours instead of a calendar-based schedule. See also Remaining Device Lifetime (4.2.), Service Schedule (4.4.), and Calibration Schedule (4.5.). • Performing a reset to Factory Defaults will reset all the Maintenance Schedule parameters to their factory defaults. • The device operates in years. To view Remaining Sensor Lifetime parameters in hours or days (via SIMATIC PDM only) see Lifetime Expected (4.3.1.).
Parameter reference    SITRANS LR250 (PROFIBUS PA) 152 Operating Instructions, 08/2014, A5E32221386-AC The device monitors the predicted lifetime of the sensor (the components exposed to the vessel environment). You can modify the expected sensor lifetime, set up schedules for maintenance reminders, and acknowledge them.  To access these parameters via SIMATIC PDM: ● Open the menu Device – Maintenance and select the Remaining Sensor Lifetime tab. ● After modifying values/units as required, click on Write to accept the change, and Read to view the effect of the change. ● Click on Snooze to add a year to the Total Expected Sensor Life. ● Click on Sensor Replaced to restart the timer and clear any fault messages. Time Units  Options a) Hours; days; years Default: years  a)  Selectable only via SIMATIC PDM.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 153 Lifetime Expected (4.3.1.)   Note The device always operates in years. Changing the units affects only the parameter view of Remaining Sensor Life parameters in SIMATIC PDM.  Allows you to override the factory default.  Values   Units a): hours, days, years Range: 0 to 20 years Default: 10.00 years  a)  Units are selectable only via SIMATIC PDM. Time in Operation (4.3.2.) The amount of time the sensor has been operating. Can be reset to zero after performing a service or replacing the sensor. To reset to zero: ● In SIMATIC PDM, open the menu Device – Maintenance, click on the Remaining Sensor Lifetime tab, and click on Sensor Replaced to restart the timer and clear any fault messages. ● Via the handheld programmer, manually reset Time in Operation (4.3.2.) to zero. Remaining Lifetime (4.3.3.)  Read only. Lifetime Expected (4.3.1.) less Time in Operation (4.3.2.).
Parameter reference    SITRANS LR250 (PROFIBUS PA) 154 Operating Instructions, 08/2014, A5E32221386-AC Reminder Activation (4.3.4.)   Note To modify this parameter via SIMATIC PDM it must be accessed via the pull-down menu Device – Maintenance.  Allows you to enable a maintenance reminder.   Options     Reminder 1 (Maintenance Required)  Reminder 2 (Maintenance Demanded)  Reminders 1 and 2 *  OFF 1. First set the values in Reminder 1 (Required) (4.3.5.)/Reminder 2 (Demanded) (4.3.6.). 2. Select the desired Reminder Activation option. Reminder 1 (Required) (4.3.5.) If Remaining Lifetime (4.3.3.) is equal to or less than this value, the device generates a Maintenance Required reminder.  Values Range: 0 to 20 years Default: 0.164 years 1. Modify values as required. 2. Set Activation Reminder (4.3.4.) to the desired option. Reminder 2 (Demanded) (4.3.6.) If Remaining Lifetime (4.3.3.) is equal to or less than this value, the device generates a Maintenance Demanded reminder.   Values Range: 0 to 20 years Default: 0.019 years 1. Modify values as required. 2. Set Reminder Activation (4.3.4.) to the desired option.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 155 Maintenance Status (4.3.7.) Indicates which level of maintenance reminder is active.  In SIMATIC PDM, open the menu View – Device Diagnostics, select Device Status, click on the Maintenance tab, and check the Sensor Lifetime Status window. Acknowledge Status (4.3.8.) Indicates which level of maintenance reminder has been acknowledged. In SIMATIC PDM, open the menu View – Device Diagnostics, select Device Status, click on the Maintenance tab, and check the Sensor Lifetime Status window. Acknowledge (4.3.9.) Acknowledges the current maintenance reminder. To acknowledge a reminder via SIMATIC PDM: 1. Open the menu View – Device Diagnostics, select Device Status and click on the Maintenance tab. 2. In the Sensor Lifetime section, click on Acknowledge Warnings. To acknowledge a reminder via the handheld programmer: 1. Press RIGHT arrow  twice to open parameter view and activate Edit Mode. 2. Press RIGHT arrow  to acknowledge the reminder. Service Schedule (4.4.)   Note • Four sets of parameters allow you to monitor the Device/Sensor Lifetimes and set up Service/Calibration schedules, based on operating hours instead of a calendar-based schedule. See also Remaining Device Lifetime (4.2.), Remaining Sensor Lifetime (4.3.), and Calibration Schedule (4.5.). • Performing a reset to Factory Defaults will reset all the Maintenance Schedule parameters to their factory defaults. • The device operates in years. To view Service Interval parameters in hours or days (via SIMATIC PDM only) see Service interval (4.4.1.).  The device tracks service intervals based on operating hours and monitors the predicted lifetime to the next service. You can modify the Total Service Interval, set schedules for maintenance reminders, and acknowledge them.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 156 Operating Instructions, 08/2014, A5E32221386-AC The maintenance warnings and alarms are communicated via the Status byte. This information can be integrated into any Asset Management system. For optimal use, we recommend that you use SIMATIC PCS7 Asset Management Software in conjunction with SIMATIC PDM. To access these parameters via SIMATIC PDM: ● Open the menu Device – Maintenance and select the Service Schedule tab. ● After modifying values/units as required, click on Write to accept the change, and Read to view the effect of the change. ● Click on Service Performed to restart the timer and clear any fault messages.  Time Units  Options a) Hours; days; years Default: years  a) Selectable only via SIMATIC PDM. Service Interval (4.4.1.)   Note The device always operates in years. Changing the units affects only the parameter view of the Service Interval parameters in SIMATIC PDM.  User-configurable recommended time between product inspections.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 157  Values Units a): hours, days, years Range: 0 to 20 years Default: 1.0 year  a) Units are selectable only via SIMATIC PDM. Time since Last Service (4.4.2.) Time elapsed since last service. Can be reset to zero after performing a service. To reset to zero: ● In SIMATIC PDM, open the menu Device – Maintenance, click on the Service Schedule tab, and click on Service Performed to restart the timer and clear any fault messages. ● Via the handheld programmer, manually reset Time since Last Service (4.4.2.) to zero. Time until Next Service (4.4.3.) Read only. Service Interval (4.4.1.) less Time since Last Service (4.4.2.).
Parameter reference    SITRANS LR250 (PROFIBUS PA) 158 Operating Instructions, 08/2014, A5E32221386-AC Reminder Activation (4.4.4.)   Note To modify this parameter via SIMATIC PDM it must be accessed via the pull-down menu Device – Maintenance.  Allows you to enable a maintenance reminder.   Options  *  Timer OFF  ON - no reminders checked  ON - Reminder 1 (Maintenance Required) checked  ON - Reminders 1 and 2 checked  ON - Reminder 2 (Maintenance Demanded) checked 1. First set the values in Reminder 1 (Required) (4.4.5.)/Reminder 2 (Demanded) (4.4.6.). 2. Select the desired Reminder Activation option. Reminder 1 (Required) (4.4.5.) If Time until Next Service (4.4.3.) is equal to or less than this value, the device generates a Maintenance Required reminder.  Values Range: 0 to 20 years Default: 0.164 years 1. Modify values as required. 2. Set Activation Reminder (4.4.4.) to the desired option. Reminder 2 (Demanded) (4.4.6.) If Time until Next Service (4.4.3.) is equal to or less than this value, the device generates a Maintenance Demanded reminder.  Values Range: 0 to 20 years Default: 0.019 years 1. Modify values as required 2. Set Reminder Activation (4.4.4.) to the desired option.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 159 Maintenance Status (4.4.7.) Indicates which level of maintenance reminder is active. Open the menu View – Device Diagnostics, select Device Status, click on the Maintenance tab and check the Service Schedule Status window. Acknowledge Status (4.4.8.) Indicates which level of maintenance reminder has been acknowledged. Open the menu View – Device Diagnostics, select Device Status, click on the Maintenance tab and check the Service Schedule Status window. Acknowledge (4.4.9.) Acknowledges the current maintenance reminder. To acknowledge a reminder via SIMATIC PDM:  1. Open the menu View – Device Diagnostics, select Device Status and click on the Maintenance tab. 2. In the Service Schedule Status section, click on Acknowledge Warnings. To acknowledge a reminder via the handheld programmer:  1. Press RIGHT   arrow twice to open parameter view and activate Edit Mode. 2. Press RIGHT   arrow to acknowledge the reminder.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 160 Operating Instructions, 08/2014, A5E32221386-AC Calibration Schedule (4.5.)   Note • Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated. • Four sets of parameters allow you to monitor the Device/Sensor Lifetimes and set up Service/Calibration schedules, based on operating hours instead of a calendar-based schedule. See also Remaining Device Lifetime (4.2.), Remaining Sensor Lifetime (4.3.), and Service Schedule (4.4.). • Performing a reset to Factory Defaults will reset all the Maintenance Schedule parameters to their factory defaults. • The device operates in years. To view Calibration Interval parameters in hours or days (via SIMATIC PDM only) see Calibration Interval (4.5.1.).  The device tracks calibration intervals based on operating hours and monitors the predicted lifetime to the next calibration. You can modify the Total Calibration Interval, set schedules for maintenance reminders, and acknowledge them. To access these parameters via SIMATIC PDM: ● Open the menu Device – Maintenance and select the Calibration Schedule tab. ● After modifying values/units as required, click on Write to accept the change, and Read to view the effect of the change. ● Click on Calibration Performed to restart the timer and clear any fault messages.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 161 Time Units  Options a) Hours; days; years Default: years  a) Selectable only via SIMATIC PDM. Calibration Interval (4.5.1.)   Note The device always operates in years. Changing the units affects only the parameter view of the Calibration Interval parameters in SIMATIC PDM.  User-configurable recommended time between product calibrations.  Values Units a): hours, days, years Range: 0 to 20 years Default: 1.0 year  a) Units are selectable only via SIMATIC PDM. Time since Last Calibration (4.5.2.) Time elapsed since last calibration. Can be reset to zero after performing a calibration. To reset to zero: ● In SIMATIC PDM, open the menu Device – Maintenance, click on the Calibration Schedule tab, and click on Calibration Performed to restart the timer and clear any fault messages. ● Via the handheld programmer, manually reset Time since Last Calibration (4.5.2.) to zero. Time until Next Calibration (4.5.3.) Read only. Calibration Interval (4.5.1.) less Time since Last Calibration (4.5.2.).
Parameter reference    SITRANS LR250 (PROFIBUS PA) 162 Operating Instructions, 08/2014, A5E32221386-AC Reminder Activation (4.5.4.)   Note To modify this parameter via SIMATIC PDM it must be accessed via the pull-down menu Device – Maintenance.  Allows you to enable a maintenance reminder.  Options  *  Timer OFF  ON - no reminders checked  ON - Reminder 1 (Maintenance Required) checked  ON - Reminders 1 and 2 checked     ON—Reminder 2 (Maintenance Demanded) checked 1. First set the values in Reminder 1 (Required) (4.5.5.)/Reminder 2 (Demanded) (4.5.6.). 2. Select the desired Reminder Activation option. Reminder 1 (Required) (4.5.5.) If Time until Next Calibration (4.5.3.) is equal to or less than this value, the device generates a Maintenance Required reminder.  Values Range: 0 to 20 years Default: 0.164 years 1. Modify values as required. 2. Set Reminder Activation (4.5.4.) to the desired option. Reminder 2 (Demanded) (4.5.6.) If Time until Next Calibration (4.5.3.) is equal to or less than this value, the device generates a Maintenance Demanded reminder.  Values Range: 0 to 20 years Default: 0.019 years 1. Modify values as required. 2. Set Reminder Activation (4.5.4.) to the desired option.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 163 Maintenance Status (4.5.7.) Indicates which level of maintenance reminder is active. In SIMATIC PDM, open the menu View – Device Diagnostics, select Device Status, click on the Maintenance tab and check the Calibration Schedule Status window. Acknowledge Status (4.5.8.) Indicates which level of maintenance reminder has been acknowledged. In SIMATIC PDM, open the menu View – Device Diagnostics, select Device Status, click on the Maintenance tab and check the Calibration Schedule Status window. Acknowledge (4.5.9.) Acknowledges the current maintenance reminder.  To acknowledge a reminder via SIMATIC PDM:  1. Open the menu View – Device Diagnostics, select Device Status and click on the Maintenance tab. 2. In the Calibration Schedule Status section click on Acknowledge Warnings. To acknowledge a reminder via the handheld programmer:  1. Press RIGHT   arrow twice to open parameter view and activate Edit Mode. 2. Press RIGHT   arrow to acknowledge the reminder. Manufacture Date (4.6.) Read only. The date of manufacture of the SITRANS LR250 (yy mm dd).  Powered Hours (4.7.) Read only. Displays the number of hours the unit has been powered up since manufacture.  In SIMATIC PDM, open the menu Device – Wear. Power-on Resets (4.8.) Read only. The number of power cycles that have occurred since manufacture.  In SIMATIC PDM, open the menu Device – Wear.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 164 Operating Instructions, 08/2014, A5E32221386-AC LCD Fast Mode (4.9.)   Note • LCD Fast Mode takes effect only after 30 minutes of inactivity. (Each time the device is powered up, a further 30 minutes of inactivity is required.) • LCD Fast Mode affects Measurement mode only; it has no effect on Navigation mode.  Enables a faster rate of measurement from the device by disabling most of the display area. Only the bar graph will be refreshed when LCD Fast Mode is set to ON.  Values   ON  * OFF LCD Contrast (4.10.) The factory setting is for optimum visibility at room temperature and in average light conditions. Extremes of temperature will lessen the contrast.   Values Range: 0 (High contrast) to 20 (Low contrast). Default: 10 Adjust the value to improve visibility at different temperatures and in light conditions. Change the value in small steps to ensure you can continue to read the display.  Communication (5.)   Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 165 Device Address (5.1.)   Note The address can be changed and locked from a remote master. See PROFIBUS address (Page 276) for details on disabling the address lock and Master Reset (4.1.) to reset Device Address to 126.  Sets the unique address of the device on the network (also called PROFIBUS address).  Values 0 - 126. Default: 126 To set Device Address via SIMATIC PDM:  ● Open the project in Process Device Network View then right-click on the device. ● Go to Object Properties > Connection to access the field Short Address. To change Device Address via the handheld programmer: See Device Address for details. PROFIBUS Ident Number (5.2.) Identifies the device on the network. The Ident Number must match that in the GSD file (the GSD file provides information on the device to the master).  Options   STD PROFILE Standard Profile (uses generic GSD for 2 AIFB) [ident # = 0x9701] * MANUFACTURER Manufacturer-specific (uses Siemens EDD and GSD file, which identifies the LR250 PROFIBUS PA [ident # = 0x8150]  STD – AIFB 1 ONL. Standard Profile AIFB 1 only (uses generic GSD for 1 AIFB) [ident # = 0x9700] Security (6.)   Note Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly stated.
Parameter reference    SITRANS LR250 (PROFIBUS PA) 166 Operating Instructions, 08/2014, A5E32221386-AC Remote Access (6.1.)  Remote Lockout (6.1.1.)   Note If access control is changed to limit remote access, it can be reset only via the handheld programmer.  Enables or disables programming via the network and PDM.  Options  *  OFF (Remote operation enabled)  ON (Remote operation disabled) Local Access (6.2.)  Write Protection (6.2.1.)   Note Do not lose this number value.  Prevents any changes to parameters via PDM or the hand-held programmer.  Hand-held programmer values Range: 0 to 99999. Default: Off  2457 (unlock value) Off (enables programming) any other value On (disables programming) Local Operation (6.2.2.) Enables or disables programming via the hand-held programmer.  Options  *  ENABLED   DISABLED In SIMATIC PDM, open the menu Device – Write Locking, select On or Off, and click on Transfer.
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 167 Language (7.) Selects the language to be used on the LCD.   Options  *  English  Deutsch  Français  Español  8.1 Alphabetical parameter list   Note For a detailed list of parameters see Parameter Reference (Page 107).   Actual Mode (2.6.2.)  AIFB1 (2.6.) AIFB2 (2.7.) Alarms and Warnings (2.6.7.) Algorithm (2.5.7.1.) Allocation (3.5.)  Auto False Echo Suppression (2.5.10.1.)  Auto False Echo Suppression Range (2.5.10.2.) Calibration (2.3.7.)  Calibration Schedule (4.5.) Channel (2.6.3.)  CLEF Range (2.5.7.4.)  Condensed Status (3.4.)  Confidence (2.5.9.1.) Descriptor (2.1.2.)  Device Address (5.1.)  Dimension A (2.4.1.3.)  Dimension L (2.4.1.4.)
Parameter reference    SITRANS LR250 (PROFIBUS PA) 168 Operating Instructions, 08/2014, A5E32221386-AC Display (2.6.8.)  Echo Lock (2.5.8.1.)  Echo Profile (3.1.)  Echo Quality (2.5.9.)  Echo Select (2.5.7.)  Echo Strength (2.5.9.2.)  Electronics Temperature (3.3.)  Empty rate (2.3.8.3.)  Event Index (3.5.1.)  Event Status (3.5.2.)  Event Diagnosis (3.5.3.)  Fail-safe Mode (2.6.9.) Far Range (2.5.2.)  Fault Reset (3.2.)  Fill Rate (2.3.8.2.)  Filter Time Constant (2.6.8.1.) Firmware Revision (2.2.2.) Hardware Revision (2.2.1.)  High Calibration Pt. (2.3.7.2.)  High Level Point (2.3.7.5.) Hover Level (2.5.10.3.) Identification (2.1.)  Input Scaling (2.6.5.) Label (2.6.4.)  Language (7.) LCD Contrast (4.10.) LCD Fast Mode (4.9.) Level Offset (2.3.7.6.)  Level Unit (2.3.2.)  Limit Hysteresis (2.6.7.5.)  Linearization (2.4.)  Loader Revision (2.2.3.)  Local Access (6.2.)
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 169 Local Operation (6.2.2.)  LOE Timer (2.3.6.)  Low Calibration Pt. (2.3.7.1.)  Lower Limit Warning (2.6.7.3.)  Lower Limit Alarm (2.6.7.4.)  Low Level Point (2.3.7.4.)  Main Output (PV– Primary Value) (2.8.1.)  Material (2.3.5.)  Master Reset (4.1.)  Max. Measured Value (3.6.2.)  Maximum Output Value - AIFB1 (3.6.4.)  Maximum Output Value - AIFB2 (3.6.6.)  Maximum Sensor Value (2.5.5.)  Maximum Value (3.3.2.)  Maximum Volume (2.4.1.2.)  Measured Values (2.8.)  Message (2.1.3.)  Min. Measured Value (3.6.1.)  Minimum Output Value - AIFB1 (3.6.3.)  Minimum Output Value - AIFB2 (3.6.5.)  Minimum Sensor Value (2.5.4.)  Minimum Value (3.3.1.)  Mode (2.6.9.1.)  Near Range (2.5.1.)  Order Option (2.2.4.)  Output, no level offset (SV2 – Secondary Value 2) (2.8.3.)  Output, no linearization (SV1 – Secondary Value 1) (2.8.2.)  Output Scaling (2.6.6.)  Peak Values (3.6.)  Position Detect (2.5.7.2.)  Powered Hours (4.7.)  Power-on Resets (4.8.)
Parameter reference    SITRANS LR250 (PROFIBUS PA) 170 Operating Instructions, 08/2014, A5E32221386-AC PROFIBUS Ident Number (5.2.)  Propagation Factor (2.5.3.)  PV Units (volume/level) (2.3.3.)  Quick Start (1.)  Rate (2.3.8.)  Remaining Device Lifetime (4.2.)  Remaining Sensor Lifetime (4.3.)  Remote Access (6.1.)  Remote Lockout (6.1.1.)  Response Rate (2.3.8.1.)  Sampling (2.5.8.)  Sampling down (2.5.8.3.)  Sampling up (2.5.8.2.)  Sensor (2.3.)  Sensor Offset (2.3.7.3.)  Service Schedule (4.4.)  Shaper Mode (2.5.10.4.)  Shots (2.5.6.) Signal Processing (2.5.)  Static Revision No. (2.6.1.) Tag (2.1.1.)  Temperature Units (2.3.4.)  TVT setup (2.5.10.)  TVT shaper (2.5.11.)  Upper Limit Warning (2.6.7.2.)  Upper Limit Alarm (2.6.7.1.) Unit (2.3.1.)  Value (2.6.9.2.)  Vessel Shape (2.4.1.1.)  Volume (2.4.1.)  Write Protection (6.2.1.)  XY index (2.4.1.5.)  X value (2.4.1.6.)
 Parameter reference    SITRANS LR250 (PROFIBUS PA) Operating Instructions, 08/2014, A5E32221386-AC 171 Y value (2.4.1.7.)
Parameter reference    SITRANS LR250 (PROFIBUS PA) 172 Operating Instructions, 08/2014, A5E32221386-AC