Siemens RF310R Tag Reader User Manual SIMATIC Sensors RFID systems SIMATIC RF300
Siemens AG Tag Reader SIMATIC Sensors RFID systems SIMATIC RF300
Siemens >
Contents
- 1. User Manual I
- 2. User Manual II
- 3. User Manual III
- 4. User Manual IV
User Manual IV
Communication modules 7.7 RF170C After start-up or updating the firmware, the LEDs SF, PRE, ERR and ACT indicate the operating status or faults of the RF170C: SF PRE_1 ERR_1 ACT_1 PRE_2 ERR_2 ACT_2 Off Off Off On On Off On Off On Off Off On On On On Off On On On Description Off Off Off Start-up active Off Off Off Checksum error at start-up * Off Off On Off Firmware invalid * On On On On LED test for approximately 4 seconds; otherwise firmware fault * On On Off On On Checksum error at start-up * On On Off On On Checksum error of the firmware * Off On On On On On External RAM defective * On On Off On On On On ESSA3 defective * On Off On On On Off On ID error firmware * â Off 1 x flash every 3 s Off Off 1 x flash every 3 s Off RF170C successfully started up, waiting for reset command â â n x flash every 3 s â â m x flash every 3 s â The number of flashes (n, m) indicates the last reported error on a given channel. â â Flashing Rapid flashing â Flashing Rapid flashing Firmware update; alternate flashing of the error LEDs at approximately 1 Hz â = not relevant * If this fault recurs, the module is defective and must be replaced. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 221 Communication modules 7.7 RF170C 7.7.4 Technical specifications Table 7-22 Technical specifications for RF170C Normal addressing Filehandler Serial interface to the user PROFIBUS DP-V1/PROFINET IO Interface to the ET 200pro ET 200pro backplane bus Connection method See ET 200pro operating instructions Transmission rate See ET 200pro operating instructions Max. block length 2 words cyclic/240 bytes acyclic (per channel) Serial interface to the reader/ write/read device Connector Max. cable length 2 x M12 coupler plug 1000 m, dependent on reader / write/read device (2 m = standard length; for other standard cables and selfassembled cables, refer to Section Connecting cables) Connectable readers / write/read devices 2x reader / write/read devices Software functions Programming Depending on the PROFIBUS DP master Depending on the PROFIBUS DP master SIMATIC S7 function blocks FB 45 / FC 45 (normal addressing without multitag) FB 56 / FC 56 (filehandler, with and without multitag) FC 55 (normal addressing with multitag) MDS addressing Direct access via addresses Access via DOS-like file system Commands Initialize MDS, read data from MDS, write data to MDS, etc. Format MDS, read file, write file, etc Yes/Yes 16KB No/No â MOBY I dialog: Normal station/VMDS Memory size VMDS Power supply 1 ⢠Rated value ⢠Permissible range Current consumption 2 Current taken from reader outputs Galvanic isolation 24 V DC 20 V to 30 V DC Max. 1 A; typ. 130 mA (without reader / write/read device) max. 800 mA (for one or 2 readers / write/read devices) Yes Ambient temperature ⢠During operation â25 to +55°C ⢠During transport and storage â40 to +70°C Dimensions (W x H x D) in mm ⢠222 RF170C (electronic and bus module) 90 x 130 x 35 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.7 RF170C Normal addressing ⢠RF170C with connection module Filehandler 90 x 130 x 60 Weight ⢠RF170C communication module Approx. 270 g ⢠RF170C connection module Approx. 500 g Degree of protection MTBF (at 40°C) Approvals IP67 129 years cULus (file E116536) 1) All supply and signal voltages must be low level protective voltage (SELV/PELV acc. to EN 60950) 24 V DC supply: Safety (electrical) isolation of low voltage (SELV / PELV acc. to EN 60950) 2) The current supply must provide the current required (max. 1 A) for intermittent periods of failed voltage ⤠20 ms. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 223 Communication modules 7.7 RF170C 7.7.5 Dimensional drawings RF170C with connection module The dimension drawing for an RF170C communication module with plugged-in connection module is shown below. 1RWHEHQGLQJ UDGLXV SF Figure 7-43 224 5HDGHU FRQQHFWLRQ Dimension drawing for RF170C communication module with connection module on mounting rack, narrow SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.7 RF170C 7.7.6 Ordering data Communication module and connection module Table 7-23 Communication module and connection module order numbers Name Order number RF170C communication module, 1 unit 6GT2002-0HD00 RF170C connection module, 1 unit 6GT2002-1HD00 RF170C connection module accessories Table 7-24 Order numbers for RF170C connection module accessories Name Write/read device cable MOBY I / E / U Order number 2.0 m 6GT2091-0FH20 5.0 m 6GT2091-0FH50 Write/read device cable MOBY D 2.0 m 6GT2691-0FH20 Reader cable RF300, extension cable RF300/MOBY I/E/U/D 2.0 m 6GT2891-0FH20 5.0 m 6GT2891-0FH50 10.0 m 6GT2891-0FN10 20.0 m 6GT2891-0FN20 50.0 m 6GT2891-0FN50 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 225 Communication modules 7.8 RF180C 7.8 RF180C 7.8.1 Description Area of application The RF180C communication module is a module that can be used on any controller for operating RFID components over PROFINET IO. RF180C communication module With M12 connection block (7/8") With push-pull connection block When operating the RF180C on a SIMATIC S7, a convenient function module is made available to the user (FB 45). When using it on other controllers, please follow the appropriate instructions for parameterization and integration in the system. The following RFID families can be operated with the RF180C: â RF300 â MOBY D â MOBY U â MOBY E â MOBY I 226 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C Features Up to two readers / SLGs can be operated on the RF180C at the same time. The user can issue a command to 2 readers / SLGs simultaneously (FB 45 when operating on a SIMATIC S7). The tag data are accessed by means of physical addressing of the tag. In SIMATIC S7, the FB 45 is available for this purpose. The FB 45 provides the S7 user with a simple-to-use interface with powerful commands (processing one complete tag with one command; command linking; S7 data structures via UDTs). Other features â Degree of protection IP67 â System integration with M12, 7/8" concept or with push-pull concept â Standardized PROFINET IO user interface for identification systems with RFID standard profile (with later firmware version) â Firmware update â Parameterizable device-specific diagnostics data â Support for I&M functionality (a mechanism for reading out information via the module and saving system information such as function, installation date, installation location, and comments). Layout The RF180C has the same enclosure as the RFID communication module ASM 456 for PROFIBUS. For connecting to PROFINET IO, the RF180C communication module features a connection block in one of the following designs: â M12 connection block design (7/8") â Push-pull connection block design, RJ45 The following figure shows the basic design of the RF180C. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 227 Communication modules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b,2 Figure 7-44 228 Basic design of the RF180C SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C Potential Ungrounded installation of the system is possible with the RF180C. The following circuit shows the internal relationships of the reference potentials. 99HUVRUJXQJ 5)&XQG5HDGHU 0 ,QWHUQH9HUVRUJXQJ 5HDGHU6FKQLWWVWHOOH 352),1(7,2 +LOIVVSDQQXQJIžU %XVDQVFKOXVV 0 0Ë 0Ë 6FKLUP Figure 7-45 Q) 0Ë Q) Q) Q) Galvanic isolation of RF180C Integration The following figure shows how the RF180C with M12 connection block (7/8") is integrated in an automation system. The push-pull connection block is integrated in the same manner as the M12 connection block (7/8"). 6WHXHUXQJ ]%6&38 5)& ; 352),1(7,2/HLWXQJ ; 9IžU5)&XQG5HDGHU6/* ]XZHLWHUHQ 352),1(7,27HLOQHKPHUQ 5HDGHU 5HDGHU 7UDQVSRQGHU Figure 7-46 RF180C configurator with M12 connection block (7/8") SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 229 Communication modules 7.8 RF180C The RF180C is integrated into the hardware configuration by means of a GSDML file. The RF180C can then be configured using HW-Config of the SIMATIC manager or another PROFINET tool. The GSDML file can be found on the RFID Systems Software & Documentation CD or on the Internet (see Section Service & Support). 7.8.2 Connection Proper use When connecting non-specified devices to the RF180C, it is possible that the connected device may be destroyed. PROFINET IO connection system Detailed information about connecting the RF180C to PROFINET IO can be found in the PROFINET System Manual. You will find the system manual on the Internet at the following address: http://www.siemens.com/automation/service&support Search for the entry with the ID number 19292127. CAUTION PROFINET Modules with PROFINET interfaces may only be operated in LANs (Local Area Networks) in which all connected nodes are equipped with SELV/PELV power supplies or protection systems of equal quality. A data transfer terminal (modem, for example) is required to access the WAN (Wide Area Network) in order to ensure compliance with this safety standard. The power supply must provide the current required (max. 1.5 A) during brief power failures of ⤠20 ms. All supply and signal voltages must be safety extra low voltage (SELV/PELV according to EN 60950). 24 V DC power supply: safe (electrical) isolation of extra-low voltage (SELV/PELV according to EN 60950). NOTICE The device must not be connected to the public telephone network without a HUB / Switch because the voltage intervals are designed for 500 V. 230 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C PROFINET IO installation techniques PROFINET IO communication can be established in BUS or STAR topology. Please note the information in the Section Loop-through connection of PROFINET IO and supply voltage. 3/& HJ6&38 5)& 5)& 5)& 352),1(7,2FDEOH 9'& Figure 7-47 RF180C with BUS topology 3/& HJ6&38 5)& 352),1(7,2FDEOH 5)& 5)& 6ZLWFK HJ6&$/$1&( 9'& Figure 7-48 RF180C with STAR topology SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 231 Communication modules 7.8 RF180C Reader/SLG connection system One reader/SLG always occupies one M12 connection socket on the RF180C. A preassembled cable therefore provides the optimum easy connection for the reader/SLG. The connection cable is 2 m long in the standard version. 3/& HJ6&38 5)& 352),1(7,2FDEOH WRRWKHU 352),1(7,2VWDWLRQV 5HDGHU 5HDGHU 7UDQVSRQGHU Figure 7-49 232 Overview of wiring SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C 7.8.2.1 Wiring connection block M12, 7/8" Features â Connect the supply voltages and PROFINET IO to connection block M12, 7/8": â M12 connection in D coding: PROFINET IO â 7/8" connection: Supply voltages â You can loop the supply voltages and PROFINET IO through via the second M12 or 7/8" round socket. Requirements â Wire connection block M12, 7/8" when the supply voltage is switched off. Required tools Stripping tool, screwdriver for wiring the M12 and/or 7/8" connector if you are not using a pre-assembled cable. Accessories required â Pre-assembled cable with connector â If you are not using a pre-assembled cable: â M12: 4-core Ethernet cable (Twisted Pair), shielded and M12 connector, 4-pole, D coding (see Table Pin assignments of M12 connector, 4-pole, D coding (PROFINET IO)) â 7/8": 5-core cable and 7/8" connector (see Table Pin assignment for 7/8" connector (supply voltages)) â For order numbers, refer to Section Ordering data. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 233 Communication modules 7.8 RF180C Wiring M12, 7/8" connector The tables below contain the pin assignment for the M12 and 7/8" connectors: Table 7-25 Pin assignment for M12 connector, 4-pole, D coding (PROFINET IO) Pin Assignment Data line TxP Data line RxP Data line TxN Data line RxN View of M12 connector, 4-pole, D coding (wiring side) (LQVSHLVHQXQG:HLWHUVFKOHLIHQ 352),1(7,2;; (WKHUQHW.DEHO 7ZLVWHG3DLU Any connector can be used for infeed and looping through Table 7-26 Pin Pin assignment for 7/8" connector (supply voltages) Assignment Load voltage ground (2M) Ground for electronic / encoder supply (1M) Functional ground (PE) Electronics / encoder supply (1L+) (voltage supply for RF180C and reader/SLG) View of 7/8" connector (wiring side) 6XSSO\; / / Load voltage supply (2L+) (unused on RF180C) /RRSWKURXJKFRQQHFWLRQ; FRUHFDEO / / Note When connecting up the supply voltage, we recommend the cable specified in the Section Ordering data (cable 5 x 1.5 mm2 pre-assembled with 7/8" connectors). If you want to assemble the cable yourself, then the conductor cross-section should be 1.5 mm2. 234 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C Connecting M12, 7/8" connectors 1. Press the connector (M12 or 7/8") into the relevant round socket on the connection block. Ensure that the correct stop is provided between the connector and bush (groove and spring). 2. Use the knurled locking ring to secure the connector. & 5) ,& $7 6, Figure 7-50 Connecting M12, 7/8" connectors Sealing unused sockets Always close all unused sockets using M12 or 7/8" seal caps in order to achieve the degree of protection IP65, IP66 or IP67. For order numbers, refer to Section Ordering data. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 235 Communication modules 7.8 RF180C 7.8.3 Parameter assignment 7.8.3.1 PROFINET IO configuration Introduction The GSDML file allows you to configure RF180C in STEP 7 V5.3 + SP 2 or higher. The GSDML file must have been installed beforehand in the configuration software. Requirements â A GSDML file is required to integrate the RF180C into the hardware configuration of the SIMATIC Manager: GSDML-V1.0-SIEMENS-RF180C-"Datum im Format yyyymmdd".xml You will find the file on the CD RFID Systems Software & Documentation in the directory Daten\PROFI_GSD\RF180C. â The RF180C must have a valid IO device name. The default device name is RF180C Configuring the RF180C on PROFINET IO with STEP 7 1. Start STEP 7, then select Options > Install New GSD File in HW Config. 2. Select the GSDML file to install from the next dialog box, then confirm with OK. Result: The RF180C is displayed in the HW catalog under Profinet IO > Ident Systems > SIMATIC RFID. 3. Create a new project. 4. Configure the RF180C in HW Config. 5. Parameterize the RF180C. 6. Save the configuration, or download it to the PROFINET IO controller. Further information can be found in the Sections Assigning device names to the IO device and Configuration parameters of the RF180C. 236 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C 7.8.3.2 Assigning device names to the I/O device Introduction Each PROFINET IO device is assigned a unique device ID by the manufacturer (MAC address). Each RF180C IO device is addressed by its device name in the configuration and user program. For detailed information on addressing in PROFINET IO, refer to the PROFINET System Description. Requirements â RF180C communication module â The PG must be online on PROFINET to the IO device to let you assign a device name to the communication module. â There must be no connection to the CPU. Transferring the device name to the communication module 1. In HW Config select PLC > Ethernet > Edit Ethernet Node. 2. Click thebutton for modules that can be accessed online. This will display all accessible PROFINET IO controllers and IO Devices complete with MAC address, IP address (where applicable), device name and device type. 3. Select the required RF180C and click . 4. Assign a device name and click the button . The device name must be unique within the plant and must comply with the HW Config configuration. Result The device name is saved in connection block and base unit of the RF180C communication module. Forwarding the device name when the communication module is replaced The device name of the IO device is saved in the connection block. To transfer the device name when the RF180C communication module is replaced, remove the connection block from the "old" RF180C and plug it into the "new" RF180C. The station can be addressed again and will operate as before the replacement. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 237 Communication modules 7.8 RF180C Station flash test If you use more than one IO device, the dialog also displays more than one IO device. In this case, you should compare the MAC address of the device with the indicated MAC address and select the proper IO device. The identification of IO devices in a system is facilitated by a node flash test. The flash test is activated as follows: 1. In the Edit Ethernet Node dialog, select one of the indicated IO devices. 2. Press the button . On the selected IO device both "Link" and "RX/TX" LEDs flash on the connection block. 3. With fliashing stops again. 238 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C 7.8.3.3 Configuration parameters of the RF180C The GSDML file contains four parameters relevant to RFID that must be set. They are set by selecting the "Object properties" for slot 0 of the RF180C in HW Config The parameters are described in the function manual FB 45. The table below shows the possible settings: Table 7-27 Setting of RFID-relevant parameters Parameter name USER_Mode MOBY_Mode Value Note FB 45 Default FB 55 With later firmware version FB 56 With later firmware version RFID standard profile With later firmware version MOBY I / E standard addressing MOBY I file handler With later firmware version MOBY U / D / RF300 standard addressing Default MOBY U file handler With later firmware version Baud rate for read/write device RF300 / MOBY U/D 19.2 k baud Diagnostics with diagnostics messages (see Diagnostics chapter) none Standard diagnostics only Hard errors Hardware-related messages only Hard/soft errors low priority All messages Hard/soft errors high priority All messages high-priority 1) 57.6 k baud 1) 115.2 k baud Default 1) Not permitted with MOBY D with SLG D11S/D12S SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 239 Communication modules 7.8 RF180C 7.8.3.4 Input parameters for RF180C Input parameters for RF180C with FB 45 Allocation is undertaken in UDT 10. Table 7-28 Input parameters for RF180C with FB 45 Address +0.0 Name ASM_address Comment Each RF180C occupies four bytes of I/O in the I/O area of the controller ASM_channel Permissible values 256, 260, 264, 268, ... 1, 2 +2.0 +8.0 MDS_control B#16#0, 1 0 = no presence check 1 = presence check +9.0 ECC_mode TRUE, FALSE +9.1 RESET_long TRUE, FALSE +10.0 MOBY_mode B#16#1, 4, 5, 6, 7, 8, 9, A, B +11.0 scanning_time +12.0 option_1 MOBY I: B#16#00 ... FF MOBY U: B#16#00 ... C8 B#16#00, 02, 04 +13.0 distance_limiting +14.0 +15.0 multitag field_ON_control +16.0 field_ON_time 240 MOBY U (normal output power): B#16#05, 0A, 0F, 14, 19, 1E, 23 MOBY U (reduced output power): B#16#85, 8A, 8F, 94, 99, 9E, A3 MOBY D: B#16#02 ... 28 B#16#1 MOBY U: B#16#0, 1, 2, 3 MOBY D, RF300: B#16#0 MOBY U: B#16#00 ... FF MOBY D: B#16#00, 01 TRUE, if MOBY_mode = 5 (MOBY U/D; RF300) Special features of the MOBY I dialog (8): ⢠Write/read device must be type SLG4x. ⢠The VMDS memory size is 16KB. The INIT command for the VMDS must be specified using 4000 hex. A value not equal to 00 is only practical if MOBY_mode has been parameterized accordingly. MOBY D, RF300 reserved (00) MOBY U/D RF300 reserved (00) MOBY U/D, RF300 MOBY U/D, RF300 MOBY U/D RF300 reserved (00) SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C 7.8.3.5 Command table of the RF180C Table of commands of the RF180C for standard addressing (FB 45) Allocation is undertaken in UDT 20 using the "command" variable. Table 7-29 Commands for RF180C with standard addressing Command code Description Available in the RFID system normal linked * 01 41 Describe MDS all 02 42 Read MDS; read fixed code all 03 43 Initialize MDS all 04 44 SLG status 08 48 Switch off MDS 0A 4A Turn antenna on/off 0B 4B MDS status RF300/MOBY U/D MOBY U RF300/MOBY U/D RF300/MOBY U *) Chained commmands are not supported by all readers / SLGs. Please note the relevant information in the RFID system manuals. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 241 Communication modules 7.8 RF180C 7.8.4 PROFINET diagnostics 7.8.4.1 Diagnosis using LEDs The following figure shows details of the LEDs of the RF180C. With M12 connection block (7/8") With push-pull connection block ; $&7B 35(B 5['B (55B 6,0$7,&5)& 6,0$7,&5)& 5HDGHU6/* ; 5HDGHU6/* $&7B 35(B 5['B (55B ; ; *7-' *7-' 6) [ %) 21 '&9 [ /LQN 5;7; [ [ [ [ 242 [ [ SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C Table 7-30 Status LEDs for the RF180C LEDs Meaning* ON Lights up when the RF180C has completed start-up without errors. 24 VDC Lights up when the 24 V supply voltage is connected to the RF180C. ACT_1, ACT_2 The corresponding reader/SLG is active in processing a user command. ERR_1, ERR_2 * A flashing pattern indicates the last error to occur. PRE_1, PRE_2 ** Indicates the presence of a tag/MDS. RxD_1, RxD_2 Indicates live communication with the reader / SLG. May also indicate malfunctions on the reader / SLG. *) The meaning of the individual flash patterns and the associated fault descriptions can be found in the relevant FB documentation. **) In multitag mode, this LED uses a flash interval to indicate the number of data media currently within the range of influence of the reader/SLG. Table 7-31 LED display for PROFINET diagnostics BF SF On â Cause of error ⢠⢠Flashes ⢠Error handling Communication module is in start- When the bus is configured correctly, this state ends a up mode. few seconds after switching the module on. No cable inserted There is no connection to the PROFINET IO controller. ⢠⢠⢠Off On ⢠A PROFINET diagnostic signal exists. ⢠Off Off ⢠Normal mode â Check the PROFINET IO connection. Check your PROFINET IO configuration (device name, GSDML file). Reload the configuration into the RF180C (see the Section "Configuration parameters of the RF180C") Analyze the diagnostic data. â = Status not relevant Table 7-32 LEDs on connection block Link (green) Tx / Tx (yellow) Meaning Off Off No physical connection over PROFINET IO On Off Physical connection over PROFINET IO, no data communication On Flashes Physical connection over PROFINET IO, with data communication Off On Temporary state following switch-on The table is applicable to both left and right PROFINET IO connection. Other communication module operating modes are indicated by the PRE, ERR, ACT, SF and ON LEDs: SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 243 Communication modules 7.8 RF180C Table 7-33 LED display for operating states ON BF SF PRE_1 ERR_1 ACT_1 PRE_2 Off Off Off Off Off Off On On On On On On ERR_2 ACT_2 Description Off Off Off Start-up active On On On LED test on start-up (start PROFINET IO) Off Off On On On Off On On Off Internal fault Off Off On On Off On On Off On Checksum error of the firmware Off Off On Off Slow flashin Off Off Slow flashin Off Firmware update (flashes with every described area) 244 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C 7.8.4.2 Parameterization of the diagnostics â Faults are reported by PROFINET IO through the generation of alarms. Alarms are output using OB82. The alarm data can be accessed through SFB 54. Parameterizing possibilities See also Section Configuration parameters of RF180C. â None An alarm will not be issued in the event of an error. â Hard errors Alarms are generated in the case of the following events: â Hardware fault (memory test) â Firmware fault (checksum) â Interrupted connection to the reader/SLG An alarm is generated and the SF LED on the S7 CPU is activated. â Hard/soft errors low priority In contrast to hard errors, in this case, errors are also reported that arise during command processing An alarm is generated. However the SF LED on the S7 CPU is activated. â Hard/soft errors high priority As under hard/soft errors low priority An alarm is generated when an event occurs as well as when the event ceases. Incoming alarm An event occurs and triggers an alarm. The SF LED of the S7 CPU is set as parameterized. Outgoing alarm An event no longer exists, an alarm is triggered and the SF LED of the S7 CPU is reset. For events that only exist momentarily, the reset is delayed by 3 seconds. Further information Detailed information about PROFINET IO diagnostics is included in the following documents: â System manual PROFINET, System Description (Article No. 19292127) â Programming manual PROFINET IO, from PROFIBUS DP to PROFINET IO (Article No. 19289930) â Product information PROFINET IO, Structure of the Diagnostic Data Records (Article No. 19327300) You will find the documents on the Internet at: http://www.siemens.com/automation/service&support Search for the specified article numbers here. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 245 Communication modules 7.8 RF180C 7.8.4.3 Structure of the diagnostic data The header of a diagnostic data record comprises 20 bytes of PROFINET IO-specific data. The manufacturer-specific diagnostic data start from Byte 21. For the RF180C, the diagnostic data are structured in accordance with the PROFIBUS Profile Guideline (PROFIBUS Proxy Guideline, Identification Systems Proxy Ident Function Block) for identification systems with MOBY-specific additional information. Byte Name Contents PROFIBUS Profile Guideline for Identification Systems 20 channel_num Bit 7..0 1d: Relating to Reader 1 21 function_num Reserved for a future expansion stage 22 error_decode Reserved for a future expansion stage 23 error_code_1 Reserved for a future expansion stage 24 error_code_2 Reserved for a future expansion stage 2d: Relating to Reader 2 RFID-specific additional information 246 25 moby_code_1 Reserved for a future expansion stage 26 moby_code_2 Reserved for a future expansion stage 27 moby_code_3 Reserved for a future expansion stage 28 moby_code_4 Error code To be taken from the corresponding FC/FBs. 29 meldecode Error code To be taken from the corresponding FC/FBs. 30 counter_high Continuous event counter high-order byte 31 counter_low Continuous event counter low-order byte 32 fw_version_high Firmware version high-order byte 33 fw_version_low Firmware version low-order byte SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C 7.8.5 Technical data Table 7-34 General technical data Ethernet interface to the user Principle PROFINET IO Physical medium Ethernet over 4-core cable Duty type 100BaseX full duplex Transmission rate 100 Mbit/s Plug-in connection M12, 4-pin, D coding Maximum cable length 100 m Cable type STP Cat 5 Autonegotation Yes Autocrossing Yes Switch function Yes, internal IRT No RT Yes Manufacturer ID (vendor ID) 002AH Device ID (DeviceID) 0C01H Serial interface to the reader/SLG Connector 2 x M12 coupler plugs, 8-pin Max. cable length 1000 m, dependent on Reader/SLG (2 m = standard length; for other standard cables and selfassembled cables, refer to Section Connection cables) Connectable readers/SLGs 2 x readers/SLGs of the RFID families RF300, MOBY D/I/E/U Software functions Programming Depends on the PROFINET IO controller SIMATIC S7 function blocks FB 45 (normal addressing without multitag) Tag/MDS addressing Direct access via addresses Commands Initialize tag, read data from tag, write data to tag, etc. Supply voltage1) Rated value 24 V DC Permissible range 20 V to 30 V DC Current consumption without reader / SLG 2) max. 500 mA; typ. 100 mA Current consumption through reader connection Each 500 mA Maximum infeed current in the M12 connection block (7/8") L1 = 6 A L2 = 8 A Maximum infeed current in the pushpull connection block Up to 40 °C: Up to 60 °C: L1 = 12 A3) L2 = 12 A L1 = 8 A L2 = 8 A Galvanic isolation SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Yes 247 Communication modules 7.8 RF180C Ambient temperature During operation 0 to +60 °C Transport and storage â40 to +70 °C Dimensions (W x H x D) in mm Base unit only 60 x 210 x 30 Base unit with M12, 7/8" connection block 60 x 210 x 54 Basic unit with push-pull connection block 60 x 216 x 100 Weight Base unit Approx. 210 g M12, 7/8" connection block Approx. 230 g Push-pull connection block Approx. 120 g Mechanical Environmental Conditions Mounting position All mounting positions are possible Vibration during operation According to IEC 61131-2: 0.75 mm (10Hz to 58 Hz) 10 g (58 Hz to 150 Hz) Shock resistance, shock during operation Acc. to IEC 61131-2: 30 g Degree of protection IP67 MTBF (Mean Time Between Failures) in years Base unit 121 Connection block 1100 Approvals cULus (file E116536) FCC Code of Federal Regulations, CFR 47, Part 15, Sections 15.107 and 15.109 (Class A) 1) All supply and signal voltages must be safety extra low voltage (SELV/PELV according to EN 60950) 24 V DC supply: Safety (electrical) isolation of low voltage (SELV / PELV acc. to EN 60950) 2) The power supply must provide the current required (max. 500 mA) during brief power failures of ⤠20 ms. 3) 248 A cable cross-section of 2.5 mm2 is mandatory for an amperage > 8 A. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C 7.8.6 Dimension drawing for RF180C with fixing holes Dimension drawing of an RF180C with M12 bus connection block (7/8" PN) [ 6,0$7,&5)& [ [ [ [ [ Figure 7-51 Dimension drawing of an RF180C with M12 bus connection block (7/8" PN) SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 249 Communication modules 7.8 RF180C Dimension drawing of an RF180C with push-pull bus connection block [ [ [ [ Figure 7-52 250 [ [ Dimension drawing of an RF180C with push-pull bus connection block SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C 7.8.7 Connecting cable to the reader/SLG 7.8.7.1 Routing of standard cables Available cables Figure 7-53 Connecting cable M12 â Reader / SLG; l = 2 m, 5 m (MOBY I / E / U) Figure 7-54 Connecting cable/extension cable M12 â M12; l = 2 m, 5 m, 10 m, 20 m, 50 m â RF300 connecting cable â Extension cable for all RFID systems P Figure 7-55 Connecting cable M12 â sub-D (MOBY D) Maximum cable length The RF180C can be operated with any reader/SLG configuration with a maximum cable length of 50 m. Longer connecting cables of up to 1000 m are possible in some instances. The current consumption of the connected reader/SLG must however be taken into account. You will find information in the relevant system manuals. Sequential arrangement of more than two sub-sections to form a long section of cable should be avoided due to the additional contact resistances. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 251 Communication modules 7.8 RF180C Pin assignment Table 7-35 Connecting cable M12 â Reader / SLG M12 connector (male) Table 7-36 â Table 7-37 Connecting cable M12 â sub-D 9-pin M12 connector (male) Connecting cable / extension cable M12 <-> M12 Reader/SLG connector (female) Sub-D connector (female) â â 1, 8 Note: Reader/SLG with Sub-D connector must be supplied over an additional connector with 24 V DC. 252 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C 7.8.7.2 Self-assembled cable A reader/SLG connector plug with screw terminals is provided for users who want to individually pre-assemble their own cables (refer to the relevant system manual). Cables and reader/SLG connector plugs can be ordered from the Catalog FS 10 Sensors for Production Automation. Cable structure You will need cables of the following specifications for self-assembled cables: 7 x 0.25 mm2 LiYC11Y 7 x 0.25 Connectors M12 connectors can be obtained from the relevant specialist dealers (e.g. Binder). Pin assignment The pin assignment is listed in the following table. Table 7-38 Pin assignment M12 connector (male) SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Pin Signal Core color 1L+ (+ 24 V) âRxD Note data sheet provided by cable manufacturer 0V RxD TxD âTxD Free Functional ground (PE)/shield 253 Communication modules 7.8 RF180C 7.8.8 Ordering data Table 7-39 RF180C ordering data and accessories RF180C RF180C communication module max. 2 SLGs or readers can be connected 6GT2002-0JD00 Connection block M12, 7/8" PN 6GT2002-1JD00 Push-pull connection block, RJ45 6GT2002-2JD00 Labels 20 x 7 mm (1 pack = 340 items) 3RT1900-1SB20 Accessories for connection block M12, 7/8" PN IE plug-in cable for PROFINET 6XV1870-8Axxx * (pre-assembled trailing cable with two M12 connectors, 4-pin, code D) 7/8"-plug-in cable for supply voltage (5 x 1.5 mm2) (pre-assembled trailing power cable with two 5-pin 7/8" connectors) 6XV1822-5Bxxx * Trailing power cable (5 x 1.5 mm2) (not preassembled; length min. 20 m, length max. 1000 m) 6XV1830-8AH10 Connector plug 7/8" for supply voltage; (1 pack = 5 items) ⢠with pin insert ⢠with socket insert 6GK1905-0FA00 6GK1905-0FB00 RJ45 plug-in cable with metal casing and FC connection system, 180 ° cable outlet;(1 pack = 1 item) 6GK1901-1BB10-2AA0 Control cabinet feedthrough for conversion from M12 connection method (D coded, IP65) to RJ45 connection method (IP20) ;(1 pack = 5 items) 6GK1901-0DM20-2AA5 M12 plug-in cable with metal casing and fast connection system, 180 ° cable outlet (D coded) ; (1 pack = 1 item) 6GK1901-3JA00-0AA0 M12 covering caps 3RX9802-0AA00 Covering caps 7/8" (1 pack = 10 items) 6ES7194-3AJ00-0AA0 PROFINET standard cable 2x2, Type A, unassembled; minimum order quantity 20 m 6XV1840-2AH10 Accessories for push-pull connection block 254 Trailing power cable (5 x 1.5 mm2) (not preassembled; length min. 20 m, length max. 1000 m) 6XV1830-8AH10 Push-pull cable connector for 1L+/2L+, not preassembled 6GK1907-0AB10-6AA0 Push-pull cable connector for RJ45, not preassembled 6GK1901-1BB10-6AA0 Caps for push-pull sockets (1L+/2L+), 5 items per package, 1 item 6ES7194-4JA50-0AA0 Caps for push-pull sockets RJ45, 5 items per package, 1 item 6ES7194-4JD50-0AA0 PROFINET standard cable 2x2, Type A, unassembled; minimum order quantity 20 m 6XV1840-2AH10 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Communication modules 7.8 RF180C Accessories for RFID SLG cable MOBY I / E / U; 2 m 6GT2091-0FH20 SLG cable MOBY I / E / U; 5 m 6GT2091-0FH50 SLG cable MOBY D; 2 m 6GT2691-0FH20 Reader cable RF300, extension cable RF300 / MOBY I / E / U / D; 2 6GT2891-0FH20 Reader cable RF300, extension cable RF300 / MOBY I / E / U / D; 5 6GT2891-0FH50 Reader cable RF300, extension cable RF300 / MOBY I / E / U / D; 10 6GT2891-0FN10 Reader cable RF300, extension cable RF300 / MOBY I / E / U / D; 20 6GT2891-0FN20 Reader cable RF300, extension cable RF300 / MOBY I / E / U / D; 50 6GT2891-0FN50 Reader cable for RF300; connector on the reader is angled; 2 m 6GT2891-0JH20 MOBY software with FB 45, GSDML file and FB 45 Function Manual (electronic in English/German) 6GT2080-2AA10 *) These cables are available in different lengths. See Catalog IK PI for more details SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 255 Communication modules 7.8 RF180C 256 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 8 System diagnostics 8.1 Error codes Error codes of the RF300 readers Flashing of red Error code LED on reader (hexadecimal) Description 00 00 no error 01 0F Boot message 02 01 Presence error, possible causes: ⢠The active command was not carried out completely ⢠The tag has left the field while the command is being processed ⢠Communication fault between reader and tag 05 05 Parameterization error, possible causes: ⢠Unknown command ⢠Incorrect parameter ⢠Function not allowed 06 06 Air interface faulty 12 0C The tag memory cannot be written, possible causes: ⢠Hardware fault (memory faulty) ⢠Memory write-protected (corresponding OTP area has already been written) 13 0D Error in the specified memory address (access attempted to nonexistent or non-accessible memory areas). 19 13 Buffer overflow: Insufficient buffer available in the reader for saving the command 20 14 Major system fault (hardware fault) 21 15 Parameter assignment error: faulty parameter in RESET command 25 19 Previous command is still active 28 1C Antenna is already switched off/Antenna is already switched on, mode in SET-ANT command not recognized. 30 1E Incorrect number of characters in frame 31 1F Running command cancelled by "RESET" command SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 257 System diagnostics 8.2 Diagnostics functions 8.2 Diagnostics functions 8.2.1 Overview Extended diagnostic functions with SIMATIC RF300 With SIMATIC RF300, extended diagnostic functions are available which simplify start-up and maintenance. These diagnostic data are accessed using the FC 45 function with the SLG STATUS and MDS STATUS commands. These two commands can each be called in various modes (subcommands) for which corresponding data structures (UDTs) are defined. Command Mode (subcommand) Meaning SLG STATUS 01 Hardware and firmware configuration, parameterization status 06 Communication error counter, current command status 01 Serial number of the tag (UID), memory configuration MDS STATUS EEPROM write-protection status 02 Serial number of the tag (UID), HF field strength value, communication error counter, presence counter (duration) Overview of the diagnostic functions 258 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 System diagnostics 8.2 Diagnostics functions 8.2.2 Reader diagnostics with SLG STATUS The SLG STATUS command can be used to scan the status and diagnostics data of the reader. SLG STATUS (mode 01), UDT110 HW ASCII Type of hardware (31 to 38 hex) HW-V Url-V Binary value Binary value HW version 0 to FF hex = Version (high byte): Unused 0 to FF hex = Version (low byte) Version of loader 0 to FF hex = Version (high byte) 0 to FF hex = Version (low byte) FW ASCII format Type of firmware FW-V Binary value Firmware version 0 to FF hex = Version (high byte) 0 to FF hex = Version (low byte) "1" = 3964R TR Binary value Type of driver TR-V Binary value Version of driver 0 to FF hex = Version (high byte) 0 to FF hex = Version (low byte) SS Binary value RS232 / RS422 Baud Binary value Baud rate 01 hex = RS422 01 hex = 19.2 Kbaud 02 hex = 57.6 Kbaud 05 hex = 115,2 Kbaud mtag Binary value Number of MDSes (Multitag/Bulk) = 1 with single-tag mode (param = that can be processed in the 0x05, 0x25) antenna field ANT Binary value Status of antenna ANW Binary value SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 01 hex = Antenna On 02 hex = Antenna Off Presence mode = Operation without presence 01 hex = Operation with presence (see ANW-MELD signal) 259 System diagnostics 8.2 Diagnostics functions SLG STATUS (mode 06), UDT280 FZP Binary value 0 ⌠255 = Error counter, passive (errors during idle time) ABZ Binary value 0 ⌠255 = Abort counter CFZ Binary value 0 ⌠255 = Code error counter SFZ Binary value 0 ⌠255 = Signature error counter CRCFZ Binary value 0 ⌠255 = CRC error counter BSTAT Binary value 0 ⌠255 = Current command status ASMFZ Binary value 0 ⌠255 = Interface problems to host (ASM/PC) parity, BCC, frame error Note All counter values are reset after reading (= SLG STATUS command executed). Explanations: â "FZP": Counts interference pulses when communication is not taking place with a transponder. (e.g. EMC interference caused by contactors, motors, etc.). Counter values can also be generated when a tag is located at the edge of the field even when there is no external interference. â "ABZ", "CFZ", "SFZ" and "CRCFZ" are protocol error counters that can be generated during reader/tag communication. This can be caused by unsuitable reader/tag positioning (e.g. tag on field boundary, several data carriers in the field) or external electromagnetic interference. To ensure clear diagnosis of the quality of communication, it is recommended that an SLG STATUS command (mode 06) is executed following receipt of the presence command to reset the error counter. The protocol error counters are not mutually independent. If a code error (CFZ) occurs, this will cause a secondary signature (SFZ) or CRC (CRCFZ) error. â "BSTAT" is the status for the most recently executed command. A value other than 0 means that the previous command was repeated by the reader due to faults (see above). â "ASMFZ" signals line-conducted communication interference between the communication module (ASM) and the reader. Faults of this type can be caused by contact problems on the connector or the cable connection. 260 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 System diagnostics 8.2 Diagnostics functions 8.2.3 Transponder diagnostics with MDS STATUS The MDS STATUS command can be used to scan the status and diagnostics data of the transponder that is located within the antenna field. MDS STATUS (mode 01), UDT260 UID Binary value 0 ⌠264 -1 = b0-31: 4 byte TAG ID, b32-63: 0 MDS type Binary value 0x01 = Transponder without FRAM 0x02 = Transponder with FRAM 8 KB 0x03 = Transponder with FRAM 32 KB 0 ⌠255 = Content of lock-bit register (EEPROM addr. 0xFF18) Lock status Binary value MDS STATUS (mode 02), UDT270 LFD Binary value 0 ⌠255 = Value for field strength FZP Binary value 0 ⌠255 = Error counter (passive) â errors during idle time FZA Binary value 0 ⌠255 = Error counter (active) ANWZ Binary value 0 ⌠255 = Presence counter Note All counter values are reset when the tag exits the field or when the antenna is switched off. Notes: â "LFD" is a value for the field strength that is determined in the transponder. The lower the value, the higher the field strength. A setpoint of < 28 hex signals reliable data transfer. â "FZP" counts fault pulses when communication with a transponder is not taking place (e.g. electromagnetic interference caused by contactors, motors, etc.). Counter values can also be generated when a transponder is located at the edge of the field even when there is no external interference. â "FZA" counts errors that can occur during reader-to-transponder communication. This can be caused by unsuitable reader/transponder positioning (e.g. transponder on field boundary, several data carriers in the field) or external electromagnetic interference. â "ANWZ" is the value for the time that the transponder remains in the field before the MDS STATUS command (mode 02) is executed. A time step is 10 ms. The maximum time that can be recorded is therefore 2.5 s. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 261 System diagnostics 8.2 Diagnostics functions 262 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 9 Accessories CD "RFID Systems Software & Documentation" The CD contains: â FB/FC for SIMATIC, 3964R â Driver for DOS/Windows 95/NT/2000/XP â C libraries â PC demonstration program â RFID documentation in PDF format, especially RFID system manuals, programming instructions and operating instructions The "RFID Systems Software & Documentation" CD has a user-friendly interface based on HTML. After Start.exe has been called, a window for selecting the RFID system appears: â RF300 â RF600 â RF-MANAGER â MOBY â CM/ASM After selecting the RFID system, you can navigate to the required information. Product Order No. CD "RFID Systems Software & Documentation" 6GT2 080-2AA10 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 263 Accessories Note Notes on "RFID system software" and licensing When purchasing a communication module or an interface module, no software or documentation is supplied. The "RFID Systems Software & Documentation" CD-ROM contains all available FBs/FCs for the SIMATIC, C libraries, demo programs, etc. and needs to be ordered separately. In addition, the CD-ROM contains the complete RFID documentation (German, English and French) in PDF format. The purchase of a communication module or an interface module includes a payment for the use of the software, including documentation, on the "RFID Systems Software & Documentation" CD-ROM and the purchaser acquires the right to make copies (copy license) insofar as they are required as part of the customer-specific application or development for the plant. The enclosed contract pertaining to the use of software products against a one-off payment shall apply in addition. 264 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 A Appendix A.1 Certificates and Approvals DIN ISO 9001 certificate The quality assurance system for the entire product process (development, production, and marketing) at Siemens fulfills the requirements of ISO 9001 (corresponds to EN29001: 1987). This has been certified by DQS (the German society for the certification of quality management systems). EQ-Net certificate no.: 1323-01 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 265 Appendix A.1 Certificates and Approvals Certifications for the United States, Canada, and Australia Safety One of the following markings on a device is indicative of the corresponding approval: Underwriters Laboratories (UL) per UL 60950 (I.T.E) or per UL 508 (IND.CONT.EQ) Underwriters Laboratories (UL) according to Canadian standard C22.2 No. 60950 (I.T.E) or C22.2 No. 142 (IND.CONT.EQ) Underwriters Laboratories (UL) according to standard UL 60950, Report E11 5352 and Canadian standard C22.2 No. 60950 (I.T.E) or UL508 and C22.2 No. 142 (IND.CONT.EQ) UL recognition mark Canadian Standard Association (CSA) per Standard C22.2. No. 60950 (LR 81690) or per C22.2 No. 142 (LR 63533) Canadian Standard Association (CSA) per American Standard UL 60950 (LR 81690) or per UL 508 (LR 63533) 266 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Appendix A.1 Certificates and Approvals EMC USA Federal Communications Commission Radio Frequency Interference Statement This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Shielded Cables Shielded cables must be used with this equipment to maintain compliance with FCC regulations. Modifications Changes or modifications not expressly approved by the manufacturer could void the user's authority to operate the equipment. Conditions of Operations This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. CANADA Canadian Notice This Class B digital apparatus complies with Canadian ICES-003. Avis Canadien Cet appareil numĂŠrique de la classe b est conforme Ă la norme NMB-003 du Canada. AUSTRALIA This product meets the requirements of the AS/NZS 3548 Norm. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 267 Appendix A.2 Service & Support A.2 Service & Support Technical Support You can reach the technical support team for all A&D projects at â Phone: +49 (0) 180 5050 222 â Fax: +49 (0) 180 5050 223 Internet â You can contact us via the Internet at: http://www.siemens.com/automation/service&support â We will gladly respond to any support queries at: http://www.siemens.com/automation/support-request â You can find the latest general information about our identification systems on the Internet at: http://www.siemens.com/simatic-sensors/rf â You will find the online catalog and the online ordering system at: http://www.siemens.com/automation/mall A.3 Contacts If you have any further questions on the use of our products, please contact one of our representatives at your local Siemens office. The addresses are found on the following pages: â On the Internet at: http://www.siemens.de/automation/partner â In catalog CA 01 â In Catalog FS 10 specially for factory automation sensors 268 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Appendix A.4 Training A.4 Training Training center We offer appropriate courses to get you started. Please contact your local Training Center or the Central Training Center in D-90327 Nuremberg. Telephone: +49 (911) 895-3200 http://www.siemens.de/sitrain SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 269 Appendix A.4 Training 270 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Glossary Active surface Area with minimum field strength containing the transmission window, as well as the areas in which the field strength is no longer sufficient for data exchange. Automation system (AS) A programmable logical controller (PLC) of the SIMATIC S7 system, comprising a central controller, a CPU and various I/O modules. Battery-free data storage unit Mobile data storage units which operate without batteries. Power is supplied to the data storage unit across an electromagnetic alternating field. Byte A group of eight bits forms a byte CE marking CommunautĂŠ EuropĂŠenne (product mark of the European Union) Communication modules Communication modules are used to integrate the MOBY identification systems in SIMATIC or SINUMERIK systems, or to connect them to PROFIBUS, PC or any other system. Once supplied with the corresponding parameters and data, they handle data communication. They then make the corresponding results and data available. Suitable software blocks (FB/FC for SIMATIC; C libraries for PCs with Windows) ensure easy and fast integration in the application. Data transmission rate Unit of measurement for the volume of data transmitted within a unit of time, e.g. bytes/s Dwell time The dwell time is the time in which the transponder dwells within the transmission window of a read/write device. The read/write device can exchange data with the transponder during this time. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 271 Glossary Dynamic mode In dynamic mode, the data carrier moves past the read/write device at a traversing rate which depends on the configuration. Various checking mechanisms (listen-in check, CRC, ECC, etc.) ensure error-free data transfer even under extreme environmental conditions. A serial connection (up to 1000 m) is used to connect the read/write device directly to an interface module, PC, or any other system. Electromagnetic compatibility Electromagnetic compatibility is the ability of an electrical or electronic device to operate satisfactorily in an electromagnetic environment without affecting or interfering with the environment over and above certain limits. EMC Directive Guidelines for electromagnetic compatibility This guideline relates to any electrical or electronic equipment, plant or system containing electric or electronic components. Equipotential bonding Potential differences between different parts of a plant can arise due to the different design of the plant components and different voltage levels. It is necessary to compensate for these differences by equipotential bonding: this is done by combining the equipotential bonding conductors of power components and non-power components on a centralized equalizing conductor. ESD Directive Directive for handling ESDs. Frequency hopping Frequency hopping technique Automatic search for free channels. In frequency hopping, data packets are transferred between the communication partners on constantly changing carrier frequencies. This makes it possible to react to interference from devices transmitting signals in the same frequency range. If an attempt to send a data packet is unsuccessful, the packet can be transmitted again on a different carrier frequency. Interface modules (ASM) See communication modules IQ-Sense interface Simple interface on the IQ-Sense module, using a standard design for all types of sensors, enabling integrated data exchange between the sensor and control system. 272 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Glossary Limit distance The limit distance is the maximum clear distance between the upper surface of the read/write device and the transponder, at which the transmission can still function under normal conditions. Centerpoint of a field of a transmission window Metal-free area Distance/area which must be maintained between the transponder and metal in order to prevent interference during data transfer between the transponder and read/write device. Mobile data storage units (MDS) See transponder Multi-tag capability Multi-tag capability means the ability to use several read/write devices which communicate simultaneously with different data carriers. Programmable logic controller (PLC) The programmable logic controllers (PLC) of the SIMATIC S5 system consist of a central controller, one or more CPUs, and various other modules (e.g. I/O modules). Read/write devices (SLG) See readers Read/write distance See transmission distance Readers Readers ensure fast, secure data transfer between mobile data storage units and higherlevel systems (PLCs, PCs, etc.). The data, energy included, are transmitted inductively across an electromagnetic alternating field or by radio. This principle enables contact-free data transmission, ensures high industrial compatibility and works reliably in the presence of contamination or through non-metallic materials. SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 273 Glossary RFID systems SIMATIC RF identification systems control and optimize material flow and production sequences. They identify reliably, quickly and economically, use non-contact data communication technology, and store data directly on the product. They are also resistant to contamination. Secondary fields The strength of the secondary fields, which exist in addition to the transmission window, is usually lower than that of the transmission window and depends on the metallic environment. Secondary fields should not be used in configuring. Static mode In static mode the transponder is positioned at a fixed distance (maximum: limit distance) exactly above the read/write device. Tag See transponder Telegram cycles The transfer of a read or write command takes place in three cycles, known as message frame cycles. 1 or 2 bytes of user data can be transferred with each command. The acknowledgement transfer (status or read data) takes place in 3 further cycles. Transmission distance Distance between communication module (read/write device) and transponder (mobile data storage unit) Transmission window Area in which reliable data exchange between transponder and read/write device is possible due to a particular minimum field strength. Transponder An invented word from transmitter and responder. Transponders are used on the product, the product carrier, the object, or its transport or packaging unit, and contain production and manufacturing data, i.e. all application-specific data. They follow the product through assembly lines, transfer and production lines and are used to control material flow. Because of their wireless design, transponders can be used, if necessary, at individual work locations or manufacturing stations, where their data can be read and updated. 274 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Index 8xIQ-Sense module Addressing, 168 Configuration, 166 Indicators, 165 Ordering data, 170 Active surface, 28 Application Planning SIMATIC RF300, 23 Approvals, 265 ASM 452 Configuration, 173 Indicators, 172 Operating mode, 174 Ordering data, 180 Pin assignments, 172 PROFIBUS address and terminating resistor, 176 PROFIBUS configuration, 173 Reader connection system, 174 ASM 456 Cable, 190 Cable assembly by the customer, 191 Cable lengths, 190 Configurations, 184 Design, 183 Dimensional drawing with ECOFAST connection block, 195 Features, 182 Field of application, 181 LED display for PROFIBUS diagnosis, 193 Ordering data, 196 PROFIBUS hardware configuration, 184 Setting PROFIBUS address, 185 Status display with LEDs, 193 Status LEDs, 192 Technical data, 194 Wiring ECOFAST connector plugs, 188 Wiring M12, 7/8" connector, 189 With connection block M12, 7/8, 195 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 ASM 473 Design and function, 197 Dimensions, 203 Features, 197 Hardware configuration, 201 Maximum configuration of an ET 200X, 201 Notes on operation, 200 Ordering data, 204 Pin assignments, 198 Reader connection system, 201 Technical specifications, 202 ASM 475 Assignment for connecting cable, 209 Cable installation, 210 Design and function, 205 Function of the LEDs, 207 Indicators, 207 Ordering data, 212 Pin assignment, 209 Status display with LEDs, 207 ASM 475 configuration Centralized configuration, 208 Decentralized design, 209 ET 200M, 209 Cabinet configuration, 80 Cable ASM 456 to reader, 190 Shielding, 85 Calculation example, 32, 36 Certificates, 265 Communication modules, 20, 163 Communication time for fault-free data transfer, 31 Configuration, 166 Connecting cable 6GT2891-0Fxxx, 190 Connecting the ASM 456 up to protective earth, 190 Contacts, 268 Conventions, 12, 20 Coupling paths, 79 Customer benefits, 19 275 Index Degree of protection IP65, IP66, IP67 M12 caps, 219 Design Centralized, 166 Distributed, 167 Diagnostic functions Readers, 259 SIMATIC RF300, 258 Transponder, 261 Diagnostics with LED display RF170C, 220 Dimension drawing RF170C with connection module, 224 Direction of motion Transponder, 28 Display elements Reader RF340R, 100 RF310R reader with RS422 interface, 94 Dwell time Transponder, 30 Dynamic mode, 29 Dwell time of the transponder, 30 Electromagnetic compatibility Coupling paths, 79 Electromagnetic interference, 77 EMC Directives Propagation of electromagnetic interference, 77 EMC Guidelines, 267 Avoiding interference, 83 Basic Rules, 75 Cabinet configuration, 80 Cable shielding, 85 Definition, 74 Equipotential bonding, 84 Overview, 73 Equipotential bonding, 84 Error codes Readers, 257 FC 45, 258 Features of ASM 452 interface module Area of application, 171 Field data Reader RF310R, 39 Reader RF340R, 40 276 Reduction due to metal, 60, 61, 62, 63, 64, 65 RF350R reader / ANT18, 40, 41 RF350R reader / ANT30, 41 RF380R reader, 42 Fields of application, 19 Flush-mounting of transponders and readers, 58 Help, 268 Indicators RF340R reader with RS422 interface, 100 Inductive alternating field, 24 Installation Several readers, 58 Installation guidelines, 57 Interface modules, 163 Interference sources Electromagnetic, 78 IQ-Sense interface Pin assignment, 88, 167 LED display RF170C, 220 LEDs For MOBY, 198 for PROFIBUS DP, 198 Main applications, 19 MDS STATUS, 258 Memory configuration of the RF300 tags, 160 Metal-free area Reader RF310R, 89, 94 Reader RF340R, 100, 119 Transponder RF320T, 127 Transponder RF340T, 131 Transponder RF350T, 135 Transponder RF360T, 139 Transponder RF370T, 144 Transponder RF380T, 152 Minimum distance Antenna to antenna, 42 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Index Reader to reader, 42 Transponder to transponder, 42 Ordering data 8xIQ-Sense module, 170 Communication module, 225 Connection module, 225 RF310R with IQ-Sense, 91 PROFIBUS cable Stripped lengths, 203 Reader RF310R, 88, 93, 105, 118 Features, 88, 93, 105, 118 Metal-free area, 89, 94 Minimum distance, 89, 95 Pin assignment of IQ-Sense interface, 88, 167 Reader RF340R, 99 Features, 99 Metal-free area, 100, 119 Readers, 87 Mounting, 58 Reducing interference due to metal, 57 Reduction of field data, 60, 61, 62, 63, 64, 65 Relationship between data transferred and speed RF310R reader with IQ-Sense interface, 44 RF310R with RS422 interface, 45 RF340R/RF350R reader, 47 RF380R reader, 52 Resistance to chemicals Transponder, 66 RF170C, 213 Accessories, 218 Area of application, 213 Configuration, 217 Connection, 218 Features, 214 LED display, 220 Status and fault LEDs, 220 with ET 200pro, 216 RF170C communication module LED display, 220 RF170C with connection module Dimension drawing, 224 RF300 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 MDS STATUS, 261 SLG STATUS, 259, 260 RF370T transponder/32 KB FRAM Technical specifications, 146 RF370T transponder/64 KB FRAM Technical specifications, 147 RFID systems Overview, 17 Safety information/instructions, 15 Secondary fields, 28 Selection criteria SIMATIC RF300 components, 23 Service, 268 Shielding, 85 SIMATIC RF300 Diagnostic functions, 258 SLG STATUS, 258 Static mode, 29 Dwell time of the transponder, 30 Status and error displays RF170C, 220 Structure System Manual, 11 Support, 268 System components Overview, 20 System diagnostics Overview, 258 Reader diagnostics functions, 259 Transponder diagnostics functions, 261 System overview RFID systems, 17 Technical data ASM 456, 194 Transponder RF320T, 128 Technical specifications RF370T transponder/32 KB FRAM, 146 RF370T transponder/64 KB FRAM, 147 Transponder RF340T, 132 Transponder RF350T, 136, 141 Transponder RF360T, 141 Time constants, 31 Tolerance of pallet side transport, 32, 37 Tolerance of pallet transport height, 32, 37 Tracking 277 Index Tolerance, 28 Tracking tolerances, 28 Training center, 269 Transmission gaps, 39 Transmission window ANT18 and ANT30 (RF350R), 26 Impact of metal, 60 Reader RF340R, 25 Reduction of field data, 60 RF310R reader and ANT1 (RF350R), 24 RF380R reader, 27 Width, 28 Transponder, 125 Active surface, 28 Directions of motion, 28 Dwell time, 30 Mounting on metal, 59 Resistance to chemicals, 66 Transponder RF320T Features, 126 Metal-free area, 127 Technical data, 128 Transponder RF340T Features, 130 Metal-free area, 131 Technical specifications, 132 Transponder RF350T Features, 134 Metal-free area, 135 Technical specifications, 136 Transponder RF360T Features, 138 Metal-free area, 139 Technical specifications, 141 Transponder RF370T Features, 143 Metal-free area, 144 Transponder RF380T Metal-free area, 152 Transponder speed, 45 User data Calculation of maximum amount of, 31 Write/read distance, 24 278 SIMATIC RF300 System Manual, 06/2008, A5E01642529-02 Get more Information www.siemens.com/simatic-sensors Siemens AG Industry Sector Postfach 48 48 90026 NĂRNBERG DEUTSCHLAND www.siemens.com/automation subject to change Š Siemens AG 2008
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.6 Linearized : No XMP Toolkit : 3.1-702 Modify Date : 2008:08:18 16:15:44+02:00 Create Date : 2008:08:18 16:15:31+02:00 Metadata Date : 2008:08:18 16:15:44+02:00 Creator Tool : Acrobat PDFMaker 7.0.7 für Word Format : application/pdf Title : SIMATIC Sensors RFID systems SIMATIC RF300 Description : System Manual Creator : I IA SE ITS POI 4 Document ID : uuid:a2860aeb-e73b-45ff-bc01-8e8b5bf5394f Instance ID : uuid:18f3a404-c19f-4419-a2a3-f303181f0327 Producer : Acrobat Distiller 7.0.5 (Windows) Page Count : 60 Subject : System Manual Author : I IA SE ITS POI 4EXIF Metadata provided by EXIF.tools