UTC Fire and Security AA3 RCR-50, RCR-PET, RCR-C User Manual 1036806B RCR50 I I P65

UTC Fire & Security B.V. RCR-50, RCR-PET, RCR-C 1036806B RCR50 I I P65

Contents

Manual 2

1PrecisionLine  RCR-50PrecisionLineļ›› RCR-50Dual Technology Motion SensorInstallation InstructionsDescriptionThe RCR detector combines range-controlled radar (RCR)technology with a passive infrared (PIR) system to increasefalse alarm immunity by allowing it to sense human-sizedobjects within a specified range. Both the RCR and PIRsystems must be triggered to set off an alarm, unless in radar-only mode.The detector is designed to use a 12VDC power supplyprovided by a UL Listed alarm control panel.Features The detector provides the following features:•High-security (radar-only) mode - Internal jumperallows you to disable the PIR, and use the radar-onlymode to detect intruders faster. This mode can be used forcovert installations (mounted behind ceiling panels orwalls).•Selectable range up to 50 feet (15.2m) - Internal jumperallows radar range selection to optimize coverage.•LED indicator - A multi-color LED provides detectorstatus.•Tamper switch - Activated when the pins on the circuitboard are removed from the terminal sockets on the base.PartsThe following parts are included:•RCR detector•1 screw to join the case halves•3 factory-installed jumpersSelecting a Location for the DetectorThe detector can be mounted in a corner or on a flat wall.Use the following guidelines to determine the best location toinstall the detector:•Mount the detector so the expected movement of anintruder is across the detection pattern. See Figure 1.•Mount the detector on a stable surface 7 to 9 feet (2.1 to2.7m) high.•DO NOT mount the detector within 2 feet (0.6m) ofmetallic objects or within 5 feet (1.5m) of florescent lights.•DO NOT place objects in front of the detector that mayprevent a clear line of sight. (Not applicable in radar-onlymode.)•Avoid locations that expose the detector to possible falsealarm sources such as:– Moving or vibrating objects (fans, pulleys, conveyor belts)– Electronic fields (electric motors, high voltage equipment)– Water spray or corrosive environments– Heat sources in the field of view (heaters, radiators)– Windows in the field of view– Strong air drafts on the detector (fans, air conditioners)•When installing multiple detectors:– DO NOT mount detectors facing each other.– Mount detectors at least 20 feet (6.1m) apart.– Use shorter range settings to avoid overlapping radarcoverage.– Mounting detectors back to back is not recommended, butif an application requires such mounting, use the 20-foot(6.1m) range and walk test the installation to ensure properoperation.SPR TMPR TMPR NO COMFigure 2.  Detector (Exploded)Radar Viewing AreaPIR Viewing AreaFigure 1. Coverage Patterns90°Top ViewSide View50’(15.2m)40’(12.2m)30’(9.1m)20’(6.1m)floor line0’50’(15.2m)40’(12.2m)30’(9.1m)20’(6.1m)60°30°15°4°0°7’2.1m
2PrecisionLine  RCR-50Installing the DetectorAll wiring must conform to the National Electric Code (NEC)and/or local codes having jurisdiction.Important: DO NOT use this device for safetyinterlock applications.To install the detector:1. Run the security system wiring to the detector location.2. To remove the front cover/electronic module, remove thenameplate and loosen the screw if necessary. To removethe nameplate, insert a small screwdriver into one of thenameplate side slots and gently push in and pry up withthe screwdriver. See Figure 2. Then press down on thetop of the front cover with one hand, while holding thesides at the top of the back cover and squeezing in andpulling back with the other hand.CAUTIONYou must be free of all static electricity beforehandling sensor circuit boards. Touch agrounded, bare metal surface before touchingcircuit boards or wear a grounding strap.3. If necessary, set the jumpers on the circuit board. SeeSetting the Jumpers.4. Remove the appropriate wiring and mounting knockoutsfrom the back cover. The detector can be mounted on aflat wall or in a corner. See Figure 3.5. Pull the wires through the knockout holes and use screwsto attach the base to the wall. Use screw anchors ifnecessary.6. Strip 1/4 inch (6.4mm) of insulation from each wire.7. Run each wire through the strain relief and under theappropriate screw terminals on the base and tighten thescrews. See Figure 3.8. Line up the tabs on the bottom of the cover/electronicmodule with the corresponding tabs on bottom of thebase and snap the cover/electronic module firmly downonto the base.9. Tighten the screw and replace the nameplate. SeeFigure 2.10. Apply power. The green LED should light for approxi-mately 25 seconds and then go out.11. Walk test the coverage pattern as follows:– Walk throughout the intended coverage area.– Verify the detector alarms. See Understanding the LED.NoteMost units walk test more accurately if the persontesting waits 10 seconds between tripping the unit andwalking again. This allows the detector to stabilizebetween trips. Figure 4. Main Circuit BoardFigure 3. Detector BaseTerminalsocketsFlatwall-mountknockoutCorner-mountknockoutsStrain reliefWiring knockoutFlat-wall mountknockoutWireCorner-mountknockoutsJ4J3J2LED DisableRadaronlyRange
3PrecisionLine  RCR-50NoteYou need to set J2 as close to the intendedcoverage range as possible. Overshooting thecoverage area may cause false alarms.J3 LED -ON = LED enabled (factory default)OFF = LED disabledJ4 PIR -ON = Radar only enabledOFF = PIR and Radar enabled(factory default)Maintaining the DetectorWhen installed and used properly, the detector provides manyyears of service with minimal maintenance. You should walktest the detector annually to ensure proper operation.Clean the inside of the unit with a soft-bristled brush orcompressed air. Clean the outside with a damp (water) clothas needed to keep it free of dust and dirt. Always test theunit after cleaning.When the cover is removed, power is interrupted to thesensor. Once the cover has been replaced, the green LED willilluminate for 25 seconds while the sensor warms up. Afterthe green LED goes off, wait one minute and walk test thesensor.Understanding the LEDThe multi-color LED located on the bottom of the detectorindicates the status of the unit as described in the followingtable.SB01 Swivel-Mount BracketFor ceiling-mount applications that require 90 degreecoverage, an optional swivel-mount bracket (SB01) isavailable from GE Security. See Figure 5.Figure 5.  SBO1 Swivel-Mount BracketSetting the JumpersThe detector provides jumpers to select the detection rangeand PIR and LED operation. See Figure 4.J2 Range - Use the jumper to cover the center pin and thepin indicating the desired range. No jumper = 50 feet (15.2m)and under.50 feet (15.2m) and under       40 feet (12.2m) and under(factory default)30 feet (9.1m) and under 20 feet (6.1m) and underIn Radar-only mode:LED StatusRed Radar detection.50’(15.2m) 50’15.2m)20’(6.1m)20’(6.1m)40’(12.2m) 40’(12.2m)30’(9.1m) 30’(9.1m)50’(15.2m) 50’(15.2m)20’(6.1m) 20’(6.1m)40’(12.2m) 40’(12.2m)30’(9.1m) 30’(9.1m)LED StatusRed PIR and Radar detection. The detector isin alarm and the relay has switched.Green PIR detection only (no alarm).Yellow Radar detection only (no alarm).
SpecificationsInput voltage 8.5 to 18VDC (UL: 10 to 16VDC)Typical current 27mAMaximum current 35mAElectrical configuration Form CRelay rating 28VDC, 100mA max.Tamper 100ma, 40VDCDetection range 50' (15.2m) x 90°Target velocity 0.5 ft/sec to 5 ft/secAlarm duration 5 sec ± 10%Mounting height 7' to 9' (2.1m to 2.7m)Operating temperature 32° F to 122° F (0° C to 50° C)Relative humidity 5 to 93% non-condensingDimensions: 2.8" (7.1cm) W5.1" (13cm) H2.3" (5.7cm) DWeight 6 oz (170g)Color whiteField wiring size 12-24 AWGMicrowave frequency 5.8GHzListing C-UL USFCC ComplianceThis device complies with Part 15 of the FCC rules.Operation is subject to the following three conditions:(1) This device may not cause harmful interference.(2) This device must accept any interference received,including interference that may cause undesiredoperation.(3) Changes or modifications not expressly approvedby the party responsible for complicance could voidthe user’s authority to operate the equipment.FCC ID: CGGAA3Product OrderingModel Number DescriptionRCR-50 Range-controlled radar, passive infrared detector with form C relay, stealth mode,tamper contacts, 50 foot (15.2m) maximum rangeAccessoriesSB01 Swivel-mount bracket1036806 Rev B  04/04Tech Support800-648-7424FaxBack: 800-483-2495www.ge-security.comGE Security12345 SW Leveton DriveTualatin, OR 97062503-692-4052USA & Canada: 800-547-2556GE Security g

Navigation menu