Nokia Solutions and Networks T5EJ1 1X SC480 BTS Microcell Base Station Transmitter User Manual print instructions

Nokia Solutions and Networks 1X SC480 BTS Microcell Base Station Transmitter print instructions

User Manual Part 4

Basic Troubleshooting MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  11-1PRELIMINARYOverviewThe information in this chapter addresses some of the scenarios likely tobe encountered by Customer Field Engineering (CFE) team memberswhile performing BTS optimization and acceptance testing. Thistroubleshooting guide was created as an interim reference document foruse in the field. It provides “what to do if” basic troubleshootingsuggestions when the BTS equipment does not perform according to theprocedures documented in the manual.Comments are consolidated from inputs provided by CFEs andinformation gained from experience in Motorola labs and classrooms.Table 11-1: Login Failure Troubleshooting ProceduresStep Action1If the GLI LED is solid RED, it implies a hardware failure. Reset GLI by re-seating it. If this persists,install GLI card in GLI slot and retry. A Red LED may also indicate no termination on an externalLAN connector (power entry compartment at rear of frame).2Verify that the span line is disconnected at the Span I/O card. If the span is still connected, verify theCBSC has disabled the BTS.3Try to ‘ping’ the GLI.4Verify the LMF is connected to the primary LAN (LAN A) at the LAN shelf below the CCP2 cage. IfLAN A is not the active LAN, force a LAN switch to LAN A by following the procedure inTable 11-2.5Verify the LMF was configured properly.6If a Xircom parallel BNC LAN interface is being used, verify the BTS-LMF cable is RG-58 (flexibleblack cable less than 2.5 feet in length).7Verify the external LAN connectors are properly terminated (power entry compartment at rear offrame).8Verify a T-adapter is not used on LMF computer side connector when connected to the primary LANat the LAN shelf.9Try connecting to the Ethernet Out port in the power entry compartment (rear of frame). Use aTRB–to–BNC (triax–to–coax) adapter at the LAN connector for this connection.10 Re-boot the LMF and retry.11 Re-seat the GLI and retry12 Verify GLI IP addresses are configured properly by following the procedure in Table 11-3.  11
Basic Troubleshooting   – continued 11-2 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable 11-2: Force Ethernet LAN A to Active State as Primary LANStep Action1If LAN A is not the active LAN, make certain all external LAN connectors are either terminated with50Ω loads or cabled to another frame.2If it has not already been done, connect the LMF computer to the stand–alone or starter frame, asapplicable (Table 6-6).3If it has not already been done, start a GUI LMF session and log into the BTS on the active LAN(Table 6-7).4Remove the 50Ω termination from the LAN B IN connector in the power entry compartment at therear of the stand–alone or starter frame. The LMF session will become inactive.5Disconnect the LMF computer from the LAN shelf LAN B connector and connect it to the LAN Aconnector.6If the LAN was successfully forced to an active state (the cards in any cage can be selected andstatused), proceed to step 13.7With the 50Ω termination still removed from the LAN B IN connector, remove the 50Ω terminationfrom LAN B OUT connector. If more than one frame is connected to the LAN, remove the terminationfrom the last frame in the chain.8If the LAN was successfully forced to an active state (the cards in any cage can be selected andstatused), proceed to step 13.9With the 50Ω terminations still removed from LAN B, unseat each GLI card in each frame connectedto the LAN, until all are disconnected from the shelf backplanes.10 Reseat each GLI card until all are reconnected.11 Allow the GLIs to power up, and attempt to select and status cards in the CCP shelves. If LAN A isactive, proceed to step 13.12 If LAN A is still not active, troubleshoot or continue troubleshooting following the procedures in 13.13 Replace the 50Ω terminations removed from the LAN B IN and OUT connectors.  11
Basic Troubleshooting   – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  11-3PRELIMINARYTable 11-3: GLI IP Address SettingStep Action1If it has not previously been done, establish an MMI communication session with the GLI card asdescribed in Table 6-11.2Enter the following command to display the IP address and subnet mask settings for the card:config lg0 currentA response similar to the following will be displayed:GLI3>config lg0 currentlg0: IP address is set to DEFAULT (configured based on card location)lg0: netmask is set to DEFAULT (255.255.255.128)3If the IP address setting response shows an IP address rather than “Default (configured basedon card location),” enter the following:config lg0 ip defaultA response similar to the following will be displayed:GLI3>config lg0 ip default_param_config_lg0_ip(): param_delete(): 0x00050001lg0: ip address set to DEFAULT4If the GLI subnet mask setting does not display as “DEFAULT (255.255.255.128),” set it todefault by entering the following command:config lg0 netmask defaultA response similar to the following will be displayed:GLI3>config lg0 netmask default_param_config_lg0_netmask(): param_delete(): 0x00050001lg0: netmask set to DEFAULT table continued on next page11
Basic Troubleshooting   – continued 11-4 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable 11-3: GLI IP Address SettingStep Action5Set the GLI route default to default by entering the following command:config route default defaultA response similar to the following will be displayed:GLI3>config route default default_esh_config_route_default(): param_delete(): 0x00050001route: default gateway set to DEFAULTNOTEChanges to the settings will not take effect unless the GLI is reset.6When changes are completed, close the MMI session, and reset the GLI card.7Once the GLI is reset, re–establish MMI communication with it and issue the following command toconfirm its IP address and subnet mask settings:config lg0 currentA response similar to the following will be displayed:GLI3>config lg0 currentlg0: IP address is set to DEFAULT (configured based on card location)lg0: netmask is set to DEFAULT (255.255.255.128)  11
Basic Troubleshooting   – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  11-5PRELIMINARYCannot Communicate withPower MeterTable 11-4: Troubleshooting a Power Meter Communication FailureStep Action1Verify power meter is connected to LMF with GPIB adapter.2Verify cable connections as specified in Chapter 4.3Verify the GPIB address of the power meter is set to the same value displayed in the applicable GPIBaddress box of the LMF Options window Test Equipment tab. Refer to Table 6-23 or Table 6-24 andthe Setting GPIB Addresses section of Appendix B for details.4Verify the GPIB adapter DIP switch settings are correct. Refer to Test Equipment Preparation sectionof Appendix F for details.5Verify the GPIB adapter is not locked up. Under normal conditions, only 2 green LEDs must be ‘ON’(Power and Ready). If any other LED is continuously ‘ON’, then cycle GPIB box power and retry.6Verify the LMF computer COM1 port is not used by another application; for example, if aHyperTerminal window is open for MMI, close it.7 Reset all test equipment by clicking Util in the BTS menu bar and selecting Test Equipment > Resetfrom the pull–down lists.  Cannot Communicate withCommunications SystemAnalyzerTable 11-5: Troubleshooting a Communications System Analyzer Communication FailureStep Action1Verify analyzer is connected to LMF with GPIB adapter.2Verify cable connections as specified in Chapter 4.3Verify the analyzer GPIB address is set to the same value displayed in the applicable GPIB addressbox of the LMF Options window Test Equipment tab. Refer to Table 6-23 or Table 6-24 and theSetting GPIB Addresses section of Appendix B for details.4Verify the GPIB adapter DIP switch settings are correct. Refer to Test Equipment Preparation sectionof Appendix F for details.5Verify the GPIB adapter is not locked up. Under normal conditions, only 2 green LEDs must be ‘ON’(Power and Ready). If any other LED is continuously ‘ON’, then cycle GPIB box power and retry.6Verify the LMF computer COM1 port is not used by another application; for example, if aHyperTerminal window is open for MMI, close it.7 Reset all test equipment by clicking Util in the BTS menu bar and selecting Test Equipment > Resetfrom the pull–down lists.  11
Basic Troubleshooting   – continued 11-6 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYCannot Communicate withSignal GeneratorTable 11-6: Troubleshooting a Signal Generator Communication FailureStep Action1Verify signal generator is connected to LMF with GPIB adapter.2Verify cable connections as specified in Chapter 4.3Verify the signal generator GPIB address is set to the same value displayed in the applicable GPIBaddress box of the LMF Options window Test Equipment tab. Refer to Table 6-23 or Table 6-24 andthe Setting GPIB Addresses section of Appendix B for details.4Verify the GPIB adapter DIP switch settings are correct. Refer to Test Equipment Preparation sectionof Appendix F for details.5Verify the GPIB adapter is not locked up. Under normal conditions, only 2 green LEDs must be ‘ON’(Power and Ready). If any other LED is continuously ‘ON’, then cycle GPIB box power and retry.6Verify the LMF computer COM1 port is not used by another application; for example, if aHyperTerminal window is open for MMI, close it.7 Reset all test equipment by clicking Util in the BTS menu bar and selecting Test Equipment > Resetfrom the pull–down lists.  Cannot DownloadTable 11-7: Troubleshooting Code Download FailureStep Action1Verify T1 or E1 span is disconnected from the BTS.2Verify LMF can communicate with the BTS devices using the LMF Status function.3Communication with GLI must first be established before trying to communicate with any other BTSdevice. GLI must be INS_ACT state (bright green).4Verify the target card is physically present in the cage and powered-up.5If the target card LED is solid RED, it implies hardware failure. Reset card by re-seating it. If LEDalarm persists, replace with same type of card from another slot and retry.6Re-seat card and try again.7If a BBX reports a failure message and is OOS_RAM, the code load was OK. Use the LMF Statusfunction to verify the load.8If the download portion completes and the reset portion fails, reset the device by selecting the deviceand Reset. table continued on next page11
Basic Troubleshooting   – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  11-7PRELIMINARYTable 11-7: Troubleshooting Code Download FailureStep Action9If a BBX or an MCC remains OOS_ROM (blue) after code download, use the LMF Device > Statusfunction to verify that the code load was accepted.10 If the code load was accepted, use LMF Device > Download > Flash to load RAM code into flashmemory.  Cannot Download DATA to AnyDevice (Card)Table 11-8: Troubleshooting Data Download FailureStep Action1Re-seat card and repeat code and data load procedure.2Verify the ROM and RAM code loads are of the same release by statusing the card. Refer to Downloadthe BTS section of Chapter 6 for more information.  Cannot ENABLE DeviceBefore a device can be enabled (placed in service), it must be in theOOS_RAM state (yellow in LMF display) with data downloaded to thedevice. The color of the device on the LMF changes to green once it isenabled.The four device states that can be displayed by the LMF are:SEnabled (bright green, INS_ACT)SStand–by (olive green, INS_SBY – redundant CSM and GLI only)SDisabled (yellow, OOS_RAM)SReset (blue, OOS_ROM)Table 11-9: Troubleshooting Device Enable (INS) FailureStep Action1Re-seat card and repeat code and data load procedure.2If CSA cannot be enabled, verify the CDF has correct latitude and longitude data for cell site locationand GPS sync.3Ensure primary CSM is in INS_ACT (bright green) state.NOTEMCCs will not enable without the CSA being INS.4Verify 19.6608 MHz CSA clock is present; MCCs will not enable without it. table continued on next page11
Basic Troubleshooting   – continued 11-8 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable 11-9: Troubleshooting Device Enable (INS) FailureStep Action5BBXs should not be enabled for ATP tests.6If MCCs give “invalid or no system time,” verify the CSA is enabled.7Log out of the BTS, exit the LMF, restart the application, log into the BTS, and re–attemptdevice–enable actions.  cCLPA ErrorsTable 11-10: cCLPA ErrorsStep Action1If cCLPAs give continuous alarms, cycle power with the applicable DC PDA circuit breakers.2Establish an MMI session with the cCLPA (Table 6-11), connecting the cable to the applicable MMIport.2a – Type alarms at the HyperTerminal window prompt and press Enter.–– The resulting display may provide an indication of the problem.2b – Call Field Support for further assistance.  11
MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYAppendix A: MCC–Data Only Appendix ContentMCC–DO Tests A-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MCC–DO Testing A-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Prerequisites A-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Test Equipment A-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MCC–DO Code Domain A-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MCC–DO TX Mask A-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MCC–DO Pilot Time Offset A-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MCC–DO Rho A-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MCC–DO Packet Error Rate A-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PER Prerequisites A-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A
Table of Contents  – continued1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesA
MCC–DO TestsMAY 2004 A-11X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYMCC–DO TestingThe tests in this appendix are provided for informationonly. The tests contained herein are not proven, andrecommended equipment and equipment setup is notprovided.IMPORTANT*The following acceptance tests evaluate different performance aspects ofthe BTS with MCC–DO. This allows the CFE to select testing to meetthe specific requirements for individual maintenance and performanceverification situations.The WinLMF must be version 2.16.4.0.04 or higher (with FR8000 –EV–DO manual ATP test support).PrerequisitesBefore attempting to run any performance verification ATP tests,  allprocedures outlined in  previous Optimization chapters should have beensuccessfully completed. At a minimum, successful completion of allBTS BLO calibration, and Bay Level Offset tests is recommended.Test EquipmentListed below are the recommended test equipment required to testMCC–DO.Signal Generator:SAgilent E4432B, with options UN8/(008 for upgrade) and 201/(251for upgrade)SE4430BK–404 – CDMA2000–1xEV–DO signal studio softwareORS Agilent E4438C, with options UN8/(008 for upgrade) and 201/(251for upgrade)SE4438CK–404 – CDMA2000–1xEV–DO signal studio softwareSpectrum Analyzer:SAgilent E4406A), with option B78 and Firmware version A.04.21SE4406AU–204 – 1xEV–DO measurement personalityMCC–DO Code DomainThe code domain power test verifies the noise floor of a carrier keyed upat a specific frequency per the CDF file.Code domain power is the power in each code channel of a CDMAChannel. The CDMA time reference used in the code domain power testis derived from the Pilot Channel and is used as the reference fordemodulation of all other code channels. This test verifies thatorthogonality is maintained between the code channels. When transmitdiversity is enabled, this test also verifies that time alignment is alsomaintained.A
MCC–DO Tests – continuedPRELIMINARY1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004A-2Follow the procedure in Table A-1 to test the MCC–DO Code DomainPower.Table A-1: Procedure to Test MCC–DO Code Domain PowerStep Action1Click the BBX(s) on DO carrier to be tested.2On the menu, click the EvDO Tests > TX>Start Manual Tx ATP.3Select the appropriate carrier from the Sector/Carrier list.4Click the OK button.A status report window is displayed.5Test tesults are displayed in the window.6Connect an MMI cable to the MCC–DO card.7Open a HyperTerminal application.8Open the COM to the MCC–DO MMI. Set parameters as follows:SBits per second:  9600SData bits:  8SParity:  NoneSStop bits:  1SFlow control:  None9When the login prompt appears, enter login mmi.10 When MMI> appears, type in the following command:set_sc <modem number> <sector number> <channel> <PN offset>where:S<modem number> is the modem on MCC–DO card to be testedS<sector number> is the sector number of the appropriate BBX (according to carrier selected inLMF)S<channel> is the appropriate channel (according to carrier selected in LMF) in the hexadecimalformat 0xHHHH or NNNN format (normal decimal)S<PN offset> is set to 0 (zero)11 Enable the modem on MCC–DO card by entering the following command:enable <modem number>where:S<modem number> is the modem selected in step 10. table continued on next pageA
MCC–DO Tests – continuedMAY 2004 A-31X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYTable A-1: Procedure to Test MCC–DO Code Domain PowerStep Action12 To generate a pattern, enter the following command:fl_pattern 313 On the Agilent E4406, set the Code Domain:SPress Measure buttonSPress More button until Code Domain option is displayedSSelect Code DomainSPress Meas Setup button, then press Meas Interval, enter 3.SPress Meas Control button, then press Measure to set it to ContSPress Meas Control buttonSSet Channel Type to MACSPress More button until Trig Source option is displayedSPress Trig Source key and select Ext Rear optionSPress More button until Advanced option is displayedSSelect Advanced optionSIf Chip Rate option is set to a value different than 1.228800, select Chip Rate and set it to1.228800SSelect Active Set Th option to a value calculated using the following formula:–xcvr_gain – cable_loss – 2dBSPress Display button and set the I/Q Combined Power Bar to OnSPress Display button, press Code Order button, select Hadamard optionSTo set appropriate frequency value,  press Frequency and enter the value calculated according to thefollowing formula:–<tx_base_band_value> + 0.05*<chan_no> [MHz]14 Read the value of the power for each MAC channel.15 Note the Max Inactive Ch value. The Max Inactive Ch value is –31dB or lower.  A
MCC–DO Tests – continuedPRELIMINARY1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004A-4MCC–DO TX MaskFollow the procedure in Table A-2 to test the MCC–DO TX Mask.Table A-2:Procedure to Test the MCC–DO TX MaskStep Action1Click the BBX(s) on DO carrier to be tested.2On the menu, click the EvDO Tests > TX>Start Manual Tx ATP.3Select the appropriate carrier from the Sector/Carrier list.4Click the OK button.A status report window is displayed.5Connect test equipment as the instructions are displayed.6Connect an MMI cable to the MCC–DO card.7Open a HyperTerminal application.8Open the COM to the MCC–DO MMI. Set parameters as follows:SBits per second:  9600SData bits:  8SParity:  NoneSStop bits:  1SFlow control:  None9When the login prompt appears, enter login mmi.10 When MMI> appears, type in the following command:set_sc <modem number> <sector number> <channel> <PN offset>where:S<modem number> is the modem on MCC–DO card to be testedS<sector number> is the sector number of the appropriate BBX (according to carrier selected inLMF)S<channel> is the appropriate channel (according to carrier selected in LMF) in the hexadecimalformat 0xHHHH or NNNN format (normal decimal).S<PN offset> is set to 0 (zero)11 Enable the modem on MCC–DO card by entering the following command:enable <modem number>where:S<modem number> is the modem selected in step 10. table continued on next pageA
MCC–DO Tests – continuedMAY 2004 A-51X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYTable A-2:Procedure to Test the MCC–DO TX MaskStep Action12 To generate a pattern, enter the following command:fl_pattern 313 On Agilent E4406, set Spectrum (Freq Domain) measurement as follows:SPress Measure buttonSPress More button until Spectrum (Freq Domain) option is displayedSSelect Spectrum optionSPress SPAN key to set its value to 4 [MHz]STo set the frequency value. press Frequency and enter the value calculated as follows:–<tx_base_band_value> + 0.05*<chan_no> [MHz]14 Use the formula from step 13 to calculate the four frequencies to measure the Power.Scheck_point_1 = freq – 750 [kHz]Scheck_point_2 = freq +  750[kHz]Scheck_point_3 = freq – 1980 [kHz]Scheck_point_4 = freq + 1980 [kHz]15 Press MARKER key:SSelect 1, 2, 3, or 4 (frequency points)SPress FUNCTION key and select Off optionSPress TRACE key and select Spectrum optionSPress NORMAL keySUse the numeric keypad to enter the calculated frequency, assigning the proper unit.SNote the Power value of markerSRepeat step for all calculated frequency checkpointsThe check point values are as follows:SCheck_point_1  > –40 dBmSCheck_point_2  > –40 dBmSCheck_point_3  > –60 dBmSCheck_ point_4  > –60 dBm  A
MCC–DO Tests – continuedPRELIMINARY1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004A-6MCC–DO Pilot Time OffsetThe pilot time offset test verifies the transmitted pilot channel elementpilot time offset of a carrier keyed up at a specific frequency per the CDFfile.The calibrated communications test set measures the pilot time offset inmicroseconds, verifying that the result is within 3 microseconds (10microseconds for JCDMA systems) of the target pilot time offset (zeromicroseconds).Pilot time is defined as the estimate of CDMA System Time derivedfrom observation of the pilot signal at the base station RF output port.Pilot time alignment error is the difference between the measured pilottime and the expected time, taking into account CDMA System Timeand pilot offset.Follow the procedure in Table A-3 to test the MCC–DO Pilot TimeOffset.Table A-3: Procedure to Test MCC–DO Pilot Time OffsetStep Action1Click the BBX(s) on DO carrier to be tested.2On the menu, click the EvDO Tests > TX>Start Manual Tx ATP.3Select the appropriate carrier from the Sector/Carrier list.4Click the OK button.A status report window is displayed.  Test results are displayed in the window.5Connect an MMI cable to the MCC–DO card.6Open a HyperTerminal application.7Open the COM to the MCC–DO MMI. Set parameters as follows:SBits per second:  9600SData bits:  8SParity:  NoneSStop bits:  1SFlow control:  None8When the login prompt appears, enter login mmi. table continued on next pageA
MCC–DO Tests – continuedMAY 2004 A-71X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYTable A-3: Procedure to Test MCC–DO Pilot Time OffsetStep Action9 When MMI> appears, type in the following command:set_sc <modem number> <sector number> <channel> <PN offset>where:S<modem number> is the modem on MCC–DO card to be testedS<sector number> is the sector number of the appropriate BBX (according to carrier selected inLMF)S<channel> is the appropriate channel (according to carrier selected in LMF) in the hexadecimalformat 0xHHHH or NNNN format (normal decimal).S<PN offset> is set to 0 (zero)10 Enable the modem on MCC–DO card by entering the following command:enable <modem number>where:S<modem number> is the modem selected in step 10.11 To generate a pattern, enter the following command:fl_pattern 312 On the Agilent E4406, set the Mod Accuracy (composite Rho) measurement:SPress Measure buttonSPress More button until Mod Accuracy (composite Rho) option is displayedSSelect Mod Accuracy (composite Rho)SPress Meas Setup buttonSPress More button until Trig Source option is displayedSPress Trig Source key and select Ext Rear optionSPress More button until Advanced option is displayedSSelect Advanced optionSIf Chip Rate option is set to a value different than 1.228800, select Chip Rate and set it to1.228800SSelect Active Set Th option to a value calculated using the following formula:–xcvr_gain – cable_loss – 2dBSTo set appropriate frequency value,  press Frequency and enter the value calculated according to thefollowing formula:–<tx_base_band_value> + 0.05*<chan_no> [MHz]13 Read the value of thePilot Offset. The Pilot Offset is less than 3 microseconds  A
MCC–DO Tests – continuedPRELIMINARY1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004A-8MCC–DO RhoThe Rho test verifies the transmitted pilot channel element digitalwaveform quality of the carrier keyed up at a specific frequency per theCDF file.Waveform quality is measured by determining the normalized correlatedpower between the actual waveform and the ideal waveform. Follow the procedure in Table A-4 to test the MCC–DO Rho.Table A-4: Procedure to Test MCC–DO RhoStep Action1Click the BBX(s) on DO carrier to be tested.2On the menu, click the EvDO Tests > TX>Start Manual Tx ATP.3Select the appropriate carrier from the Sector/Carrier list.4Click the OK button.A status report window is displayed.  Test results are displayed in the window.5Connect an MMI cable to the MCC–DO card.6Open a HyperTerminal application.7Open the COM to the MCC–DO MMI. Set parameters as follows:SBits per second:  9600SData bits:  8SParity:  NoneSStop bits:  1SFlow control:  None8When the login prompt appears, enter login mmi.9 When MMI> appears, type in the following command:set_sc <modem number> <sector number> <channel> <PN offset>where:S<modem number> is the modem on MCC–DO card to be testedS<sector number> is the sector number of the appropriate BBX (according to carrier selected inLMF)S<channel> is the appropriate channel (according to carrier selected in LMF) in the hexadecimalformat 0xHHHH or NNNN format (normal decimal).S<PN offset> is set to 0 (zero) table continued on next pageA
MCC–DO Tests – continuedMAY 2004 A-91X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYTable A-4: Procedure to Test MCC–DO RhoStep Action10 Enable the modem on MCC–DO card by entering the following command:enable <modem number>where:S<modem number> is the modem selected in step 10.11 To generate a pattern, enter the following command:fl_pattern 312 On the Agilent E4406, set the Mod Accuracy (composite Rho) measurement:SPress Measure buttonSPress More button until Mod Accuracy (composite Rho) option is displayedSSelect Mod Accuracy (composite Rho)SPress Meas Setup buttonSPress More button until Trig Source option is displayedSPress Trig Source key and select Ext Rear optionSPress More button until Advanced option is displayedSSelect Advanced optionSIf Chip Rate option is set to a value different than 1.228800, select Chip Rate and set it to1.228800SSelect Active Set Th option to a value calculated using the following formula:–xcvr_gain – cable_loss – 2dBSTo set appropriate frequency value,  press Frequency and enter the value calculated according to thefollowing formula:–<tx_base_band_value> + 0.05*<chan_no> [MHz]13 Read the value of the Rho. Rho normalized cross coefficient ( ò ) is greater than 0.912  MCC–DO Packet Error RateThe PER test verifies PER (Packet Error Rate) of traffic channels of anXCVR carrier keyed up at a specific frequency per the current CDF file.The XCVR is keyed to generate a CDMA carrier (with pilot channelelement only) of the correct level.The calibrated communications test set measures the all zero long codeand verifies that the PER is not greater than 1 percent. A total number ofpackets to be received is dependent on Rate Set chosen.PER PrerequisitesTo perform the following test, the Agilent E4432B Signal Generatormust have the following installed:A
MCC–DO Tests – continuedPRELIMINARY1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004A-10SAgilent Signal Studio – 1xEV Reverse Link” (requires installation of”Agilent IO Libraries” application)SAgilent E4432B Signal Generator with option 404Follow the procedure in Table A-5 to test the MCC–DO Packet ErrorRate.Table A-5: Procedure to Test MCC–DO Packet Error RateStep Action1Click the BBX(s) on DO carrier to be tested.2On the menu, click the EvDO Tests > TX>Start Manual Tx ATP.3Select the appropriate carrier from the Sector/Carrier list.4Click the OK button.A status report window is displayed.  Test results are displayed in the window.5Connect the lap top computer to the Agilent E4432B Signal Generator and run the Agilent SignalStudio – 1x EV Reverse Link application. table continued on next pageA
MCC–DO Tests – continuedMAY 2004 A-111X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYTable A-5: Procedure to Test MCC–DO Packet Error RateStep Action6Enter the following parameters for signal generation.Channel Configuration:SRRI Channel – checked     RRI Bits – 1SDRC Channel – checked   Rel. gain (dB) – 3SACK Channel – checked   Rel. gain (dB) – 0SData Channel – checked    Rel. gain (dB) – 3.75SData Channel encoder active – checkedSData Channel Data rate – 9.6 kbpsSData Channel bit stream – PN15SI Mask  – 3FF80000000SQ Mask – 3FF00000001 Signal Generation:SOversampling ratio – 4SFilter Type – IS 95 StdSMirror Spectrum – uncheckedESG Configuration:SFrequency – calculated according to the formula: <rx_base_band_value> + 0,05 * <chan_no>[MHz]SAmplitude – depending on attenuation applied – overall signal value should be –122 [dBm]SSampling rate 4.1952 [MHz]SReconstruction filter 2.5 [MHz]SRF Blanking – uncheckedSInternal ReferenceS+ Mkrs7 Press Time Slot Setup button and set the following parameters:ACK ChannelSActive – All OnSData – 0sDRC ChannelSActive – All OnSData – F (1111)SCover – 18 Press DOWNLOAD button on the ”Agilent Signal Studio – 1xEV Reverse Link” application. table continued on next pageA
MCC–DO Tests – continuedPRELIMINARY1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004A-12Table A-5: Procedure to Test MCC–DO Packet Error RateStep Action9Connect an MMI cable to the MCC–DO card.10 Open a HyperTerminal application.11 Open the COM to the MCC–DO MMI. Set parameters as follows:SBits per second:  9600SData bits:  8SParity:  NoneSStop bits:  1SFlow control:  None12 When the login prompt appears, enter login mmi.13 When MMI> appears, type in the following command:set_sc <modem number> <sector number> <channel> <PN offset>where:S<modem number> is the modem on MCC–DO card to be testedS<sector number> is the sector number of the appropriate BBX (according to carrier selected inLMF)S<channel> is the appropriate channel (according to carrier selected in LMF) in the hexadecimalformat 0xHHHH or NNNN format (normal decimal).S<PN offset> is set to 0 (zero) table continued on next pageA
MCC–DO Tests – continuedMAY 2004 A-131X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYTable A-5: Procedure to Test MCC–DO Packet Error RateStep Action14 Enter the command to receive the PER measurements results:rl_test 1 60 dflt dflt dflt dflt dflt dflt dflt dflt dflt dflt dflt dflt dflt dfltthis will set the MCC–DO to measure the PER with following parameters:SPerform PER Test at 9.6 KBPSSDuration 60 secondsSDataOffsetNominal dflt=0dBSDataOffset9k6 dflt=0dBSDataOffset19k2 dflt=0dBSDataOffset38k4 dflt=0dBSDataOffset76k8 dflt=0dBSDataOffset153k6 dflt=0dBSMacIndex dflt=5SFrameOffset dflt=0SDRCGating dflt=0 Continuous transmissionSDRCLength dflt = 0SDRCCover dflt = 1SUATI dflt = 0x1234ABCDSAckChannelGain dflt=0dBSDRCChannelGain dflt=3dB 15 Read the results (after 1 minute) and calculate the PER value from the MCC–DO mmi result screen:Compute PER using the outcome of the rl_testPER = (expect–total+invalid) /expectExample output:Reverse Link Test has completedReverse Link Test OK MODEM#1pattern = 1 (9.6 kbps)expect = xxxtotal  = xxxinvalid = xxx16 Receiver sensitivity is below –121.2 dBm at a signal rate of 9.6 kbps.Read the value of the PER. PER is less than 0.01 (1%)  A
MCC–DO Tests – continuedPRELIMINARY1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004A-14NotesA
MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYAppendix B: Test Equipment Preparation Appendix ContentTest Equipment Preparation B-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Purpose B-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Agilent R7495A Test Equipment Setup B-2 . . . . . . . . . . . . . . . . . . . . . . . . Verifying and Setting GPIB Addresses B-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Agilent E4406A Transmitter Tester GPIB Address B-5 . . . . . . . . . . . . . . . . Agilent E4432B Signal Generator GPIB Address B-6 . . . . . . . . . . . . . . . . . Advantest R3267 Spectrum Analyzer GPIB Address B-7 . . . . . . . . . . . . . . Advantest R3562 Signal Generator GPIB Address B-9 . . . . . . . . . . . . . . . . Agilent 8935 Series E6380 (formerly HP 8935) Test Set GPIB Address B-9 Hewlett Packard HP8921A and HP83236A/B GPIB Address B-11 . . . . . . . Advantest R3465 Communications Test Set GPIB Address B-12 . . . . . . . . . Motorola CyberTest GPIB Address B-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . HP 437 Power Meter GPIB Address B-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . Gigatronics 8541C Power Meter GPIB Address B-15 . . . . . . . . . . . . . . . . . . RS232 GPIB Interface Adapter B-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Test Equipment Connection, Testing, and Control B-17 . . . . . . . . . . . . . . . . . . . . . . . Inter–unit Connection, Testing, and Control Settings B-17 . . . . . . . . . . . . . . HP 8921A with PCS Interface Test Equipment Connections B-17 . . . . . . . . HP 8921A with PCS Interface System Connectivity Test B-21 . . . . . . . . . . . Pretest Setup for HP 8921A B-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pretest Setup for Agilent 8935 B-22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Advantest R3465 Connection B-22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . R3465 GPIB Clock Set–up B-24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pretest Setup for Advantest R3465 B-25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Agilent 8932/E4432B Test Equipment Interconnection B-25 . . . . . . . . . . . . Agilent E4406A/E4432B Test Equipment Interconnection B-26 . . . . . . . . . Advantest R3267/R3562 Test Equipment Interconnection B-27 . . . . . . . . . . Equipment Calibration B-28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Calibration Without the LMF B-28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Agilent E4406A Transmitter Tester Self–alignment (Calibration) B-28 . . . . Calibrating HP 437 Power Meter B-29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Calibrating Gigatronics 8541C Power Meter B-31 . . . . . . . . . . . . . . . . . . . . Manual Cable Calibration B-32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Calibrating Test Cable SetupUsing HP PCS Interface (HP83236) B-32 . . . . . . . . . . . . . . . . . . . . . . . . . . . Calibrating Test Cable Setup Using Advantest R3465 B-36 . . . . . . . . . . . . . B
Table of Contents  – continued1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesB
Test Equipment PreparationMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-1PRELIMINARYPurposeThis appendix provides information on pre–testing set–up for thefollowing test equipment items (not required for the Cybertest test set):SAgilent E7495A test equipment setupSAgilent E4406A transmitter test setSAgilent E4432B signal generatorSAdvantest R3267 spectrum analyzerSAdvantest R3562 signal generatorSAgilent 8935 analyzer (formerly HP 8935)SHP 8921 with PCS interface analyzerSAdvantest R3465 analyzerSMotorola CyberTestSHP 437 power meterSGigatronics 8541C power meterSGPIB adapterPre–testing set–up information covered includes verification and settingGPIB addresses, inter–unit cabling, connectivity testing, pre–test controlsettings, and equipment calibration for items which are not calibratedwith the Calibrate Test Equipment function of the LMF.The following procedures cover verification and changing GPIBaddresses for the various items of CDMA test equipment supported bythe LMF.B
Test Equipment Preparation  – continued B-2 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYAgilent R7495A Test EquipmentSetupThis test equipment requires a warm-up period of at least 30 minutesbefore BTS testing or calibration begins.Using the Agilent E7495A with the LMFThe Agilent E7495A does not require the use of the 19MHz frequencyreference; if connected, it will be ignored. The Even Sec SYNCconnection is required.The Agilent E7495A signal generator is only calibrated down to –80db.In order to achieve accurate FER testing, be sure the RX setup includesat least 40db of attenuation. This will ensure the signal generator willoutput sufficient power to operate in the calibrated range.Set the IP Address as described in Table B-1.Table B-1: Set IP Address on Agilent E7495A test setnStep Action1Use the System Button > Controls >IPAdmin to set an IP address on the E7495A as 128.0.0.49,and Netmask to 255.255.255.128. ConnectionsIt is recommended that you use a hub with BNC and RJ–45 connections.[Suggested models: Netgear model EN104 (4 port) or EN108 (8 port).Do NOT use model numbers ending with “TP”; those have no BNCconnectors.]The LMF will connect to the hub which in turn is connected to the BTSand to the Agilent E7495A.Agilent E7495A to Hub – This is an Ethernet cable, RJ–45 to RJ–45.LMF to Hub – Use one of the following cables to connect the LMF tothe Hub:– Ethernet cable, RJ–45 to RJ–45 (be sure that the LAN card is set foreither AUTO or to use the RJ–45 only).– Coax cable between LAN card and Hub.  (Use a “T” on the hub andconnect a cable between the other end of the “T” and the BTS LANconnection).Hub to BTS – Use BNC “T” connector on the hub. [If your hub doesn’thave BNC ports, use a BNC to UTP adapter.]B
Test Equipment Preparation  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-3PRELIMINARYDetecting Test EquipmentCheck that no other equipment is connected to the LMF. Agilentequipment must be connected to the LAN to detect it. Then perform theprocedures described in Table B-2.Table B-2: Detecting Agilent E7495A Test EquipmentnStep Action1Click the Tools Menu.2 Choose Options.3 Check Agilent E7495A option in non–GPIB Test Equipment and enter its IP number.4 Click Apply and wait a moment.5 Click Dismiss. Power Sensor CalibrationTable B-3 describes the E7495A Power Sensor Calibration.Table B-3: E7495A Power Sensor CalibrationnStep Action1Display the power meter screen.2Zero the power meter. Make sure you are connected as shown in Figure B-1.– Press the Zero softkey.– Press the Continue softkey.3Calibrate the power meter:– Press Ref CF.– Enter the reference cal factor, reading it off the label on the power sensor head.– Press Calibrate.– Connect the power sensor (see Figure B-2).– Press Continue.– Press Cal Factor.– Enter the cal factor from the label on the power sensor  head. Select a cal factor that’s withinthe operating frequency of the base station. B
Test Equipment Preparation  – continued B-4 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYFigure B-1: Agilent E7495A Pre–Power Sensor Calibration ConnectionUse onlyAgilent suppliedpower adapterGPSGPIOSerial 1Serial 2Power REF50 MHzSensorExt RefInEven SecondSync InAntennaPort 1RF Out / SWRPort 2RF InPOWER SENSORNOT CONNECTEDFigure B-2: Agilent E7495A Power Sensor Calibration ConnectionUse onlyAgilent suppliedpower adapterGPSGPIOSerial 1Serial 2Power REF50 MHzSensorExt RefInEven SecondSync InAntennaPort 1RF Out / SWRPort 2RF InPOWER SENSORCONNECTEDCable CalibrationFollow the directions in the WinLMF program to calibrate cables.– Calibrate the short cable (see Figure 6-12 or Figure 6-13) and two10 dB pads to get a base line and then calibrate the TX and RXsetup.  Since you need at least 40 dB of loss when doing the FERtest, the setup for RX is the same as TX.ATP SetupTX Path Calibration setup is shown in Test Equipment Setup (seeFigure 6-17 through Figure 6-20).B
Verifying and Setting GPIB AddressesMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-5PRELIMINARYAgilent E4406A TransmitterTester GPIB AddressRefer to Figure B-3 and follow the procedure in Table B-4 to verify and,if necessary, change the Agilent E4406A GPIB address.Figure B-3: Setting Agilent E4406A GPIB AddressSystem KeyBk Sp KeyEnter KeyData Entry KeypadSoftkey ButtonsSoftkey Label Display AreaActive Function Areati-CDMA-WP-00085-v01-ildoc-ftwTable B-4: Verify and Change Agilent E4406A GPIB AddressStep Action1In the SYSTEM section of the instrument front panel, press the System key.– The softkey labels displayed on the right side of the instrument screen will change.2Press the Config I/O softkey button to the right of the instrument screen.– The softkey labels will change.– The current instrument GPIB address will be displayed below the GPIB Address softkey label.3If the current GPIB address is not set to 18, perform the following to change it:3a Press the GPIB Address softkey button. In the on–screen Active Function Area, GPIB Address willbe displayed followed by the current GPIB address.. . . continued on next pageB
Verifying and Setting GPIB Addresses  – continued B-6 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable B-4: Verify and Change Agilent E4406A GPIB AddressStep Action3b On front panel Data Entry keypad, enter the communications system analyzer GPIB address of 18.– The GPIB Address label will change to Enter.– Characters typed with the keypad will replace the current GPIB address in the Active FunctionArea.NOTETo correct an entry, press Bk Sp key to delete one character at a time.3c Press the Enter softkey button or the keypad Enter key to set the new GPIB address.– The Config I/O softkey labels will reappear.– The new GPIB address will be displayed under the GPIB Address softkey label. Agilent E4432B SignalGenerator GPIB AddressRefer to Figure B-4 and follow the procedure in Table B-5 to verify and,if necessary, change the Agilent E4432B GPIB address.Figure B-4: Setting Agilent E4432B GPIB AddressNumericKeypadSoftkeyButtonsSoftkey LabelDisplay AreaActive EntryAreaBackspaceKeyUtilityKeyB
Verifying and Setting GPIB Addresses  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-7PRELIMINARYTable B-5: Verify and Change Agilent E4432B GPIB AddressStep Action1In the MENUS section of the instrument front panel, press the Utility key.– The softkey labels displayed on the right side of the instrument screen will change.2Press the GPIB/RS232 softkey button to the right of the instrument screen.– The softkey labels will change.– The current instrument GPIB address will be displayed below the GPIB Address softkey label.3If the current GPIB address is not set to 1, perform the following to change it:3a Press the GPIB Address softkey button.– The GPIB Address label and current GPIB address will change to boldface.– In the on–screen Active Entry Area, Address: will be displayed followed by the current GPIBaddress.3b On the front panel Numeric keypad, enter the signal generator GPIB address of 1.– The GPIB Address label will change to Enter.– Characters typed on the keypad will replace the current GPIB address in the Active Entry display.NOTETo correct an entry, press the backspace key at the lower right of the keypad to delete one character ata time.3c Press the Enter softkey button to set the new GPIB address.– The new GPIB address will be displayed under the GPIB Address softkey label. Advantest R3267 SpectrumAnalyzer GPIB AddressRefer to Figure B-5 and perform the procedure in Table B-6 to verifyand, if necessary, change the Advantest R3267 spectrum analyzer GPIBaddress.B
Verifying and Setting GPIB Addresses  – continued B-8 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYFigure B-5: Setting Advantest R3267 GPIB AddressonREMOTELEDLCL KeyCONFIGKeySoftkey LableDisplay Area SoftkeyButtonsKeypad BSKey ENTRKeyTable B-6: Verify and Change Advantest R3267 GPIB AddressStep Action1If the REMOTE LED is lighted, press the LCL key.– The LED extinguishes.2Press the CONFIG key.–CONFIG softkey labels will appear in the softkey label display area of the instrument display.– The current GPIB address will be displayed below the GPIB Address softkey label.3If the current GPIB address is not set to 18, perform the following to change it:3a Press the GPIB Address softkey. A GPIB Address entry window will open in the instrument displayshowing the current GPIB address.3b Enter 18 on the keypad in the ENTRY section of the instrument front panel.– Characters typed on the keypad will replace the address displayed in the GPIB Address entrywindow.NOTETo correct an entry, press the BS (backspace) key at the lower right of the keypad to delete onecharacter at a time.3c Press the ENTR key to the lower right of the keypad to set the new GPIB address.– The GPIB Address entry window closes.– The new address is displayed in the bottom portion of the GPIB Address softkey label. B
Verifying and Setting GPIB Addresses  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-9PRELIMINARYAdvantest R3562 SignalGenerator GPIB AddressSet the GP–IB ADDRESS switch on the rear of the Advantest R3562signal generator to address 1 as shown in Figure B-6.Figure B-6: Advantest R3562 GPIB Address Switch Setting123 4567 854321GP–IP ADDRESS10GPIB Address set to “1”Agilent 8935 Series E6380(formerly HP 8935) Test SetGPIB AddressRefer to Figure B-7 and follow the procedure in Table B-7 to verify and,if necessary, change the Agilent 8935 GPIB address.Figure B-7: Agilent 8935 Test SetPre-setCursor ControlShiftInst Con-figLocalFW00885NOTE This procedure assumes that the test equipment is set up andready for testing.B
Verifying and Setting GPIB Addresses  – continued B-10 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable B-7: Verify and/or Change Agilent 8935 (formerly HP 8935) GPIB AddressStep Action1NOTEThe HP I/O configuration MUST be set to Talk & Listen, or no device on the GPIB will beaccessible. (Consult test equipment OEM documentation for additional information as required.)To verify that the GPIB addresses are set correctly, press Shift and LOCAL on the Agilent 8935.– The current HP–IB address is displayed at the top of the screen.NOTEHP–IB is the same as GPIB.2If the current GPIB address is not set to 18, perform the following to change it:2a – Press Shift and Inst Config.2b – Turn the Cursor Control knob to move the cursor to the HP–IB Adrs field.2c – Press the Cursor Control knob to select the field.2d – Turn the Cursor Control knob as required to change the address to 18.2e – Press the Cursor Control knob to set the address.3 Press Preset to return to normal operation.B
Verifying and Setting GPIB Addresses  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-11PRELIMINARYHewlett Packard HP8921A andHP83236A/B GPIB AddressRefer to Figure B-8 and follow the procedure in Table B-8 to verify and,if necessary, change the HP 8921A HP 83236A GPIB addresses.Figure B-8: HP 8921A and HP 83236A/BPresetCursor ControlShiftLocalNOTE This procedure assumes that the test equipment is set up andready for testing.Table B-8: Verify and/or Change HP 8921A and HP 83236A GPIB AddressesStep Action1To verify that the GPIB addresses are set correctly, press Shift and LOCAL on the HP 8921A.– The current HP–IB address is displayed at the top of the screen.NOTEHP–IB is the same as GPIB.2If the current HP–IB address is not set to 18, perform the following to change it:2a – Turn the Cursor Control knob to move the cursor to More and press the knob to select the field.2b – Turn the Cursor Control knob to move the cursor to I/O Config and press the knob to select thefield.2c – Turn the Cursor Control knob to move the cursor to Adrs and press the knob to select the field.2d – Turn the Cursor Control knob to change the HP–IB address to 18 and press the knob to set theaddress.B
Verifying and Setting GPIB Addresses  – continued B-12 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable B-8: Verify and/or Change HP 8921A and HP 83236A GPIB AddressesStep Action2e – Press Shift and Preset to return to normal operation.3To set the HP 83236A (or B) PCS Interface GPIB address=19, set the DIP switches as follows:– A1=1, A2=1, A3=0, A4=0, A5=1, HP–IB/Ser = 1Advantest R3465Communications Test Set GPIBAddressRefer to Figure B-9 and follow the procedure in Table B-9 to verify and,if necessary, change the GPIB address for the Advantest R3465.Figure B-9: R3465 Communications Test SetBNC“T”REF UNLOCK EVENSEC/SYNC IN CDMATIME BASE INPOWEROFF ONREF FW00337LCL Shift PresetGPIB and othersVernierKnobNOTE This procedure assumes that the test equipment is set up andready for testing.Table B-9: Verify and/or Change Advantest R3465 GPIB AddressStep Action1To verify that the GPIB address is set correctly, perform the following:1a – Press SHIFT then PRESET.1b – Press LCL.1c – Press the GPIB and Others CRT menu key to view the current address.2If the current GPIB address is not set to 18, perform the following to change it:2a – Turn the vernier knob as required to select 18.B
Verifying and Setting GPIB Addresses  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-13PRELIMINARYTable B-9: Verify and/or Change Advantest R3465 GPIB AddressStep Action2b – Press the vernier knob to set the address.3To return to normal operation, press Shift and Preset.Motorola CyberTest GPIBAddressFollow the steps in Table B-10 to verify and, if necessary, change theGPIB address on the Motorola CyberTest. Changing the GPIB addressrequires the following items:SMotorola CyberTest communications analyzer.SComputer running Windows 3.1/Windows 95.SMotorola CyberTAME software program “TAME”.SParallel printer port cable (shipped with CyberTest).NOTE This procedure assumes that the test equipment is set up andready for testing.Table B-10:  Verify and/or Change Motorola CyberTest GPIB AddressStep Action1On the LMF desktop, locate the CyberTAME icon. Double click on the icon to run the CyberTAMEapplication.2In the CyberTAME window taskbar, under Special, select IEEE.488.2.3CyberTAME software will query the CyberTest Analyzer for its current GPIB address. It then willopen the IEEE 488.2 dialog box. If the current GPIB address is not 18, perform the followingprocedure to change it:3a Use the up or down increment arrows or double–click in the field and type the number to set theaddress to 18.3b Click on the OK button.  The new address will be written to the CyberTest through the parallel portand saved.4Verify that the address has been set by repeating steps 2 and 3.  The new address should now appear inthe IEEE 488.2 dialog box Address field.B
Verifying and Setting GPIB Addresses  – continued B-14 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYHP 437 Power Meter GPIBAddressRefer to Figure B-10 and follow the steps in Table B-11 to verify and, ifnecessary, change the HP 437 GPIB address.Figure B-10: HP 437 Power MeterENTERPRESETSHIFT (BLUE) PUSHBUTTON –ACCESSES FUNCTION ANDDATA ENTRY KEYS IDENTIFIEDWITH LIGHT BLUE TEXT ONTHE FRONT PANEL ABOVETHE BUTTONSFW00308REFNOTE This procedure assumes that the test equipment is set up andready for testing.Table B-11: Verify and/or Change HP 437 Power Meter GPIB AddressStep Action1 Press Shift and PRESET.2Use the y arrow  key to navigate to HP–IB ADRS and press ENTER.The HP–IB address is displayed.NOTEHP–IB is the same as GPIB.3If the current GPIB address is not set to 13, perform the following to change it:– Use the y b arrow keys to change the HP–IB ADRS to 13.– Press ENTER to set the address.4 Press Shift and ENTER to return to a standard configuration. B
Verifying and Setting GPIB Addresses  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-15PRELIMINARYGigatronics 8541C PowerMeter GPIB AddressRefer to Figure B-11 and follow the steps in Table B-12 to verify and, ifnecessary, change the Gigatronics 8541C power meter GPIB address.Figure B-11: Gigatronics 8541C Power Meter DetailNOTE This procedure assumes that the test equipment is set up andready for testing.Table B-12: Verify and/or Change Gigatronics 8541C Power Meter GPIB AddressStep Action1! CAUTIONDo not connect/disconnect the power meter sensor cable with AC power applied to the meter.Disconnection could result in destruction of the sensing element or miscalibration.Press MENU.2Use the b arrow key to select CONFIG MENU and press ENTER.3Use the b arrow key to select GPIB and press ENTER.The current Mode and GPIB Address are displayed.4If the Mode is not set to 8541C, perform the following to change it:Use the a ’  arrow keys as required to select MODE.Use the by arrow keys as required to set MODE to 8541C.5If the GPIB address is not set to 13, perform the following to change it:Use the ’ arrow key to select ADDRESS.Use the by arrow keys as required to set the GPIB address to 13.6 Press ENTER to return to normal operation.B
Verifying and Setting GPIB Addresses  – continued B-16 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYRS232 GPIB Interface AdapterBe sure that the RS–232 GPIB interface adapter DIP switches are set asshown in Figure B-12.Figure B-12: RS232 GPIB Interface AdapterRS232–GPIBINTERFACE BOXS MODEDATA FORMATBAUD RATEGPIB ADRSONDIP SWITCH SETTINGSG MODEB
Test Equipment Connection, Testing, and ControlMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-17PRELIMINARYInter–unit Connection, Testing,and Control SettingsThe following illustrations, tables, and procedures provide theinformation necessary to prepare various items of CDMA test equipmentsupported by the WinLMF for BTS calibration and/or acceptance testing.HP 8921A with PCS InterfaceTest Equipment ConnectionsThe following diagram depicts the rear panels of the HP 8921A testequipment as configured to perform automatic tests. All test equipmentis controlled by the WinLMF via an IEEE–488/GPIB bus. The WinLMFexpects each piece of test equipment to have a factory-set GPIB address(refer to Table B-8 and Figure B-8). If there is a communicationsproblem between the WinLMF and any piece of test equipment, verifythat the GPIB addresses have been set correctly and that the GPIB cablesare firmly connected to the test equipment.Table B-13 shows the connections when not using an external 10 MHzRubidium reference.Table B-13: HP 8921A/600 Communications Test Set Rear Panel Connections Without Rubidium ReferenceFrom Test Set: To Interface:Connector Type8921A 83203B CDMA 83236A PCSConnector TypeCW RF OUT CW RF IN SMC–female – SMC–female114.3 MHZ IF OUT 114.3 MHZ IF IN SMC–female – SMC–femaleIQ RF IN IQ RF OUT SMC–female – SMC–femaleDET OUT AUX DSP IN SMC–female – SMC–femaleCONTROL I/O CONTROL I/O 45–pin custom BUS10 MHZ OUT SYNTH REF IN BNC–male – BNC–maleHPIB INTERFACE HPIB INTERFACE HPIB cable10 MHZ OUT REF IN BNC–male – BNC–maleB
Test Equipment Connection, Testing, and Control  – continued B-18 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYREAR PANELCOMMUNICATIONS TEST SETREF INHP 83203B CDMACELLULAR ADAPTERHP 8921A CELLSITE TEST SETHP 83236A PCSINTERFACEHP–IBTO GPIBINTERFACEBOXTO POWERMETER GPIBCONNECTORFW00368Figure B-13: HP 8921A/600 Cable Connections for 10 MHz Signal and GPIBwithout Rubidium ReferenceB
Test Equipment Connection, Testing, and Control  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-19PRELIMINARYFigure B-14 shows the connections when using an external 10 MHzRubidium reference.Table B-14: HP 8921A/600 Communications Test Set Rear Panel Connections With Rubidium ReferenceFrom Test Set: To Interface:Connector Type8921A 83203B CDMA 83236A PCSConnector TypeCW RF OUT CW RF IN SMC–female – SMC–female114.3 MHZ IF OUT 114.3 MHZ IF IN SMC–female – SMC–femaleIQ RF IN IQ RF OUT SMC–female – SMC–femaleDET OUT AUX DSP IN SMC–female – SMC–femaleCONTROL I/O CONTROL I/O 45–pin custom BUS10 MHZ OUT REF IN BNC–male – BNC–maleHPIB INTERFACE HPIB INTERFACE HPIB cable10 MHZ INPUT 10 MHZ OUT BNC–male – BNC–maleB
Test Equipment Connection, Testing, and Control  – continued B-20 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYREF INREAR PANELCOMMUNICATIONS TEST SETTO POWERMETER GPIBCONNECTORTO GPIBINTERFACEBOX10 MHZ WITHRUBIDIUM STANDARDHP 83203B CDMACELLULAR ADAPTERHP 8921A CELLSITE TEST SETHP 83236A PCSINTERFACEHP–IBFW00369Figure B-14: HP 8921A Cable Connections for 10 MHz Signal and GPIB with Rubidium ReferenceB
Test Equipment Connection, Testing, and Control  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-21PRELIMINARYHP 8921A with PCS InterfaceSystem Connectivity TestFollow the steps outlined in Table B-15 to verify that the connectionsbetween the PCS Interface and the HP 8921A are correct and cables areintact. The software also performs basic functionality checks of eachinstrument.Disconnect other GPIB devices, especially systemcontrollers, from the system before running theconnectivity software.NOTETable B-15: System ConnectivityStep ActionNOTE– Perform this procedure after test equipment has been allowed to warm–up and stabilize for aminimum of 60 minutes.1Insert HP 83236A Manual Control/System card into memory card slot.2Press the [PRESET] pushbutton.3Press the Screen Control [TESTS] pushbutton to display the “Tests” Main Menu screen.4Position the cursor at Select Procedure Location and select it by pressing the cursor control knob. Inthe Choices selection box, select Card.5Position the cursor at Select Procedure Filename and select it by pressing the cursor control knob. Inthe Choices selection box, select SYS_CONN.6Position the cursor at RUN TEST and select it. The software will provide operator prompts throughcompletion of the connectivity setup.7Do the following when the test is complete,Sposition cursor on STOP TEST and select itSOR press the [K5] pushbutton.8To return to the main menu, press the [K5] pushbutton.9Press the [PRESET] pushbutton.  Pretest Setup for HP 8921ABefore the HP 8921A CDMA analyzer is used for WinLMF–controlledtesting it must be set up correctly for automatic testing. Perform theprocedure in Table B-16.B
Test Equipment Connection, Testing, and Control  – continued B-22 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable B-16: Pretest Setup for HP 8921AStep Action1Unplug the memory card if it is plugged in.2Press the CURSOR CONTROL knob.3Position the cursor at IO CONFIG (under To Screen and More) and select it.4Select Mode and set for Talk&Lstn.  Pretest Setup for Agilent 8935Before the Agilent 8935 analyzer is used for WinLMF controlled testingit must be set up correctly for automatic testing. Perform the procedurein Table B-17.Table B-17: Pretest Setup for Agilent 8935Step Action1Unplug the memory card if it is plugged in.2Press the Shift button and then press the I/O Config button.3Press the Push to Select knob.4Position the cursor at IO CONFIG and select it.5 Select Mode and set for Talk&Lstn.  Advantest R3465 ConnectionThe following diagram depicts the rear panels of the Advantest R3465test equipment as configured to perform automatic tests. All testequipment is controlled by the WinLMF via an IEEE–488/GPIB bus.The WinLMF expects each piece of test equipment to have a factory-setGPIB address (refer to Table B-9 and Figure B-9). If there is acommunications problem between the WinLMF and any piece of testequipment, verify that the GPIB addresses have been set correctly andthat the GPIB cables are firmly connected to the test equipment.Figure B-15 shows the connections when not using an external 10 MHzRubidium reference.B
Test Equipment Connection, Testing, and Control  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-23PRELIMINARYADVANTEST R3465REAR PANELGPIBCONNECTORSERIAL I/OLOCAL INSERIAL I/OSYN REF IN 10 MHZ OUTPARALLELEXT TRIGGER10 MHZ REFGATE INGPIBCDMA  CLOCK OUTAC POWERAC POWERR3561LREAR PANELR3465REAR PANELTO T–CONNECTORON FRONT PANEL(EVEN/SEC/SYNC IN)XYZIF OUT421 MHZTO POWER METERGPIB CONNECTORTO GPIBINTERFACE BOXFW00370Figure B-15: Cable Connections for Test Set without 10 MHz Rubidium ReferenceB
Test Equipment Connection, Testing, and Control  – continued B-24 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYFigure B-16 shows the connections when using an external 10 MHzRubidium reference.SERIAL I/OGPIBCONNECTOR ADVANTEST R3465REAR PANELFROM 10 MHZRUBIDIUM REFERENCELOCAL INSERIAL I/OIF OUTSYN REF IN 10 MHZ OUTPARALLELEXT TRIGGER10 MHZ REFGATE INGPIBCDMA  CLOCK OUTAC POWERAC POWERR3465/3463REAR PANELR3561LREAR PANELTO T–CONNECTORON FRONT PANEL(EVEN SEC/SYNC IN)XYZ421 MHZTO POWER METERGPIB CONNECTORTO GPIBINTERFACE BOXFW00371Figure B-16: Cable Connections for Test Set with 10 MHz Rubidium ReferenceR3465 GPIB Clock Set–upTable B-18 describes the steps to set the clock for the Advantest R3465equipment.Table B-18: Advantest R3465 Clock SetupStep Action1Observe the current date and time displayed in upper right of the CRT display.2If the date and time are incorrect, perform the following to change them:2a – Push the Date/Time CRT menu key.2b – Rotate the vernier knob to select and set.2c – Push the vernier knob to enter.2d – Push the SHIFT then PRESET pushbutton (just below the CRT display).  B
Test Equipment Connection, Testing, and Control  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-25PRELIMINARYPretest Setup for AdvantestR3465Before the Advantest R3465 analyzer is used for WinLMF–controlledtesting it must be set up correctly for automatic testing. Perform theprocedure in Table B-19.Table B-19: Pretest Setup for Advantest R3465Step Action1Press the SHIFT button so the LED next to it is illuminated.2Press the RESET button.  Agilent 8932/E4432B TestEquipment InterconnectionTo perform FER testing on a 1X BTS with the Agilent 8935, a1X–capable signal generator, such as the Agilent E4432B, must be usedin conjunction with the CDMA base station test set. For properoperation, the test equipment items must be interconnected as follows:10 MHz reference signal – Connect a BNC (M)–BNC (M) cable fromthe 8935 10 MHz REF OUT connector to the E4432B 10MHz INconnector as shown in Figure B-17Even second pulse reference – Refer to Figure B-17, and connect aBNC “T” connector to the 8935 EVEN SEC SYNC IN connector.Connect a BNC (M)–BNC (M) cable from one side of the BNC “T” tothe E4432B PATTERN TRIG IN connector. Connect the other side ofthe BNC “T” to the CSA Card SYNC MONITOR connector using aBNC (M)–BNC (M) cable.B
Test Equipment Connection, Testing, and Control  – continued B-26 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYE4432B10 MHz INTO GPIBE4432BPATTERN TRIG INTO CSA CARDSYNC MONITOR(EVEN SEC TICK)893510 MHzREF OUT8935EVEN SECONDSYNC INWITH BNC “T” TDME0011–1Figure B-17: Agilent 8935/E4432B 10MHz Reference and Even Second Tick ConnectionsAgilent E4406A/E4432B TestEquipment InterconnectionTo provide proper operation during testing when both units are required,the 10 MHz reference signal from the E4406A transmitter test set mustbe provided to the E4432B signal generator. Connect a BNC (M)–BNC(M) cable from the E4406A 10 MHz OUT (SWITCHED) connector tothe E4432B 10MHz IN connector as shown in Figure B-18.E4406A10 MHz OUT(SWITCHED)E4432B10 MHz INTO GPIB BOXTDME0009–1Figure B-18: Agilent 10 MHz Reference ConnectionsB
Test Equipment Connection, Testing, and Control  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-27PRELIMINARYAdvantest R3267/R3562 TestEquipment InterconnectionTo provide proper operation during testing when both units are required,the R3257 spectrum analyzer must be interconnected with the R3562signal generator as follows:10 MHz reference signal – Connect a BNC (M)–BNC (M) cablebetween the R3562 SYNTHE REF IN connector and the R3267 10MHz OUT connector as shown in Figure B-19.Serial I/O – Using the Advantest cable provided, connect the R3267SERIAL I/O connector to the R3562 SERIAL I/O connector as shownin Figure B-19.TDME0010–1R3562SYNTHE REF IN TO GPIBBOX R3562SERIAL I/OTO GPIB BOXR326710 MHZ OUT R3267SERIAL I/OFigure B-19: Advantest 10 MHz Reference and Serial I/O ConnectionsB
Equipment Calibration B-28 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYCalibration Without the LMFSeveral test equipment items used in the optimization process requirepre–calibration actions or calibration verification which are notsupported by the LMF. Procedures to perform these activities for theapplicable test equipment items are covered in this section.Agilent E4406A TransmitterTester Self–alignment(Calibration)SystemKeySoftkeyButtonsSoftkey LabelDisplay AreaFigure B-20: Performing Agilent E4406ASelf–alignment (Calibration)Refer to Figure B-20 and follow the procedure in Table B-20 to performthe Agilent E4406A self–alignment (calibration).Table B-20: Perform Agilent E4406A Self–alignment (Calibration)Step Action1In the SYSTEM section of the instrument front panel, press the System key.– The softkey labels displayed on the right side of the instrument screen will change.2Press the Alignments softkey button to the right of the instrument screen.– The softkey labels will change.3Press the Align All Now softkey button.– All other instrument functions will be suspended during the alignment.– The display will change to show progress and results of the alignments performed.– The alignment will take less than one minute. B
Equipment Calibration  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-29PRELIMINARYCalibrating HP 437 PowerMeterPrecise transmit output power calibration measurements are made usinga bolometer–type broadband power meter with a sensitive power sensor.Follow the steps outlined in Table B-21 to enter information unique tothe power sensor before calibrating the test setup. Refer to Figure B-21as required.NOTE This procedure must be done before the automated calibration toenter power sensor specific calibration values.Figure B-21: Power Meter DetailCONNECT POWERSENSOR WITH POWERMETER TURNED OFFCONNECT POWER SENSORTO POWER REFERENCEWHEN CALIBRATING UNIT.POWER REFERENCE ISENABLED USING THE SHIFT ’KEYSSHIFT (BLUE) PUSHBUTTON –ACCESSES FUNCTION ANDDATA ENTRY KEYS IDENTIFIEDWITH LIGHT BLUE TEXT ONTHE FRONT PANEL ABOVETHE BUTTONSFW00308Table B-21: HP 437 Power Meter Calibration ProcedureStep Action1! CAUTIONDo not connect/disconnect the power meter sensor cable with AC power applied to the meter.Disconnection could result in destruction of the sensing element or mis–calibration.Make sure the power meter AC LINE pushbutton is OFF.2Connect the power sensor cable to the SENSOR input.3Set the AC LINE pushbutton to ON.NOTEThe calibration should be performed only after the power meter and sensor have been allowed towarm–up and stabilize for a minimum of 60 minutes.4Perform the following to set or verify the correct power sensor model:4a – Press [SHIFT]  then [a] to select SENSOR.4b – Identify the power sensor model number from the sensor label.4c – Use the [y] or [b] button to select the appropriate model; then press [ENTER].5Refer to the illustration for step 8, and perform the following to ensure the power reference output isOFF:. . . continued on next pageB
Equipment Calibration  – continued B-30 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable B-21: HP 437 Power Meter Calibration ProcedureStep Action5a – Observe the instrument display and determine if the triangular indicator over PWR REF isdisplayed.5b – If the triangular indicator is displayed, press [SHIFT] then [’] to turn it off.6 Press [ZERO].– Display will show “Zeroing ******.”– Wait for process to complete.7Connect the power sensor to the POWER REF output.8Turn on the PWR REF by performing the following:8a – Press [SHIFT] then [’].8b – Verify that the triangular indicator (below) appears in the display above PWR REF.9Perform the following to set the REF CF%:9a – Press ([SHIFT] then [ZERO]) for CAL.9b – Enter the sensor’s REF CF% from the sensor’s decal using the arrow keys and press [ENTER].(The power meter will display ”CAL *****” for a few seconds.)NOTEIf the REF CAL FACTOR (REF CF) is not shown on the power sensor, assume it to be 100%.10 Perform the following to set the CAL FAC %:10a – Press [SHIFT] then [FREQ] for CAL FAC.10b – On  the  sensor’s  decal,  locate  an  approximate  calibration  percentage  factor  (CF%)  at  2  GHz.10c – Enter the sensor’s calibration % (CF%) using the arrow keys and press [ENTER].–– When complete, the power meter will typically display 0.05 dBm. (Any reading between0.00 and 0.10 is normal.)11 To turn off the PWR REF, perform the following:11a – Press [SHIFT] then [’].11b – Disconnect the power sensor from the POWER REF output. B
Equipment Calibration  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-31PRELIMINARYCalibrating Gigatronics 8541CPower MeterPrecise transmit output power calibration measurements are made usinga bolometer–type broadband power meter with a sensitive power sensor.Follow the steps in Table B-22 to enter information unique to the powersensor.Table B-22: Calibrate Gigatronics 8541C Power MeterStep Action1! CAUTIONDo not connect/disconnect the power meter sensor cable with AC power applied to the meter.Disconnection could result in destruction of the sensing element or miscalibration.Make sure the power meter POWER pushbutton is OFF.2Connect the power sensor cable to the SENSOR input.3Set the POWER pushbutton to ON.NOTEAllow the power meter and sensor to warm up and stabilize for a minimum of 60 minutes beforeperforming the calibration procedure.4Connect the power sensor to the CALIBRATOR output connector.5 Press ZERO.– Wait for the process to complete. Sensor factory calibration data is read to power meter during thisprocess.6When the zeroing process is complete, disconnect the power sensor from the CALIBRATOR output.Figure B-22: Gigatronics 8541C Power Meter DetailCONNECT POWER SENSORWITH POWER METERTURNED OFFCONNECT POWER SENSOR TOCALIBRATOR POWER REFERENCEWHEN CALIBRATING/ZEROING UNITFRONT View REAR ViewGPIB CONNECTIONAC POWERFW00564B
Manual Cable Calibration B-32 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYCalibrating Test Cable SetupUsing HP PCS Interface(HP83236)Table B-23 covers the procedure to calibrate the test equipment using theHP8921 Cellular Communications Analyzer equipped with the HP83236PCS Interface.NOTE This calibration method must be executed with great care. Somelosses are measured close to the minimum limit of the powermeter sensor (–30 dBm).PrerequisitesEnsure the following prerequisites have been met before proceeding:STest equipment to be calibrated has been connected correctly for cablecalibration.STest equipment has been selected and calibrated.Table B-23: Calibrating Test Cable Setup (using the HP PCS Interface)Step ActionNOTEVerify that GPIB controller is turned off.1Insert HP83236 Manual Control System card into memory card slot.2Press the Preset pushbutton.3 Under Screen Controls, press the TESTS pushbutton to display the TESTS (Main Menu) screen.4Position the cursor at Select Procedure Location and select it. In the Choices selection box, selectCARD.5Position the cursor at Select Procedure Filename and select it. In the Choices selection box, selectMANUAL.6Position the cursor at RUN TEST and select it. HP must be in Control Mode Select YES.7If using HP83236A:Set channel number=<chan#>:– Position cursor at ChannelNumber and select it.– Enter the chan# using the numerickeypad; press [Enter] and thescreen will go blank.– When the screen reappears, thechan# will be displayed on thechannel number line.If using HP83236B:Set channel frequency:– Position cursor at Frequency Band and press Enter.– Select User Defined Frequency.– Go Back to Previous Menu.– Position the cursor to 83236 generator frequency andenter actual RX frequency.– Position the cursor to 83236 analyzer frequency andenter actual TX frequency.8Set RF Generator level:– Position the cursor at RF Generator Level and select it.– Enter –10 using the numeric keypad; press [Enter] and the screen will go blank.– When the screen reappears, the value –10 dBm will be displayed on the RF Generator Level line.. . . continued on next pageB
Manual Cable Calibration  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-33PRELIMINARYTable B-23: Calibrating Test Cable Setup (using the HP PCS Interface)Step Action9Set the user fixed Attenuation Setting to 0 dBm:– Position cursor at Analyzer Attenuation and select it– Position cursor at User Fixed Atten Settings and select it.– Enter 0 (zero) using the numeric keypad and press [Enter].10 Select Back to Previous Menu.11 Record the HP83236 Generator Frequency Level:Record the HP83236B Generator Frequency Level:– Position cursor at Show Frequency and Level Details and select it.– Under HP83236 Frequencies and Levels, record the Generator Level.– Under HP83236B Frequencies and Levels, record the Generator Frequency Level (1850 – 1910MHz).– Position cursor at Prev Menu and select it.12 Click on Pause for Manual Measurement.13 Connect the power sensor directly to the RF OUT ONLY port of the PCS Interface.14 On the HP8921A, under To Screen, select CDMA GEN.15 Move the cursor to the Amplitude field and click on the Amplitude value.16 Increase the Amplitude value until the power meter reads 0 dBm ±0.2 dB.NOTEThe Amplitude value can be increased coarsely until 0 dBM is reached; then fine tune the amplitudeby adjusting the Increment Set to 0.1 dBm and targeting in on 0 dBm.17 Disconnect the power sensor from the RF OUT ONLY port of the PCS Interface.NOTEThe Power Meter sensor’s lower limit is –30 dBm. Thus, only components having losses ≤30 dBshould be measured using this method. For further accuracy, always re-zero the power meterbefore connecting the power sensor to the component being calibrated. After connecting thepower sensor to the component, record the calibrated loss immediately.18 Disconnect all components in the test setup and calibrate each one separately by connecting eachcomponent, one-at-a-time, between the RF OUT ONLY PORT and the power sensor. Record thecalibrated loss value displayed on the power meter.SExample: (A) Test Cable(s) = –1.4 dB(B) 20 dB Attenuator  = –20.1 dB(B) Directional Coupler = –29.8 dB19 After all components are calibrated, reassemble all components together and calculate the total testsetup loss by adding up all the individual losses:SExample: Total test setup loss = –1.4 –29.8 –20.1 = –51.3 dB.This calculated value will be used in the next series of tests.20 Under Screen Controls press the TESTS button to display the TESTS (Main Menu) screen.. . . continued on next pageB
Manual Cable Calibration  – continued B-34 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable B-23: Calibrating Test Cable Setup (using the HP PCS Interface)Step Action21 Select Continue (K2).22 Select RF Generator Level and set to –119 dBm.23 Click on Pause for Manual Measurement.24 Verify the HP8921A Communication Analyzer/83203A CDMA interface setup is as follows (fieldsnot indicated remain at default):SVerify the GPIB (HP–IB) address:– under To Screen, select More– select IO CONFIG– Set HP–IB Adrs to 18– set Mode to Talk&LstnSVerify the HP8921A is displaying frequency (instead of RF channel)– Press the blue [SHIFT] button, then press the Screen Control [DUPLEX] button; this switches tothe CONFIG (CONFIGURE) screen.– Use the cursor control to set RF Display to Freq25 Refer toChapter 3 for assistance in setting the cable loss values into the LMF. B
Manual Cable Calibration  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-35PRELIMINARYFigure B-23: Cable Calibration Using HP8921 with PCS Interface(A)(C)(A)POWERSENSOR(C)30 dBDIRECTIONALCOUPLER150 WNON–RADIATINGRF LOADPOWERSENSOR(B)POWERSENSOR(B)MEMORYCARDSLOT20 dB / 20 WATTATTENUATORFW0029250 ΩTERMINATIONPOWERSENSORB
Manual Cable Calibration  – continued B-36 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYCalibrating Test Cable SetupUsing Advantest R3465NOTE Be sure the GPIB Interface is OFF for this procedure.Advantest R3465 Manual Test setup and calibration must be performedat both the TX and RX frequencies.Table B-24: Procedure for Calibrating Test Cable Setup Using Advantest R3465Step Action* IMPORTANT– This procedure can only be performed after test equipment has been allowed to warm–up andstabilize for a minimum of 60 minutes.1Press the SHIFT and the PRESET keys located below the display2Press the ADVANCE key in the MEASUREMENT area of the control panel.3Select the CDMA Sig CRT menu key4Select the Setup CRT menu key5Using the vernier knob and the cursor keys set the following parametersNOTEFields not listed remain at defaultGenerator Mode: SIGNALLink: FORWARDLevel Unit: dBmCalCorrection: ONLevel Offset: OFF6Select the return CRT menu key7 Press FREQ key in the ENTRY area8Set the frequency to the desired value using the keypad entry keys9Verify that the Mod CRT menu key is highlighting OFF; if not, press the Mod key to toggle it OFF.10 Verify that the Output CRT menu key is highlighting OFF; if not, press the Output key to toggle itOFF.11 Press the LEVEL key in the ENTRY area.12 Set the LEVEL to 0 dBm using the key pad entry keys.13 Zero power meter. Next connect the power sensor directly to the “RF OUT” port on the R3561LCDMA Test Source Unit.14 Press the Output CRT menu key to toggle Output to ON.15 Record the power meter reading  ________________________. . . continued on next pageB
Manual Cable Calibration  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  B-37PRELIMINARYTable B-24: Procedure for Calibrating Test Cable Setup Using Advantest R3465Step Action16 Disconnect the power meter sensor from the R3561L RF OUT jack.* IMPORTANTThe Power Meter sensor’s lower limit is –30 dBm.  Thus, only components having losses < 30 dBshould be measured using this method. For best accuracy, always re–zero the power meter beforeconnecting the power sensor to the component being calibrated.  Then, after connecting thepower sensor to the component, record the calibrated loss immediately.17 Disconnect all components in the the test setup and calibrate each one separately.  Connect eachcomponent one–at–a–time between the “RF OUT” port and the power sensor (see Figure B-24,“Setups A, B, and C”).  Record the calibrated loss value displayed on the power meter for eachconnection.Example:  (A) 1st Test Cable =  –0.5 dB(B) 2nd Test Cable  =  –1.4 dB(C) 20 dB Attenuator  =  –20.1 dB(D) 30 dB Directional Coupler  =  –29.8 dB18 Press the Output CRT menu key to toggle Output OFF.19 Calculate the total test setup loss by adding up all the individual losses:Example:  Total test setup loss  =  0.5 + 1.4 + 20.1 + 29.8  =  51.8 dBThis calculated value will be used in the next series of tests.20 Press the FREQ key in the ENTRY area21 Using the keypad entry keys, set the test frequency to the RX frequency22 Repeat steps 9 through 19 for the RX frequency.23 Refer to Chapter 3 for assistance in setting the cable loss values into the LMF. B
Manual Cable Calibration  – continued B-38 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYFigure B-24: Cable Calibration Using Advantest R3465POWERSENSOR20 DB / 2 WATTATTENUATOR(A)(C)POWERSENSOR(D)30 DBDIRECTIONALCOUPLER(C)100 WNON–RADIATINGRF LOADPOWERSENSORRF OUTPOWERSENSOR& (B)FW0032050 ΩTERMINATIONB
MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYAppendix C: Download ROM Code Appendix ContentDownloading ROM Code C-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Exception Procedure – Downloading ROM Code C-1 . . . . . . . . . . . . . . . . . C
Table of Contents  – continued1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesC
Downloading ROM CodeMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  C-1PRELIMINARYException Procedure –Downloading ROM CodeThis procedure is not part of a normal optimization.Perform this procedure only on an exception basis when no alternativeexists to load a BTS device with the correct version of ROM code.One GLI must be INS_ACT (bright green) before ROMcode can be downloaded to non–GLI devices.NOTEThe correct ROM and RAM codes for the software releaseused on the BSS must be loaded into BTS devices. Toidentify the correct device ROM and RAM code loads forthe software release being used on the BSS, refer to theVersion Matrix section of the SCt CDMA Release Notes(supplied on the tapes or CD–ROMs containing the BSSsoftware).All devices in a BTS must be loaded with the ROM andRAM code specified for the software release used on theBSS before any optimization or ATP procedures can beperformed.If a replacement device is loaded with ROM code which isnot compatible with the BSS software release being used,the device ROM code can be changed using the LMFbefore performing the BTS optimization and ATPs. Adevice loaded with later release ROM code can not beconverted back to a previous release ROM code in the fieldwithout Motorola assistanceCAUTIONIf it is necessary to download ROM code to a device from the LMF, theprocedure in Table C-1 includes steps for both ROM and RAM codedownload using the LMF.PrerequisitesPrior to performing this procedure, ensure the correct ROM and RAMcode files exist in the LMF computer’s applicable <x>:\<lmf homedirectory>\cdma\loads\<codeload#>\code folder for each of the devicesto be loaded.C
Downloading ROM Code  – continued C-2 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYThe Release level of the ROM code to be downloadedmust be the one specified for the software release installedin the BSS. The release level of the ROM code resident inthe other devices in the BTS must also be correct for theBSS software release being used. ROM code must not bedownloaded to a frame loaded with code for a BSSsoftware release with which it is not compatible.This procedure should only be used to upgradereplacement devices for a BTS. It should NOT be used toupgrade all devices in a BTS. If a BTS is to be upgradedfrom R15.x to R16.0, the upgrade should be done by theOMC–R using the DownLoad Manager.CAUTIONTable C-1: Download ROM and RAM Code to DevicesStep Action1Click on the device to be loaded.NOTEMore than one device of the same type can be selected for download by either clicking on each one tobe downloaded or from the BTS menu bar Select pull–down menu, select the device item that applies.Where:  device  =  the type of device to be loaded (BBX, CSA, GLI, MCC)2From the BTS menu bar Device pull–down menu, select Status.– A status report window will appear.3Make a note of the number in the HW Bin Type column.NOTE“HW Bin Type” is the Hardware Binary Type for the device. This code is used as the last four digits inthe filename of a device’s binary ROM code file. Using this part of the filename, the ROM code filecan be matched to the device in which it is to be loaded.4 Click OK to close the status window.5Click on the device to be loaded.NOTEROM code is automatically selected for download from the <x>:\<lmf homedirectory>\version folder>\<code folder> specified by the NextLoad property inthe bts–#.cdf file. To check the value of the NextLoad property, click on Util > Examine >Display Nextload. A pop–up message will show the value of the NextLoad.6From the BTS menu bar Device pull–down menus, select Download > ROM.– If the file matching the Hardware Binary Type of the device is found in the code folder, a statusreport shows the result of the download. Proceed to Step 11.– If a file selection window appears, select the ROM code file manually.7Double–click on the version folder with the desired version number for the ROM code file (forexample 2.16.0.x).. . . continued on next pageC
Downloading ROM Code  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  C-3PRELIMINARYTable C-1: Download ROM and RAM Code to DevicesStep Action8Double–click the Code folder.– A list of ROM and RAM code files will be displayed.9! CAUTIONA ROM code file with the correct HW Bin Type must be chosen. Using a file with the wrong HW BinType can result in unpredictable operation and damage to the device.Click on the ROM code file with the filename which matches the device type and HW Bin Typenumber noted in step 3 (for example, file bbx_rom.bin.0604 is the ROM code file for a BBX with aHW Bin Type of 0604).– The file should be highlighted.10 Click on the Load button.– A status report window is displayed showing the result of the download.NOTEIf the ROM load failed for some devices, load them individually by clicking on one device, performsteps 6 through 10 for it, and repeat the process for each remaining device.11 Click OK to close the status window.12 From the LMF window menu bar Tools pull–down menus, select Update NextLoad > CDMA.13 In the left–hand pane of the window which opens, click on the BTS number for the frame being loaded(for example, BTS–14).14 On the list of versions displayed in the right–hand pane, click the button next to the version number ofthe folder that was used for the ROM code download (for example, 2.16.0.x) and click Save.– A pop–up message will appear showing the CDF has been updated.15 Click on the OK button to dismiss the pop–up message.16 Click on the device that was loaded with ROM code.17 NOTERAM code is automatically selected for download.From the BTS menu bar Device pull–down menus, select Download > Code/Data to download RAMcode and dds file data.– A status report is displayed showing the result of the download.18 Click OK to close the status window.19 Observe the downloaded non–GLI device to ensure it is OOS_RAM (yellow).20 Click on the device which was loaded with code.21 From the BTS menu bar Device pull–down menu, select Status.Verify that the correct ROM and RAM version numbers are displayed in the status report window.22 Click OK to close the status window. C
Downloading ROM Code  – continued C-4 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesC
MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYAppendix D: MMI Cable Fabrication Appendix ContentMMI Cable Fabrication D-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Purpose D-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Required Parts D-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable Details D-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wire Run List D-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  D
Table of Contents  – continued1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesD
MMI Cable FabricationMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  D-1PRELIMINARYPurposeWhen the Motorola SLN2006A MMI Interface Kit is not available, acable can be fabricated by the user to interface a nine–pin serialconnector on an LMF computer platform with an MMI connector onGLI cards and other Motorola BTS assemblies. This section providesinformation necessary for fabricating this cable.Required PartsTable D-1: Parts Required to Fabricate MMI CableItem Part Number Qty DescriptionAMotorola 3009786R01 1Ribbon cable assembly, 1.524 M, one 8–contact MMIconnector, one 10–contact connectorBAMP 749814–1,Belkin A4B202BGC,or equivalent1Receptacle kit, unassembled, 9–position, socket contacts,unshielded, metal or plastic shell, solder or crimp–typecontacts Cable DetailsFigure D-1 illustrates the details of the fabricated MMI cable.Figure D-1: Fabricated MMI Cable DetailsDB–9 Plug Socket Numbering(Mating Side)123456789123456788–Contact  MMI PlugSocket Numbering(Mating Side)Item A: Cable assembly 3009786R01 (with 10–contact plug removed)MMIFAB001–0FABRICATION NOTES:1. Remove 10–contact connector from ribbon cable of cable assembly 3009786R012. Separate wires at unterminated end of ribbon cable as required to connect to DB–9connector contacts3. Dark wire on ribbon cable of cable assembly 3009786R01 connects to pin 1 of the8–contact plug4. Strip three ribbon cable wires with connections specified in Table D-2 and connect toDB–9 plug contacts as specified in Table D-25. Shorten un–connected ribbon cable wires enough to prevent contacting DB–9contacts, leaving enough wire to egage any strain relief in the DB–9 connector shellItem BD
MMI Cable Fabrication  – continued D-2 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYWire Run ListTable D-2 provides the wire run/pin–out information for the fabricatedMMI cable.Table D-2: Fabricated MMI Cable Wire Run List8–CONTACT MMIPLUG CONTACT DB–9 PLUGCONTACT1 ––––––––––––––––– 52 ––––––––––––––––– 23 ––––––––––––––––– 34No Connection (NC)5 NC6 NC7 NC8 NC D
MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYAppendix E: Multiple BTS Configurations Appendix ContentCompact BTS Expansion Configuration (Indoor) E-1 . . . . . . . . . . . . . . . . . . . . . . . Introduction E-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Materials Needed E-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External Combiner and Directional Coupler E-1 . . . . . . . . . . . . . . . . . . . . . Frame ID Switch Settings E-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation Procedure for Expansion Compact BTS with Dual cCLPAs E-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starter and Three Expansion BTSes Interconnect Cabling for Dual cCLPA E-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starter and Two Expansion BTSes Interconnect Cabling for Dual cCLPA E-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starter and One Expansion BTSes Interconnect Cabling for Dual cCLPA E-7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation Procedure for Expansion Compact BTS with Single cCLPA E-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starter and Three Expansion BTSes Interconnect Cabling for Single cCLPA E-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starter and Two Expansion BTSes Interconnect Cabling for Single cCLPA E-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starter and One Expansion BTSes Interconnect Cabling for Single cCLPA E-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation Procedure for Expansion Compact BTS without cCLPA E-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starter and Expansion BTSes Interconnect Cabling without cCLPA E-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Starter and Two Expansion BTSes to cCLPA Cabling E-20 . . . . . . . . . . . . . Starter and One Expansion BTS to cCLPA Cabling E-21 . . . . . . . . . . . . . . . Multiple Compact BTS Configuration (Outdoor) E-22 . . . . . . . . . . . . . . . . . . . . . . . Introduction E-22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Materials Needed E-22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . External Combiner and Directional Coupler E-22 . . . . . . . . . . . . . . . . . . . . . ExpansionCompact BTS Installation Procedure E-23 . . . . . . . . . . . . . . . . . . Frame ID Switch Settings E-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Other Diagrams E-26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E
Table of Contents  – continued1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesE
Compact BTS Expansion Configuration (Indoor)MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-1PRELIMINARYIntroductionThis appendix covers the indoor and outdoor version of  the CompactBTS Expansion configuration.  This configuration is set up for onlyusing other Compact BTSes. Power and ground cabling is not shown.Figure E-1 through Figure E-3 show expansion BTSes using twocCLPAs.Figure E-4 through Figure E-6 show expansion BTSes using onecCLPA.Materials NeededThe following materials are required to configure expansion BTSes.SInterconnect cabling of varying lengthsSVarious sized conduit (if used)SData cable for cCLPA (if used)SCustomer I/O cablingExternal Combiner andDirectional CouplerA combiner and directional coupler are required for some of theconfigurations. The following are the recommended specifications forthe combiner and directional coupler.Table E-1: Combiner and Directional Coupler SpecificationsItem SpecificationsCombinerConnector: N–TypeFrequency Range: Up to 2 GHzInsertion Loss: 3.5 dB maximumReturn Loss: 16 dB minimumAverage Input Power: 60 Watts minimumDirectional CouplerConnector: N–TypeFrequency Range: 810 to 950 MHzCoupling: 30 +/–1 dBDirectivity: 28 dB minimumReturn Loss: 18 dB minimumAverage Input Power: 10 Watts minimum E
Compact BTS Expansion Configuration (Indoor)  – continued E-2 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYSMotorola recommended directional coupler is P/N 809643T03SRecommended cable with combiner is Andrew LDF4–50 orequivalentFrame ID Switch SettingsRefer to Chapter 5, Figure 5-1 or Figure 5-2 or Table 5-1 throughTable 5-4 for the Frame DIP Switch settings.Installation Procedure forExpansion Compact BTS withDual cCLPAsFollow the procedure in Table E-2 for installation of expansion CompactBTS with Dual cCLPAs.Table E-2: Procedure for Installing Expansion Compact BTS with Dual cCLPAStep Action1Follow the procedure in Chapter 4 for installing a Compact BTS in a rack.2For a 3 BTS expansion configuration, follow Figure E-1. Proceed to step 3.2a For a 2 BTS expansion configuration, follow Figure E-2. Proceed to step 3.2b For a 1 BTS expansion configuration, follow  Figure E-3. Proceed to step 3.3If not using conduit, dress cables as necessary.4Perform Optimization and ATP as described in Chapter 6. LMF Help provides further information.  E
Compact BTS Expansion Configuration (Indoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-3PRELIMINARYStarter and Three ExpansionBTSes Interconnect Cabling forDual cCLPATable E-3 shows in tabular format the interconnect cabling ofFigure E-1.Table E-3: Starter and Three Expansion BTS Interconnect Cabling for Circuit or Packet Configuration with Dual cCLPABTS Expansion 1 Expansion 2 Expansion 3 cCLPAStarter TX–1 –––cCLPA–1 (TX IN)Starter TX–2 –––cCLPA–2 (TX IN)Starter EXP–TX 2 EXP TX–2 – – *cCLPA–2Starter EXP–TX 3 –EXP TX–2 – *cCLPA–1Starter EXP–TX 4 – – EXP TX–2 *cCLPA–2Starter RX MAIN – – – cCLPA–1 (RX OUT)Starter EXP–RX MAIN 2 –EXP – RXMAIN 2 – *cCLPA–1Starter EXP–RX MAIN 3 EXP – RXMAIN 2 – – *cCLPA–2Starter EXP–RX MAIN 4 – – EXP – RXMAIN 2 *cCLPA–2Starter RX DIV – – – cCLPA–2 (RX OUT)Starter EXP–RX DIV 2 EXP – RX DIV2– – *cCLPA–2Starter EXP–RX DIV 3 –EXP – RX DIV2– *cCLPA–1Starter EXP–RX DIV 4 – – EXP – RX DIV2*cCLPA–2Starter SDCX 2 SDC INPUTEXPANSION – – –Starter SDCX 3 –SDC INPUTEXPANSION – –Starter SDCX 4 – – SDC INPUTEXPANSION –* Not actual physical connections to cCLPA, but software connections through the Starter BTS. E
Compact BTS Expansion Configuration (Indoor)  – continued E-4 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYFigure E-1:  Three Expansion BTSes Cabling Diagram with Two cCLPAsEXPANSION 3EXPANSION 2EXPANSION 1STARTERcCLPA 1cCLPA 2LOCAL GPSPower and Ground not shownLALAEnsure that the expansionBTSes have an ExpansioncMPC card installed.E
Compact BTS Expansion Configuration (Indoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-5PRELIMINARYStarter and Two ExpansionBTSes Interconnect Cabling forDual cCLPATable E-4 shows in tabular format the interconnect cabling ofFigure E-2.Table E-4: Starter and Two Expansion BTS Interconnect Cabling for Circuit or Packet Configuration with Dual cCLPABTS Expansion 1 Expansion 2 Expansion 3 cCLPAStarter TX–1 –––cCLPA–1 (TX IN)Starter TX–2 –––cCLPA–2 (TX IN)Starter EXP–TX 2 EXP TX–2 – – *cCLPA–2Starter EXP–TX 3 –EXP TX–2 – *cCLPA–1Starter EXP–TX 4 – – – –Starter RX MAIN – – – cCLPA–1 (RX OUT)Starter EXP–RX MAIN 2 EXP – RXMAIN 2 – *cCLPA–1Starter EXP–RX MAIN 3 EXP – RXMAIN 2 – *cCLPA–2Starter EXP–RX MAIN 4 – – – –Starter RX DIV – – – cCLPA–2 (RX OUT)Starter EXP–RX DIV 2 EXP – RX DIV 2 – – *cCLPA–2Starter EXP–RX DIV 3 –EXP – RX DIV 2 – *cCLPA–1Starter EXP–RX DIV 4 – – – –Starter SDCX 2 SDC INPUTEXPANSION – – –Starter SDCX 3 –SDC INPUTEXPANSION – –Starter SDCX 4 – – – –* Not actual physical connections to cCLPA, but software connections through the Starter BTS. E
Compact BTS Expansion Configuration (Indoor)  – continued E-6 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYFigure E-2: Two Expansion BTSes Cabling Diagram with Two cCLPAsEXPANSION 2EXPANSION 1STARTERcCLPA 1cCLPA 2LOCAL GPSPower and Ground not shownLALAEnsure that the expansionBTSes have an ExpansioncMPC card installed.E
Compact BTS Expansion Configuration (Indoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-7PRELIMINARYStarter and One ExpansionBTSes Interconnect Cabling forDual cCLPATable E-5 shows in tabular format the interconnect cabling ofFigure E-3.Table E-5: Starter and One Expansion BTS Interconnect Cabling for Circuit or Packet Configuration with Dual cCLPABTS Expansion 1 Expansion 2 Expansion 3 cCLPAStarter TX–1 –––cCLPA–1 (TX IN)Starter TX–2 –––cCLPA–2 (TX IN)Starter EXP–TX 2 EXP TX–2 – – –Starter EXP–TX 3 – – – –Starter EXP–TX 4 – – – –Starter RX MAIN – – – cCLPA–1 (RX OUT)Starter EXP–RX MAIN 2 – – – –Starter EXP–RX MAIN 3 EXP – RXMAIN 2 – – *cCLPA–2Starter EXP–RX MAIN 4 – – – –Starter RX DIV – – – cCLPA–2 (RX OUT)Starter EXP–RX DIV 2 EXP – RX DIV 2 – – *cCLPA–2Starter EXP–RX DIV 3 – – – –Starter EXP–RX DIV 4 – – – –Starter SDCX 2 SDC INPUTEXPANSION – – –Starter SDCX 3 – – – –Starter SDCX 4 – – – –* Not actual physical connections to cCLPA, but software connections through the Starter BTS. E
Compact BTS Expansion Configuration (Indoor)  – continued E-8 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYLALAEXPANSION 1STARTERcCLPA 1cCLPA 2LOCAL GPSFigure E-3: One Expansion BTS Cabling Diagram with Two cCLPAsPower and Ground not shownEnsure that the expansionBTS has an Expansion cMPCcard installed.E
Compact BTS Expansion Configuration (Indoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-9PRELIMINARYInstallation Procedure forExpansion Compact BTS withSingle cCLPAFollow the procedure in Table E-2 for installation of expansion CompactBTS with Dual cCLPAs.Table E-6: Procedure for Installing Expansion Compact BTS with Single cCLPAStep Action1Follow the procedure in Chapter 4 for installing a Compact BTS in a rack.2For a 3 BTS expansion configuration, follow Figure E-4. Proceed to step 3.2a For a 2 BTS expansion configuration, follow Figure E-5. Proceed to step 3.2b For a 1 BTS expansion configuration, follow  Figure E-6. Proceed to step 3.3If not using conduit, dress cables as necessary.4Perform Optimization and ATP as described in Chapter 6. LMF Help provides further information.  E
Compact BTS Expansion Configuration (Indoor)  – continued E-10 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYStarter and Three ExpansionBTSes Interconnect Cabling forSingle cCLPATable E-7 shows in tabular format the interconnect cabling ofFigure E-4.Table E-7: Starter and Three Expansion BTS Interconnect Cabling for Circuit or Packet Configuration with Single cCLPABTS Expansion 1 Expansion 2 Expansion 3 cCLPAStarter TX–1 Signals are sent thruogh an external combiner anddirectional couplercCLPA–1 (TX IN)Starter TX–2directional couplerStarter EXP–TX 2 EXP TX–2 – – *cCLPA–1Starter EXP–TX 3 –EXP TX–2 – *cCLPA–1Starter EXP–TX 4 – – EXP TX–2 *cCLPA–1Starter RX MAIN – – – AntennaStarter EXP–RX MAIN 2 EXP – RXMAIN 2 – – *cCLPA–1Starter EXP–RX MAIN 3 –EXP – RXMAIN 2 – *cCLPA–1Starter EXP–RX MAIN 4 – – EXP – RXMAIN 2 *cCLPA–1Starter RX DIV – – – cCLPA–1(RX OUT)Starter EXP–RX DIV 2 EXP – RX DIV2– – *cCLPA–1Starter EXP–RX DIV 3 –EXP – RX DIV2– *cCLPA–1Starter EXP–RX DIV 4 – – EXP – RX DIV2*cCLPA–1Starter SDCX 2 SDC INPUTEXPANSION – – –Starter SDCX 3 –SDC INPUTEXPANSION – –Starter SDCX 4 – – SDC INPUTEXPANSION –* Not actual physical connections to cCLPA, but software connections through the Starter BTS. E
Compact BTS Expansion Configuration (Indoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-11PRELIMINARYFigure E-4: Three Expansion BTSes Cabling Diagram with One cCLPAEXPANSION 3EXPANSION 2EXPANSION 1STARTERcCLPA 1LOCAL GPSPower and Ground not shownCOMBINERLALARX DIVRX MAINTX 1TX 2DCEnsure that the expansionBTSes have an ExpansioncMPC card installed.E
Compact BTS Expansion Configuration (Indoor)  – continued E-12 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYStarter and Two ExpansionBTSes Interconnect Cabling forSingle cCLPATable E-8 shows in tabular format the interconnect cabling ofFigure E-5.Table E-8: Starter and Two Expansion BTS Interconnect Cabling for Circuit or Packet Configuration with Single cCLPABTS Expansion 1 Expansion 2 Expansion 3 cCLPAStarter TX–1 Signals are sent thruogh an external combiner anddirectional couplercCLPA–1 (TX IN)Starter TX–2directional couplerStarter EXP–TX 2 EXP TX–2 – – *cCLPA–1Starter EXP–TX 3 –EXP TX–2 – *cCLPA–1Starter EXP–TX 4 – – – –Starter RX MAIN – – – AntennaStarter EXP–RX MAIN 2 EXP – RXMAIN 2 – – *cCLPA–1Starter EXP–RX MAIN 3 –EXP – RXMAIN 2 – *cCLPA–1Starter EXP–RX MAIN 4 – – – –Starter RX DIV – – – cCLPA–1 (RX OUT)Starter EXP–RX DIV 2 EXP – RX DIV 2 – – *cCLPA–1Starter EXP–RX DIV 3 –EXP – RX DIV 2 – *cCLPA–1Starter EXP–RX DIV 4 – – – –Starter SDCX 2 SDC INPUTEXPANSION – – –Starter SDCX 3 –SDC INPUTEXPANSION – –Starter SDCX 4 – – – –* Not actual physical connections to cCLPA, but software connections through the Starter BTS. E
Compact BTS Expansion Configuration (Indoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-13PRELIMINARYFigure E-5: Two Expansion BTSes Cabling Diagram with One cCLPALAEXPANSION 2EXPANSION 1STARTERcCLPA 1LOCAL GPSPower and Ground not shownCOMBINERLARX DIVRX MAINTX 1TX 2DCEnsure that the expansionBTSes have an ExpansioncMPC cards installed.E
Compact BTS Expansion Configuration (Indoor)  – continued E-14 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYStarter and One ExpansionBTSes Interconnect Cabling forSingle cCLPATable E-9 shows in tabular format the interconnect cabling ofFigure E-6.Table E-9: Starter and One Expansion BTS Interconnect Cabling for Circuit or Packet Configuration with Single cCLPABTS Expansion 1 Expansion 2 Expansion 3 cCLPAStarter TX–1 –––cCLPA–1 (TX IN)Starter TX–2 – – – –Starter EXP–TX 2 EXP TX–2 – – –Starter EXP–TX 3 – – – –Starter EXP–TX 4 – – – –Starter RX MAIN – – – AntennaStarter EXP–RX MAIN 2 – – – –Starter EXP–RX MAIN 3 EXP – RXMAIN 2 – – *cCLPA–1Starter EXP–RX MAIN 4 – – – –Starter RX DIV – – – cCLPA–1 (RX OUT)Starter EXP–RX DIV 2 EXP – RX DIV 2 – – *cCLPA–1Starter EXP–RX DIV 3 – – – –Starter EXP–RX DIV 4 – – – –Starter SDCX 2 SDC INPUTEXPANSION – – –Starter SDCX 3 – – – –Starter SDCX 4 – – – –* Not actual physical connections to cCLPA, but software connections through the Starter BTS. E
Compact BTS Expansion Configuration (Indoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-15PRELIMINARYLAEXPANSION 1STARTERcCLPA 1LOCAL GPSFigure E-6: One Expansion BTS Cabling Diagram with One cCLPAPower and Ground not shownEnsure that the expansionBTS has an Expansion cMPCcard installed.LARX MAINRX DIVTX 1E
Compact BTS Expansion Configuration (Indoor)  – continued E-16 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYInstallation Procedure forExpansion Compact BTSwithout cCLPAFollow the procedure in Table E-2 for installation of expansion CompactBTS without cCLPAs. Table E-7 through Table E-9 (less the cCLPA) arevirtually the same and are can be used for the diagrams without cCLPA,and so separate tables will not be included here.Table E-10: Procedure for Installing Expansion Compact BTS without cCLPAStep Action1Follow the procedure in Chapter 4 for installing a Compact BTS in a rack.2For a 3 BTS expansion configuration, follow Figure E-7. Proceed to step 3.2a For a 2 BTS expansion configuration, follow Figure E-8. Proceed to step 3.2b For a 1 BTS expansion configuration, follow  Figure E-9. Proceed to step 3.3If not using conduit, dress cables as necessary.4Perform Optimization and ATP as described in Chapter 6. LMF Help provides further information.  Starter and Expansion BTSesInterconnect Cabling withoutcCLPATable E-7 through Table E-9 are virtually the same and are can be usedfor the diagrams without cCLPA. Separate tables will not be includedhere.E
Compact BTS Expansion Configuration (Indoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-17PRELIMINARYFigure E-7: Three Expansion BTSes Cabling DiagramEXPANSION 3EXPANSION 2EXPANSION 1STARTERLOCAL GPSPower and Ground not shownCOMBINERRX MAINRX DIVTX 1TX 2LALALADCEnsure that the expansionBTSes have the expansioncMPC cards installed.E
Compact BTS Expansion Configuration (Indoor)  – continued E-18 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYFigure E-8: Two Expansion BTSes Cabling DiagramEXPANSION 2EXPANSION 1STARTERLOCAL GPSPower and Ground not shownEnsure that the expansionBTSes have the expansioncMPC cards installed.COMBINERTX 1RX MAINRX DIVTX 2DCLALALAE
Compact BTS Expansion Configuration (Indoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-19PRELIMINARYEXPANSION 1STARTERLOCAL GPSFigure E-9: One Expansion BTS Cabling DiagramPower and Ground not shownEnsure that the expansionBTS has an expansion cMPCcard installed.TX 1RX MAINRX DIVLALALAE
Compact BTS Expansion Configuration (Indoor)  – continued E-20 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable E-11: BBX (Carrier) to cCLPA Via RS485BTS cCLPAStarter – BBX1 cCLPA–1Starter – BBX4 cCLPA–1Expansion 1 – BBX1 cCLPA–2Expansion 1 – BBX4 cCLPA–2Expansion 2 – BBX1 cCLPA–1Expansion 2 – BBX4 cCLPA–1Expansion 3 – BBX1 cCLPA–2Expansion 3 – BBX4 cCLPA–2 Table E-12 shows in tabular format the BTS–to–cCLPA cabling ofFigure E-1.Table E-12: Starter and Three Expansion BTS Cabling for Circuit or Packet to Dual cCLPAsBTS cCLPAStarter – BBX1 CPA–A (CPA–1)Starter – BBX4 CPA–A (CPA–1)Expansion 1 – BBX1 CPA–B (CPB–2)Expansion 1 – BBX4 CPA–B (CPB–2)Expansion 2 – BBX1 CPA–A (CPA–1)Expansion 2 – BBX4 CPA–A (CPA–1)Expansion 3 – BBX1 CPA–B (CPA–2)Expansion 3 – BBX4 CPA–B (CPA–2) Starter and Two ExpansionBTSes to cCLPA CablingTable E-13 shows in tabular format the BTS–to–cCLPA cabling ofFigure E-2.E
Compact BTS Expansion Configuration (Indoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-21PRELIMINARYTable E-13: Starter and Two Expansion BTS Cabling for Circuit or Packet to Dual cCLPAsBTS cCLPAStarter – BBX1 CPA–A (CPA–1)Starter – BBX4 CPA–A (CPA–1)Expansion 1 – BBX1 CPA–B (CPB–2)Expansion 1 – BBX4 CPA–B (CPB–2)Expansion 2 – BBX1 CPA–A (CPA–1)Expansion 2 – BBX4 CPA–A (CPA–1) Starter and One ExpansionBTS to cCLPA CablingTable E-14 shows in tabular format the BTS–to–cCLPA cabling ofFigure E-3.Table E-14: Starter and One Expansion BTS Cabling for Circuit or Packet to Dual cCLPAsBTS cCLPAStarter – BBX1 CPA–A (CPA–1)Starter – BBX4 CPA–A (CPA–1)Expansion 1 – BBX1 CPA–B (CPB–2)Expansion 1 – BBX4 CPA–B (CPB–2) E
Multiple Compact BTS Configuration (Outdoor) E-22 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYIntroductionThis section covers only the outdoor version of  the multiple CompactBTS configuration.Materials NeededThe following materials are required to configure expansion BTSes.SVaried length cables with RJ45 connectorsSVaried length cables with RF connectorsSConduit (customer supplied)SDC Power source (custoemr supplied)SBattery Backup (customer supplied)External Combiner andDirectional CouplerA combiner and directional coupler are required for some of theconfigurations. The following are the recommended specifications forthe combiner and directional coupler.Table E-15: Combiner and Directional Coupler SpecificationsItem SpecificationsCombinerConnector: N–TypeFrequency Range: Up to 2 GHzInsertion Loss: 3.5 dB maximumReturn Loss: 16 dB minimumAverage Input Power: 60 Watts minimumDirectional CouplerConnector: N–TypeFrequency Range: 810 to 950 MHzCoupling: 30 +/–1 dBDirectivity: 28 dB minimumReturn Loss: 18 dB minimumAverage Input Power: 10 Watts minimum SMotorola recommended directional coupler is P/N 809643T03SRecommended cable with combiner is Andrew LDF4–50 orequivalentE
Multiple Compact BTS Configuration (Outdoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-23PRELIMINARYSDirectional coupler and combiner are not environmentally protected ,and so must be placed within the TME.ExpansionCompact BTSInstallation ProcedureFollow the procedure in Table E-16for installation of multiple CompactBTSes.Table E-16: Procedure for Installing Expansion Compact BTSesStep Action1Follow the procedure in Chapter 4 for installing a Compact BTS in a rack.2For a 3 BTS expansion configuration, follow Figure E-1. Proceed to step 3.2a For a 2 BTS expansion configuration, follow Figure E-2. Proceed to step 3.2b For a 1 BTS expansion configuration, follow  Figure E-3. Proceed to step 3.3If conduit is not used, dress cables as necessary.4Perform Optimization and ATP as described in Chapter 6. LMF Help provides further information.  Frame ID Switch SettingsRefer to Chapter 5, Figure 5-1 or Figure 5-2 or Table 5-1 throughTable 5-4 for the Frame DIP Switch settings.E
Multiple Compact BTS Configuration (Outdoor)  – continued E-24 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYFigure E-10: Three Expansion BTSes Cabling DiagramLIGHTNINGARRESTORLIGHTNINGARRESTOREXPANSION 3EXPANSION 2EXPANSION 1STARTERcCLPA 1cCLPA 2LOCAL GPSTX1TX2RX DIVRX MAINTME ANTENNACONNECTORSTMERF–GPSCONNECTORPower and Ground not shownE
Multiple Compact BTS Configuration (Outdoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  E-25PRELIMINARYFigure E-11: Outdoor Two Expansion BTSes Cabling DiagramLIGHTNINGARRESTORLIGHTNINGARRESTOREXPANSION 2EXPANSION 1STARTERcCLPA 1cCLPA 2LOCAL GPSTMERF–GPSCONNECTORTX2TX1RX MAINRX DIVTME ANTENNACONNECTORSPower and Ground not shownE
Multiple Compact BTS Configuration (Outdoor)  – continued E-26 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYLIGHTNINGARRESTORLIGHTNINGARRESTOREXPANSION 1STARTERcCLPA 1cCLPA 2LOCAL GPSFigure E-12: Outdoor One Expansion BTS Cabling DiagramTMERF–GPSCONNECTORTX1RX MAINRX DIVTX2TME ANTENNACONNECTORSPower and Ground not shownOther DiagramsFor single cCLPA and no cCLPA, refer to the diagrams for indoor andallow for the TME connectors as shown in the diagrams presented in thisappendix.E
MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYAppendix F: Logical BTS Configuration Appendix ContentLogical BTS LAN Configuration for Compact BTS (Indoor) F-1 . . . . . . . . . . . . . . Introduction F-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Materials Needed F-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Frame ID Switch Settings F-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Logical BTS LAN Cabling Installation Procedure F-3 . . . . . . . . . . . . . . . . F
Table of Contents  – continued1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesF
Logical BTS LAN Configuration for Compact BTS (Indoor)MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  F-1PRELIMINARYIntroductionThis appendix covers only the Logical BTS configuration for cicruitCompact BTS. The diagrams cover only the LAN connections. Thisconfiguration is set up to be used only with other Compact BTSes.Power and ground cabling are not shown.The LAN operates at 10Mbps which is an ethernet standard. It providesan interface for each GLI in the confiiguration.Refer to Figure 6-1 for location of the LAN connectors. In circuit mode,the LAN connections are used by the LMF to download data, and for usein calibration, acceptance testing, and optimization.Use these diagrams in conjunction with the diagrams for expansionBTSes in Appendix E.Materials NeededThe following materials are required to configure LAN connectionsBTSes.S7 – RG–58 U cables (Length depends on spacing)S14 – BNC, Terminaton  Resistor Plugs (IEC 169–8 spec)S2 – BNC, 50 Ohm terminationsBTS ID Switch SettingsRefer to Chapter 5, Figure 5-1 or Figure 5-2 or Table 5-1 throughTable 5-4 for the BTS DIP Switch settings.EXPANSION 3EXPANSION 2EXPANSION 1STARTERFigure F-1: Three Expansion BTSes LAN Cabling DiagramAout BoutAin Bin Aout BoutAin Bin Aout BoutAin Bin Aout BoutAin Bin50–ohmLoad50–ohmLoadF
Logical BTS LAN Configuration for Compact BTS (Indoor)  – continued F-2 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYEXPANSION 2EXPANSION 1STARTERFigure F-2: Two Expansion BTSes LAN Cabling DiagramAout BoutAin Bin Aout BoutAin Bin Aout BoutAin Bin50–ohmLoad50–ohmLoadEXPANSION 1STARTERFigure F-3: One Expansion BTSes LAN Cabling DiagramAout BoutAin Bin Aout BoutAin Bin50–ohmLoad50–ohmLoadF
Logical BTS LAN Configuration for Compact BTS (Indoor)  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  F-3PRELIMINARYLogical BTS LAN CablingInstallation ProcedureFollow the procedure in Table F-1 for installation of LAN cables forLogical BTS.Table F-1: Procedure for Installing LAN Cabling for Logical BTSStep Action1Follow the procedure in Chapter 4 for installing a Compact BTS in a rack.2For a 3 BTS expansion configuration, follow Figure F-1. Proceed to step 3.2a For a 2 BTS expansion configuration, follow Figure F-2. Proceed to step 3.2b For a 1 BTS expansion configuration, follow  Figure F-3. Proceed to step 3.3Route LAN cables through conduit from Starter to Expansion BTS 1.4Route LAN cables through conduit from Starter to Expansion BTS 2 or 3  (depending onconfiguration).5If in use, route LAN cables from Expansion BTS 1 to Expansion BTS 2.6If in use, route LAN cables from Expansion BTS 2 to Expansion BTS 3.7Ensure that unused LAN connections are terminated in 50 ohms.8If not already performed, proceed to Appendix E for expansion cabling diagrams.9Perform Optimization and ATP as described in Chapter 6. LMF Help provides further information.   F
Logical BTS LAN Configuration for Compact BTS (Indoor)  – continued F-4 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesF
MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYAppendix G: Integrated BTS Router Preliminary Operations Appendix ContentIntegrated BTS Router Preliminary Operations – Introduction G-1 . . . . . . . . . . . . . Introduction G-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preliminary Operations G-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . When to Perform the Verifications G-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Verify GLI3 Software Version and Span Parameter Settings G-2 . . . . . . . . . . . . . . . Verify GLI3 Software Version and Span Parameter Settings G-2 . . . . . . . . Required Items G-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Verifying GLI3 Software Version and Span Parameter Settings G-2 . . . . . . Change GLI3 Span Parameter Settings G-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Change GLI3 Span Parameter Configuration G-6 . . . . . . . . . . . . . . . . . . . . G
Table of Contents  – continued1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesG
Integrated BTS Router Preliminary Operations – IntroductionMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  G-1PRELIMINARYIntroductionThe information and procedures provided are performed in cases wherethe GLI3 load and span parameters need to be verified.Preliminary OperationsImplementing the Integrated BTS Router (IBR) function requires somepreliminary checks of the GLI3 cards which will be used. This appendixprovides the procedures to accomplish these checks. The checks are:SVerification that IBR–capable software is installed on GLI3 cardswhich will be used for IBRSVerification that span parameter settings on GLI3 cards match therequirement for the spans at the BTS where the cards will be installed.When to Perform theVerificationsAll preliminary verifications provided in this chapter can be performedat either the BTS site or in a central facility equipped to power–up theGLI3 cards. Depending on the circumstances of the cards’ use, however,it may be advantageous in reducing the on–site upgrade time andlogistics to perform some of the verifications prior to installation at theBTS site. Table G-1 lists card conditions of use and the correspondingsuggested verification locations for the software version and spanparameter settings.Table G-1: Suggested Preliminary Verification LocationsGLI3 Card Condition InstallationLocation Software VersionVerificationLocationSpan ParameterSettings VerificationLocationInstalled and operating(circuit or packet) Site where installed At site Not required unlessspan type willchangeDifferent operatingsite from wherecurrently installedAt site wherecurrently installed Before or afterinstallation atdifferent site G
Verify GLI3 Software Version and Span Parameter Settings G-2 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYVerify GLI3 Software Versionand Span Parameter SettingsSoftware Version Verification – Before upgrading a BTS to packetbackhaul with an IBR, the software version installed in the GLI3 card orcards must be verified. If the installed software version does not supportIBR functionality, it must be upgraded to a version which does. For BTSsites which are already in operation, the upgrade can be done through anetwork download to the GLI3 once it is installed. For cards to beinstalled in new BTS sites not previously in operation, the upgraderequires special procedures, and must be done with Motorola FieldOperations or Account Team assistance.Span Parameter Settings – Prior to initializing a GLI3 card for the firsttime in a live circuit BTS or IBR packet BTS site, the span parametersettings in the card must be verified as matching those provisioned in theOMC–R database. If the settings are not correct, the card will be unableto communicate with the RAN network elements and the site will not gointo service. Procedures are included in this section to change the GLI3card span parameter settings if this is necessary to match those requiredfor the BTS.Required ItemsThe following items are required to perform the verification:SLocal Maintenance Facility (LMF) computer with the LMFapplication program version installed which is compatible with thesoftware release installed on the BSS refer to Chapter 6Optimization/ATP in this manual.SOne of the following– Motorola cable part number CGDSMMICABLE219112– Fabricated DB–9 receptacle–to–8–contact MMI connector cable(see the MMI Cable Fabrication Section of Appendix D forfabrication instructions and Figure 6-9 for connection)– SLN2006A MMI Interface Kit (this kit is no longer available toorder), consisting of the following:–– Motorola Model TRN9666A null modem board–– Motorola 3009786R01 MMI cable or equivalentS(For use with SLN2006A only) Straight–through RS–232 cable,DB–9 to DB–9, and DB–9 to DB–25 connector adapter (seeFigure D-1)Verifying GLI3 SoftwareVersion and Span ParameterSettingsFollow the procedure in Table G-2 to verify GLI3 card software versionand span parameter settings.G
Verify GLI3 Software Version and Span Parameter Settings  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  G-3PRELIMINARYTable G-2: Verify GLI3 Software Version and Span Parameter SettingsStep Action1If it has not been done, start a GLI3 MMI communication session on the LMF computer as describedin Table 6-11.2Verify the installed software version by entering the following at the GLI3 prompt:display version3Response to the command will depend on the operating mode of the card. Responses similar to thefollowing will be displayed for:3a – Cards in circuit mode:GLI3>  display version01.09.1980 20:01:59 MGLI–002–2  OOS–SBY   BTS–CDMA 16.41.200.14 RAM version: 16.41.200.14ROM version: 16.41.200.14Built: Tue Oct 21 09:52:28 2003 il27–2112Bootrom version: 16.41.200.12Bootrom Built: Thu Oct  2 03:11:34 2003 IL27–0775Bootblock version: 16.1.59.00Bootblock Built: Wed Apr 10 07:08:06 2002 RIPCORD004This GLI board is in RAMBooted from /nvram00/loads/gli3_ckt_rom_upgrade.elfNext boot from /nvram00/loads/gli3_ckt_rom_upgrade.elfGLI3>  . . . continued on next page G
Verify GLI3 Software Version and Span Parameter Settings  – continued G-4 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable G-2: Verify GLI3 Software Version and Span Parameter SettingsStep Action3b – For cards in packet mode:GLI3>  display version03.23.2004 18:16:07 MGLI–250–1  CC PRESENT BTS–CDMA 16.41.00.11 INTERNAL RAM VERSION: 16.41.0.11RAM Built: Tue Mar  2 04:59:33 2004 il27–2112BOOTROM VERSION: 16.41.00.08BOOTROM Built: Tue Feb 17 10:52:27 2004 il27–0507BOOTBLOCK VERSION: 16.1.59.00BOOTBLOCK Built: Wed Apr 10 07:08:06 2002 RIPCORD004SYSTEM VERSION: 2.16.4.50.15 COMMITTED VERSION: 2.16.4.50.15 NEXT VERSION: 2.16.4.50.15 BACK UP VERSION 2.16.4.50.10 CURRENT RELEASE PATH: /nvram00/screl/2.16.4.50.15/ CURRENT LIF: /nvram00/screl/2.16.4.50.15/NE_LIF.xml CURRENT IMAGE: /nvram00/screl/2.16.4.50.15/gli_ram.bin.0108 CODE SERVER: 128.0.0.1 GLI3>  4Note the bootROM or System version numbers displayed and determine if the GLI3 is loaded withIBR–capable code as follows:SIf the booROM version number is 2.16.41.00.08 or later, the GLI3 is IBR–capableSIf the System version number is 2.16.4.50.7 or later (for example, 2.16.4.50.25), the GLI3 isIBR–capableNOTEIf the card is to be installed in a new BTS site which has not previously been in operation, contact thelocal Motorola Account Team for assistance in upgrading the card with IBR–capable software version.. . . continued on next pageG
Verify GLI3 Software Version and Span Parameter Settings  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  G-5PRELIMINARYTable G-2: Verify GLI3 Software Version and Span Parameter SettingsStep Action5Verify the span parameter settings for frame format, equalization, and linkspeed by entering thefollowing at the GLI3>  prompt:config ni currentThe system will respond with a display similar to the following:The frame format in flash is set to use T1_2.Equalization:  Span A – Default (0–131 feet for T1/J1, 120 Ohm for E1)  Span B – Default (0–131 feet for T1/J1, 120 Ohm for E1)  Span C – Default (0–131 feet for T1/J1, 120 Ohm for E1)  Span D – Default (0–131 feet for T1/J1, 120 Ohm for E1)  Span E – Default (0–131 feet for T1/J1, 120 Ohm for E1)  Span F – Default (0–131 feet for T1/J1, 120 Ohm for E1)Linkspeed: Default (56K for T1 D4 AMI, 64K otherwise)Currently, the link is running at the default rate The actual rate is 0NOTESDefaults for span equalization are 0–131 feet for T1/J1 spans and 120 Ohm for E1.SDefault linkspeed is 56K for T1 D4 AMI spans and 64K for all other types.SThere is no need to change from defaults unless the provisioned span configuration requires it.6The span parameter settings in the GLI must match those provisioned in the OMC–R database for theBTS. If they do not, proceed to Table G-3 in the Change GLI3 Span Parameter Settings section.7If no other MMI actions are required for the card, terminate the MMI communication session anddisconnect the LMF computer from the card. G
Change GLI3 Span Parameter Settings G-6 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYChange GLI3 Span ParameterConfigurationIf span parameter settings in the GLI3 card do not match the OMC–Rdatabase span parameters for the BTS where they are to be installed,follow the procedure in Table G-3 to change them.Table G-3: Set GLI3 Span Parameter ConfigurationStep Action1If it has not been done, start a GLI3 MMI communication session on the LMF computer as describedin Table 6-11.2At the GLI3>  prompt, enter the following:config  ni  formatThe terminal will display a response similar to the following:COMMAND SYNTAX: config ni format option Next available options:   LIST –     option : Span Option                    E1_1 : E1_1 – E1 HDB3 CRC4    no TS16                    E1_2 : E1_2 – E1 HDB3 no CRC4 no TS16                    E1_3 : E1_3 – E1 HDB3 CRC4    TS16                    E1_4 : E1_4 – E1 HDB3 no CRC4 TS16                    T1_1 : T1_1 – D4, AMI, No ZCS                    T1_2 : T1_2 – ESF, B8ZS                    J1_1 : J1_1 – ESF, B8ZS (Japan) – Default                    J1_2 : J1_2 – ESF, B8ZS                    T1_3 : T1_3 – D4, AMI, ZCS>NOTEWith this command, all active (in–use) spans will be set to the same format.3To set or change the span type, enter the correct option from the list at the entry prompt (>), as shownin the following example:> T1_2NOTEThe entry is case–sensitive and must be typed exactly as it appears in the list. If the entry is typedincorrectly, a response similar to the following will be displayed:CP: Invalid command01.061980 00:11’59 MGLI–000–2 INS–ACT BTS–CDMA 16.1.68.00GLI3>. . . continued on next pageG
Change GLI3 Span Parameter Settings  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  G-7PRELIMINARYTable G-3: Set GLI3 Span Parameter ConfigurationStep Action4An acknowledgement similar to the following will be displayed:The value has been programmed. It will take effect after the next reset.GLI3>5If the current GLI span rate must be changed, enter the following MMI command:config  ni  linkspeedA response similar to the following will be displayed :Next available options: LIST –  linkspeed : Span Linkspeed                   56K : 56K (default for T1_1 and T1_3 systems)                   64K : 64K (default for all other span configurations)>NOTEWith this command, all active (in–use) spans will be set to the same linkspeed.6To set or change the span linkspeed, enter the required option from the list at the entry prompt (>), asshown in the following example:> 64KNOTEThe entry is case–sensitive and must be typed exactly as it appears in the list. If the entry is typedincorrectly, a response similar to the following will be displayed:CP: Invalid command01.061980 00:12’04 MGLI–000–2 INS–ACT BTS–CDMA 16.1.68.00GLI3>7An acknowledgement similar to the following will be displayed:The value has been programmed.  It will take effect after the next reset.GLI3>. . . continued on next pageG
Change GLI3 Span Parameter Settings  – continued G-8 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable G-3: Set GLI3 Span Parameter ConfigurationStep Action8If the span equalization must be changed, enter the following MMI command:config  ni  equalA response similar to the following will be displayed:COMMAND SYNTAX: config ni equal span equal Next available options:   LIST –       span : Span                       a : Span A                       b : Span B                       c : Span C                       d : Span D                       e : Span E                       f : Span F>. . . continued on next pageG
Change GLI3 Span Parameter Settings  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  G-9PRELIMINARYTable G-3: Set GLI3 Span Parameter ConfigurationStep Action9At the entry prompt (>), enter the designator from the list for the span to be changed as shown in thefollowing example:> aA response similar to the following will be displayed :COMMAND SYNTAX: config ni equal a equal Next available options:   LIST –      equal : Span Equalization                       0 : 0–131 feet (default for T1/J1)                       1 : 132–262 feet                       2 : 263–393 feet                       3 : 394–524 feet                       4 : 525–655 feet                       5 : LONG HAUL                       6 : 75 OHM                       7 : 120 OHM (default for E1)                       8 : T1 Long Haul mode. No Attenuation                       9 : T1 Long Haul mode. 7.5 dB Attenuation                      10 : T1 Long Haul mode. 15.0 dB Attenuation                      11 : T1 Long Haul mode. 22.5 dB Attenuation                      12 : E1 Long Haul mode.>! CAUTIONWhen selecting span equalization settings, comply with the following or the BTS may operateerratically or unpredictably:SFor ALL BTS types, do not select any of the following settings if they are displayed:– 5   LONG HAUL– 6   75 OHM– 11  T1 Long Haul mode.  22.5 dB Attenuation– 12  E1 Long Haul modeSFor four–digit BTSs supported with Channel Service Units (CSU), do not select any of thefollowing additional settings:– 8   T1 Long Haul mode.  No Attenuation– 9   T1 Long Haul mode.  7.5 dB Attenuation– 10  T1 Long Haul mode.  15.0 dB Attenuation. . . continued on next pageG
Change GLI3 Span Parameter Settings  – continued G-10 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTable G-3: Set GLI3 Span Parameter ConfigurationStep Action10 At the entry prompt (>), enter the code for the required equalization from the list as shown in thefollowing example:> 0A response similar to the following will be displayed :> 0The value has been programmed. It will take effect after the next reset.GLI2>11 Repeat steps 8 through 10 for each in–use span.12 NOTEThis step must be performed for GLI3 cards operating on a packet image to ensure the span parameterchanges will replace the previous settings.For a GLI3 card in packet mode, enter the following:rmfile  /nvram00/config/hlp_param.txtA response similar to the following will be displayed :GLI3>  rmfile /nvram00/config/hlp_param.txt11.24.2003 23:14:57 MGLI–004–1  CC PRESENT BTS–CDMA 16.40.00.09 Removing file: /nvram00/config/hlp_param.txtSuccessfully removed file: /nvram00/config/hlp_param.txtGLI3>13 * IMPORTANTSAfter executing the config  ni  format, config  ni  linkspeed, and/or config  ni  equal commands,the affected MGLI/GLI board MUST be reset and reloaded for changes to take effect.SAlthough defaults are shown in the software, always consult site–specific documentation for spantype, equalization, and linkspeed used at the site where the cards are to be installed.Reset the card using the MMI reset command.. . . continued on next pageG
Change GLI3 Span Parameter Settings  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  G-11PRELIMINARYTable G-3: Set GLI3 Span Parameter ConfigurationStep Action14 Once the card has completed resetting, execute the following command to verify span settings are asrequired:config  ni  currentA response similar to the following will be displayed :The frame format in flash is set to use T1_2.Equalization:  Span A – 0–131 feet  Span B – 0–131 feet  Span C – Default (0–131 feet for T1/J1, 120 Ohm for E1)  Span D – Default (0–131 feet for T1/J1, 120 Ohm for E1)  Span E – Default (0–131 feet for T1/J1, 120 Ohm for E1)  Span F – Default (0–131 feet for T1/J1, 120 Ohm for E1)Linkspeed: 64KCurrently, the link is running at 64K The actual rate is 015 If the span configuration is not correct, perform the applicable step from this table to change it andrepeat steps 12, 13, and 14 to verify required changes have been programmed.16 If no other MMI actions are required for the card, terminate the MMI communication session anddisconnect the LMF computer from the card. G
Change GLI3 Span Parameter Settings  – continued G-12 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesG
MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYAppendix H: Integrated BTS Router Installation Appendix ContentIntegrated BTS Router Installation – Introduction H-1 . . . . . . . . . . . . . . . . . . . . . . . Background H-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . New Packet BTS Installation with IBR H-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . New Packet BTS Installation H-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Prerequisites H-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Implementing IBR Functionality H-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BTS Span Connections for IBR H-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BTS Span Connections H-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BTS Span Cable H-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . BTS Span Connections for IBR – One Span H-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . One Span Frame H-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . H
Table of Contents  – continued1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesH
Integrated BTS Router Installation – IntroductionMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  H-1PRELIMINARYBackgroundThe IBR capability was developed to provide a low–cost solution forproviding CDMA packet backhaul benefits at cell sites with lower trafficvolumes. The IBR function is implemented by using the GLI3 cardConcentration Highway Interface (CHI) bus 2 processor to perform therouter function. This is accomplished through changes in the GLI3 cardsoftware. A card with the IBR–capable software can perform as a circuitGLI3 card, as a GLI3 with IBR, and as a GLI3 used with external BTSrouter groups. The card has the capability to recognize the environmentin which it is installed and autoselect the appropriate operating mode(circuit, IBR packet, external BTS router packet).Span line channel capability for an IBR–equipped SC480 BTS is limitedto those available on a single T1 or E1 span.H
New Packet BTS Installation with IBR H-2 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNew Packet BTS InstallationThis section covers the actions necessary for implementing IBR packetcapability in the installation of a new BTS. Procedures unique to thisimplementation are contained in this section. When procedures requiredin this implementation are contained in other parts of this publication orin other publications, the user will be specifically directed to them at theappropriate places in this section.PrerequisitesThe following must be accomplished prior to traveling to the BTS sitefor IBR implementation:SThe BTS has been installed as described in Chapter 4 of this manual.SOne of the following:– GLI3 card(s) for the site have been verified as having IBR–capablesoftware image installed– Motorola Field Operations or Account Team member is identifiedto travel to the BTS site to perform GLI3 IBR–capable softwareinstallation, if requiredSGLI3 card(s) for the BTS are on hand for transport to the BTS site orare verified to be at the BTS siteSRequired publications to support IBR implementation activities are onhand for transportation to the BTS siteImplementing IBR FunctionalityFollow the procedure in Table H-1 to implement IBR functionality forthe BTS.Table H-1: Implement IBR Functionality in New BTSStep Action1Upon arrival at the site, contact the OMC–R and notify the operator that site operations are starting.2If the BTS has not been initially powered up, apply power to the BTS in accordance with the PowerPre–Power–up Tests and Initial Power–up Tests and Procedures described in Chapter 5 of this manual.3Once the BTS is fully powered up with these procedures, the GLI3 card should have been seated in thecorrect slot. If it is not, seat the card at this time and allow each to complete its initialization.4If it was not previously done, follow the procedure in Table G-2 to:SVerify the software version in the GLI3 card(s)SVerify the span parameter settings in each GLI3 card match those established for the site in theOMC–R database5If the GLI3software requires upgrading for IBR capability, request Motorola Field Operations orAccount Team assistance in upgrading the software.6If GLI3 card span parameter settings do not match those required, change them as necessary byfollowing the procedure in Table G-3.. . . continued on next pageH
New Packet BTS Installation with IBR  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  H-3PRELIMINARYTable H-1: Implement IBR Functionality in New BTSStep Action7Refer to the site documentation for IBR spans and inspect the BTS span cabling connections to be surethey match Figure H-1.8Correct any cabling discrepancies between the BTS span cabling and site documentation, referring toFigure H-1 and the Install Span and Alarm Cables and Span Line Cable Pin Numbering Chapter 4 ofthis manual as required.9If the BTS requires optimization and/or ATP, perform them at this time by following the applicableprocedures in Chapter 6 of this manual.10 When all preparations for BTS operation are completed, contact the OMC–R and notify the operatorthat the BTS is ready for operation and request notification when the operator no longer requiressupport on–site.11 When advised that there is no further requirement for on–site support of BTS and IBR initialization,proceed to Chapter 8 and follow the procedures to prepare to leave the site. H
BTS Span Connections for IBR H-4 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYBTS Span ConnectionsThe illustration in this section provides the detail of span connection fora  non–redundant BTS to support IBR packet operation. The requiredconfiguration for IBR in redundant BTS is a single span.BTS Span CableAll connections in the BTS span connection diagram for IBR are basedon the use of the following Motorola–standard BTS span cable:Table H-2: BTS Span CablesItem Part Number Qty DescriptionBTS span cable CGDS1583461orCGDS15834621Cable, 50–wire, shielded twisted 25 pair, 100ohm, 24–AWG, 7.6 m (25 ft – CGDS1583461) or15.2 m (50 ft – CGDS1583462), one male50–contact TELCO connector attached. One endof cable is un–terminated to allow connection tosite termination equipment. H
BTS Span Connections for IBR – One SpanMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  H-5PRELIMINARYOne Span FrameFigure H-1 illustrates the connection details for one span to supportpacket operation with IBR for non–redundant BTS.Figure H-1: Cabling Compact BTS Packet Operation Integrated BTS Router Spans – One SpanBTS TerminationEquipmentALL CROSS–CONNECTSARE DONE WITHINTERMINATIONEQUIPMENTSC4812TL0201PIN 2 RX TIP APIN 1 RX RING APIN 5 TX TIP APIN 4 TX RING ASPAN I/O ABTS SPANCABLEORG–WHT  TX TIPWHT–ORG  TX RINGBLU–WHT  RX TIPWHT–BLU  RX RINGH
BTS Span Connections for IBR – One Span  – continued H-6 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesH
MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRUPRELIMINARYAppendix I: Packet Backhaul Configuration Appendix ContentPacket Backhaul BTS  I-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Introduction I-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Packet Backhaul BTS Procedures I-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I
Table of Contents  – continued1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesI
Packet Backhaul BTS MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  I-1PRELIMINARYIntroductionFor Packet Backhaul, the LMF Help should be accessed for theappropriate procedures.Packet Backhaul BTSProceduresOptimization ProceduresSClick on LMF HelpSSelect Optimization/ATP ProcessSSelect Optimization procedure for SC48X– Important CDF Parameters– CSA– Optimization of SC48X High Power Configuration– Optimization of SC48X Low Power Configuration– Optimization of SC48X High Power in Logical Configuration– Optimization of SC48X Low Power in Logical Configuration– Calibrating Procedures for SC48X Expansion Frame ConfigurationsFollow the appropriate procedure identified in the LMF Help.I
Packet Backhaul BTS   – continued I-2 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYNotesI
MAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  Index-1PRELIMINARYIndexNumbers10BaseT/10Base2 converter, LMF to BTSconnection, 6-17 AAbbreviatedRX acceptance test, all–inclusive, 7-5 TX acceptance test, all–inclusive, 7-5 Acceptance Test Procedure. See ATPAccessing OMCR CLI Window, 10-2 Advantest R3267 Spectrum Analyzer GPIB Address,B-7 Advantest R3465 Communications Test Set GPIBAddress, B-12 Advantest R3562 Signal Generator GPIB Address,B-9 Agilent 8935 Series E6380 (formerly HP 8935) TestSet GPIB Address, B-9 Agilent E4406A, calibration, B-28 Agilent E4406A Transmitter Tester GPIB Address,B-5 Agilent E4432B Signal Generator GPIB Address, B-6All Cal/Audit procedure, 6-82 All RX ATP Test Procedure, 7-8 All TX ATP Test Procedure, 7-7 All TX/RX ATP Test Procedure, 7-6 ATPall inclusive TX acceptance test outline, 7-5 automated introduction, 7-1 code domain noise floor acceptance test procedure,7-19 code domain power acceptance test procedure, 7-19failure report generation, 7-23 FER test, frame error rate testing, 7-21 pilot time offset, 7-16 prerequisites, 7-2 spectral purity TX mask, 7-11 test set–up, 6-61 Advantest R3267/R3562, DRDCs, 6-64 Advantest R3465, 6-61 Agilent 8935, DRDCs, 6-61 Agilent 8935/E4432B, DRDCs, 6-63 Agilent E4406A/E4432B, DRDCs, 6-63 CyberTest, 6-61 HP 8921A, 1.9 GHz, 6-62 HP 8921A, 800 MHz, 6-59 , 6-62 waveform quality (Rho), 7-14 waveform quality (RHO) acceptance test procedure,7-14 ATP – Reduced, 7-1 Attenuator, required test equipment, 1-18 BBasic Troubleshooting Overview, 11-1 Bay Level Offset calibrationdescription, 6-76 purpose, 6-76 when to calibrate, 6-76 BBXcarrier spectral purity, 7-11 primary and redundant, TX tests to be performed,7-9 BLO. See Bay Level Offset calibrationBroad Band Receiver. See BBXBTSdownload, 6-36 Ethernet LAN interconnect diagram, 6-33 LMF connection, 6-16 , 6-17
Index  – continued Index-2 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYRX sensitivity/frame error rate, 7-10 system software download, 6-6 BTS Frame Erasure Rate. See FERBTS Log In Procedure, GUI, 6-25 BTS loginCLI environment, 6-27 General, 6-25 GUI environment, 6-25 BTS LogoutCLI environment, 6-29 GUI environment, 6-28 Create CAL File, 6-88 Ccable calibration, automatic, test set–up, 6-56 Advantest R3267/R3562, 6-57 Advantest R3465, 6-56 Agilent 8935, 6-56 Agilent E4406A/E4432B, 6-57 CyberTest, 6-56 HP 8921A, 6-56 CAL file. See calibration data fileCalibrate Test Cabling Using Signal Generator &Spectrum Analyzer, 6-71 Calibrating, Test Equipment, 6-68 Calibrating Cables, Overview, 6-69 Calibrating Test Cable Setup, PCS InterfaceHP83236B, B-32 Calibrating Test Cabling using CommunicationsSystem Analyzer, 6-70 Calibration, required test equipment, 1-14 calibrationcalibration data file, 6-77 Gigatronics 8542B, B-31 calibration data file, description of, 6-77 Cannot communicate to Power Meter, 11-5 CCP shelf illustration, left side, 1-24 CDF, 6-5 site equipage verification, 6-6 site type and equipage data information, 6-1 CDMA, subscriber mobile radiotelephone, optionaltest equipment, 1-19 Cell Siteequipage verification, 6-2 types configuration, 6-5 Cell Site Data File. See CDFCLI, 6-24 Clock Sync Module. See CSMCode domain power/noise flooracceptance test, 7-18 analyzer display, 7-20 Command Line Interface, 6-24 Communication test set, rear panel, B-18 , B-20 communications test set, TX acceptance tests, 7-4 Connect BTS E1/T1 spans, 8-4 Connect BTS T1/E1 spans, 8-4 Connecting test equipment to the BTS, 6-51 Control, TX output verification, 7-4 Copy and Load Cal File to to CBSC, 8-1 Copy BTS CDF (or NECF) and CBSC CDF Files tothe LMF, 6-12 Copying CAL files from CDMA LMF to the CBSC,8-1 Copying CAL files to the CBSC, 8-2 CSMclock source, select, 6-40 enable, 6-41 LEDs, 6-43 system description, 6-43 CSM clock source, select, 6-40 CSM frequency verification, 6-45 DDevices, download. See DownloadDigital multimeter, required test equipment, 1-19 DownloadSee also DevicesBTS, 6-36 BTS system software, 6-6 Download BLO Procedure, 6-84 download ROM and RAM code. See ROM codeDownload/Enable MCCs, 6-42 Download/Enable MGLIs, 6-39
Index  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  Index-3PRELIMINARYEE1, isolate BTS from the E1 spans, 6-16 E4406A, calibration, B-28 Enable CSMs. See CSMEquipment, warm–up, required test equipment, 1-14 Equipment warm-up, 6-55 establish MMI communication, 6-30 Ethernet LAN, interconnect diagram, 6-33 Ethernet LAN termination, 6-3 External Test Equipment Removal, 8-3 FFailure report generation, 7-23 FER, acceptance test, 7-21 Files, intermediate file, 7-23 files, calibration data, 6-77 Fluke, model 8062A with Y8134 test lead kit, testequipment, 1-19 Folder Structure Overview, 6-9 Frame, equipage preliminary operations, 6-1 Frequency counter, optional test equipment, 1-19 GGeneral Purpose Interface Bus, IEEE–488 protocolinterface bus. See GPIBGenerating an ATP Report, 7-23 Gigatronics 8541C Power Meter GPIB Address, B-15Gigatronics 8542 power meter, calibration, B-31 GPIB, B-17 , B-21 , B-22 cables required test equipment, 1-17 set address, HP 437B, B-14 GPIB AddressAdvantest R3267, B-7 Advantest R3465, B-12 Advantest R3562, B-9 Agilent (formerly HP) 8935, B-9 Agilent E4406A, B-5 Agilent E4432B, B-6 Gigatronics 8541C Power Meter, B-15 Hewlett Packard HP8921a & HP83236A/B, B-11 Motorola CyberTest, B-13 GPIB Interface Box, RS232, B-16 GPS Initialization/Verificationestimated position accuracy, 6-46 surveyed position accuracy, 6-46 GPS satellite system, 6-41 GUI, 6-19 HHardware Requirements, 1-15 Hewlett Packard, 10833A or equivalent, required testequipment, 1-17 Hewlett Packard HP8921A and HP83236A/B GPIBAddress, B-11 High–impedance conductive wrist strap, required testequipment, 1-18 HP 437Pre–calibration, B-29 setting GPIB address, B-14 HP 83236A, B-21 HP 8921A PCS interface, Cables Connection for 10MHz Signal and GPIB , B-18 , B-20 HP 8921A/600 test set, 1-16 HP8921A, B-21 Test equipment connections , B-17 HyperTerminal, Creating named HyperTerminalconnection, 6-14 HyperTerminal , create named connection, 6-14 IIEEE–488 protocol interface bus. See GPIBInitial HP8921A setup, B-32 Initial Installation of Boards/Modules, preliminaryoperations, 6-2 Intermediate file, generate ATP file using, 7-23 LLAN, tester optional test equipment, 1-19 LAN termination, 6-3 LED, CSM, 6-43 LIF, Load Information File, 6-10 LMF, B-17 , B-22 1X FER acceptance test, 7-4
Index  – continued Index-4 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARY1X upgrade preparation, home directory, 6-9 BTS connection, 6-17 to BTS connection, 6-16 TX acceptance tests, 7-4 view CDF information, 6-6 LMF BTS displays, 6-19 LMF Removal, 8-4 Load Information File, 6-10 Logging Into a BTS, 6-25 Logging Out, 6-28 MMotorola CyberTest GPIB Address, B-13 Multi Channel Card. See MCCNNational Instruments, GPIB–232–CT or equivalent,required test equipment, 1-16 NECF, 6-5 OOMCR CLI access procedure, 10-2 Online Help, 6-32 Optional, test equipment list, 1-19 Optional test equipmentCDMA subscriber mobile or portableradiotelephone, 1-19 frequency counter, 1-19 LAN tester, 1-19 oscilloscope, 1-19 RF test cable, 1-19 spectrum analyzer, 1-19 Oscilloscope, optional test equipment, 1-19 PPCMCIA, Ethernet adapter, LMF to BTS connection,6-17 Pilot time offset, acceptance test, 7-16 Ping, 6-33 Policy, required test equipment, 1-14 Power Meter, setting GPIB address, HP437B, B-14 Power meterrequired test equipment, 1-17 , 1-18 TX acceptance tests, 7-4 Pre–calibration, HP 437, B-29 Preliminary operations, cell Site types, 6-1 Prepare to leave siteconnect BTS E1/T1 spans, 8-4 connect BTS T1/E1 spans, 8-4 Prepare to Leave the SiteExternal Test Equipment Removal, 8-3 Final Checks before leaving site, 8-5 LMF Removal, 8-4 Re–connect BTS T1 spans, 8-4 Prerequisites, automated acceptance tests, 7-2 Procedures to Copy CAL Files From Diskette to theCBSC, 8-2 Procedures to Copy Files to a Diskette, 8-1 RRAM code, described, 6-36 Re–connect BTS T1 Spans, 8-4 receive path, calibration, 6-76 component verification, 6-76 Reduced ATP, 7-1 Report generation, ATP report, 7-23 Required test equipmentcalibration, 1-14 communications system analyzer, 1-16 digital multimeter, 1-19 equipment warm–up, 1-14 GPIB cables, 1-17 high–impedance conductive wrist strap, 1-18 list, 1-15 optional equipment, 1-19 policy, 1-14 power meter, 1-17 , 1-18 RF adaptors, 1-18 RF attenuator, 1-18 RF load, 1-18 RS232 to GPIB interface, 1-16 test cable calibration, 1-14 Restore Carrier Signaling Operations for a CircuitBTS, 10-29 Restore Carrier Signaling Operations for a PacketBTS, 10-59
Index  – continuedMAY 2004 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU  Index-5PRELIMINARYRestore Carrier Signaling Operations Procedure For aCircuit BTS, Starting Up, 10-29 Restore Carrier Signaling Operations Procedure For aPacket BTS, Starting Up, 10-59 Restore Sector Signaling Operations for a CircuitBTS, 10-26 Restore Sector Signaling Operations for a PacketBTS, 10-56 Restore Sector Signaling Operations Procedure For aCircuit BTS, Starting Up, 10-26 Restore Sector Signaling Operations Procedure For aPacket BTS, Starting Up, 10-56 Restore Site Signaling Operations for a Circuit BTS,10-23 Restore Site Signaling Operations Procedure For aCircuit BTS, Starting Up, 10-23 Restore Site Signaling Operations for a Packet BTS,10-53 Restore Site Signaling Operations Procedure For aPacket BTS, Starting Up, 10-53 RFattenuator, 1-18 load for required test equipment, 1-18 required test equipment load, 1-18 test cable, 1-18 RF path calibration. See Bay Level Offset calibrationRhoTX waveform quality acceptance test, 7-14 waveform quality requirements, 7-14 ROM codedescribed, 6-36 downloading, C-1 procedure, C-2 RS232 GPIB Interface Box, B-16 RS232 to GPIB interface, required test equipment,1-16 RXacceptance tests, FER, 7-21 sensitivity/frame error rate, 7-10 SSelecting Test Equipment, 6-66 Set–up for TX Calibration, 6-81 Setting Cable Loss Values, 6-73 Setting TX Coupler Loss Value, 6-74 Shut Down Carrier Signaling Functions for a CircuitBTS, 10-16 Shut Down Carrier Signaling Functions for a PacketBTS, 10-46 Shut Down Carrier Signaling Functions ProcedureFor a Circuit BTS, Shutting Down, 10-16 Shut Down Carrier Signaling Functions ProcedureFor a Packet BTS, Shutting Down, 10-47 Shut Down Sector Signaling Functions for a  PacketBTS, 10-39 Shut Down Sector Signaling Functions for a CircuitBTS, 10-9 Shut Down Sector Signaling Functions Procedure Fora Circuit BTS, Shutting Down, 10-9 Shut Down Sector Signaling Functions Procedure Fora Packet BTS, Shutting Down, 10-40 Shut Down Site Signaling Functions for a CircuitBTS, 10-3 Shut Down Site Signaling Functions for a PacketBTS, 10-32 Shut Down Site Signaling Functions Procedure For aCircuit BTS, Shutting Down, 10-3 Shut Down Site Signaling Functions Procedure For aPacket BTS, Shutting Down, 10-33 signal generator, 1X FER acceptance test, 7-4 Site, equipage verification, 6-6 Site equipage, CDF/NECF, 6-5 Software Release caveats, 8-1 Span line, J1 verification equipment, optional testequipment, 1-19 Spectral purity, TX mask – primary and redundantBBX, 7-9 Spectral purity transmit mask, acceptance test, 7-11 Spectrum analyzer, optional test equipment, 1-19 Supported Test Sets, 6-51 System Connectivity Test, B-21 TT1, isolate BTS from the T1 spans, 6-16 Tektronics, model 2445 or equivalent, optional testequipment, 1-19
Index  – continued Index-6 1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU MAY 2004PRELIMINARYTest cable calibration, required test equipment, 1-14 Test Equipment, Calibrating, 6-68 Test equipmentset up, TX output verification/control, 7-4 system analyzer, 1-16 TX acceptance tests, 7-4 Test equipment connections , preliminary AgilentE4406A/E4432B set–up, B-26 Test Equipment Setup Calibration for TX Bay LevelOffset, B-36 Test Equipment Setup Chart, 6-53 Test equipment setup RF path  calibration, 6-78 transmit path, calibration, 6-76 component verification, 6-76 Transmit TX path audit, 6-85 Transmit TX path calibration, 6-79 TXacceptance testscode domain power/noise floor, 7-18 equipment setup, 7-4 pilot time offset, 7-16 spectral purity mask, 7-11 spectrum analyzer display, 7-13 waveform quality (rho), 7-14 all inclusive TX ATP test, 7-5 output acceptance testscode domain power noise, 7-9 pilot time offset, 7-9 waveform quality, 7-9 TX Audit Test, 6-85 Tx BLO Nominal Offset, Setup for TX Cal, 6-82 TX calibration, 6-82 All Cal/Audit, 6-82 set–up, 6-58 Advantest R3267, 6-60 Agilent 8935, 6-58 Agilent E4406A, 6-60 CyberTest, 6-58 TX path calibration, 6-82 UUpdating Calibration Data FilesCopy and Load Cal File to to CBSC, 8-1 Software Release caveats, 8-1 UTP, LMF to BTS connection, 6-17 Vverification during calibration, 6-76 Verify, TX output, 7-4 Verify GLI ROM code load, 6-38 WWaveform quality (Rho), acceptance test procedure,7-14 XXircom Model PE3–10B2, LMF to BTS connection,6-17
*68P09260A11−7*68P09260A11–7
PRELIMINARY68P09260A11–7MAY 2004ENGLISHCDMA2000 1XSOFTWARE RELEASE 2.16.4.XTechnicalInformation1X SC480 BTS HARDWAREINSTALLATION, OPTIMIZATION/ATP, ANDFRU800 MHZ
SOFTWARE RELEASE 2.16.4.X800 MHZCDMA2000 1X1X SC480 BTS HARDWARE INSTALLATION, OPTIMIZATION/ATP, AND FRUENGLISHMAY 200468P09260A11–7PRELIMINARY
Technical Information Products and Services11STANDARD MANUAL PRINTING INSTRUCTIONSSTANDARD SPECIFICATIONS – FOR REFERENCE–DO NOT MODIFYPart Number:  68P09260A11–7 APC:Title:  1X SC480 BTS Hardware Installation, Optimization/ATP, and FRU379PAPER:Body: 70 lb.Inside Cover: 65 lb. CougarTabs: 110 lb. IndexBinder Cover: Standard TEDcover – 10 pt. Carolina1st. LEVEL TABS:Single Sided5 CutsClear MylarPantone 2706–CBlack Ink2nd. LEVEL TABS: FINISHING:3–Ring BinderSlant–D3–Hole Punched(5/16–in. dia.)Shrink Wrap BodyBlack ink for body, inside cover, and binder cover.SPECIAL INSTRUCTIONSTAB and SHEET SIZE/QUANTITY7X9 8.5x11 648 11x17NON–STANDARD SPECIFICATIONSTape Bound Corner Stitch   Other: Meet with manager to determine the deliverable.Sheets = (Total Pages) / 2Single Sided7 CutsClear MylarWhiteBlack InkFilename: 260A11–71st Level Tabs 2nd Level TabsVolume MAY 2004of DatePrint Vendor: eDOC

Navigation menu