Powerwave Technologies 5JS0056 Multi Carrier RF Power Amplifier User Manual 273678
Powerwave Technologies Inc Multi Carrier RF Power Amplifier 273678
Contents
Manual 3

 G3S-800-140-031 Installation & Service Manual 
 Copyright Powerwave Technologies, Inc., September 2001. All rights reserved 
044-05095 Rev. A 3-1  September 2001 
Section 3  Operating Instructions 
3-1  Introduction 
This section contains operating instructions for the Multicarrier Cellular Amplifier System. 
3-2  Location And Function Of Amplifier Module Controls And Indicators 
Primary +27 Vdc power is applied to the amplifier via a 100-amp circuit breaker (ON-OFF) lo-
cated on the left side of the amplifier front panel. 
The plug-in amplifier module RF control and indicators, located in the center of the amplifier front 
panel between the cooling fans, are shown in figure 3-1.  The status and RF control functions and 
alarms are described in detail in the subsequent paragraphs. 
Figure 3-1   G3S-800-140-031 Amplifier Module RF Control and Indicators 
3-2.1   Voltage Indicators And On/Off/Reset Switch 
3-2.1.1   +27VDC Indicator  
Green LED.  When lit, indicates that the +27 Vdc supply is greater than +21 Vdc and less than 
+31 Vdc.  If the +27 Vdc indicator goes out, the DC FAIL indicator will illuminate.  This indicates 
that the +27 Vdc voltage dropped below +21 Vdc. 
3-2.1.2   +15VDC Indicator  
Green LED.  When lit, indicates that the +15 Vdc supply is greater than +12 Vdc and less than 
+17 Vdc.  If the +15 Vdc indicator goes out, the DC FAIL indicator will illuminate.  This indicates 
that the +15 Vdc voltage dropped below +12 Vdc or increased above +17 Vdc. 

 G3S-800-140-031 Installation & Service Manual 
 Copyright Powerwave Technologies, Inc., September 2001. All rights reserved 
044-05095 Rev. A 3-2  September 2001 
3-2.1.3   +5VDC Indicator 
Green LED.  When lit, indicates that the +5 Vdc supply is greater than +2 Vdc and less than +7 
Vdc.  If the +5 Vdc indicator goes out, the DC FAIL indicator will illuminate.  This indicates that 
the +5 Vdc voltage dropped below +2 Vdc or increased above +7 Vdc. 
3-2.1.4   -5VDC Indicator 
Green LED.  When lit, indicates that the -5 Vdc supply is greater than -7 Vdc and less than -2 
Vdc.  If the -5 Vdc indicator goes out, the DC FAIL indicator will illuminate.  This indicates that the 
-5 Vdc voltage dropped below -7 Vdc or increased above  -2 Vdc. 
3-2.1.5   RF ON Switch 
Three position switch: 
Off (down position) - Turns off amplifier module. 
On (center position) - Normal amplifier on position. 
Reset (up position) - When toggled to reset position, all the red LED indicators will turn on 
one at a time in sequence followed by all the green indicators one at a time in sequence; this 
will also reset the fault latches.  If the switch is held in the reset position, a microcontroller 
reset will occur.  This will be verified by the LEDs toggling state again. The switch is spring 
loaded to return to the normal ON position when released.  If a fault occurs and the MCPA is 
disabled, the alarms can be cleared and the MCPA enabled by this reset position.  The func-
tions of the switch are disabled for five seconds after a power-up condition. 
3-2.2   Alarm Indicators 
The alarm modes described here are indicative of amplifier alarm modes made to the amplifier 
subrack. The amplifier subrack interprets these alarms and may subsequently deliver a different 
alarm indication to the host equipment. Refer to the amplifier subrack manual to determine host 
equipment level alarms.  
Refer to section 6 to interpret and correct the various alarm states. 
Refer to table 3-1.  
A ‘Minor Alarm’ indicates a potential fatal amplifier problem via the amplifier front panel LEDs. 
and the MCPA fault will be in evaluation.  
A ‘Major Alarm’ indicates a major problem but the MCPA module will not be disabled. 
A ‘Critical Alarm’ is indicative of a fatal problem.  The fault indicator will latch on and the MCPA 
module will be disabled.  
Both ‘Major Alarm’ and ‘Critical Alarm’ will be sent to the host system via the MCPA subrack. 

 G3S-800-140-031 Installation & Service Manual 
 Copyright Powerwave Technologies, Inc., September 2001. All rights reserved 
044-05095 Rev. A 3-3  September 2001 
Table 3-1   Amplifier Module Alarm Indicators Definition 
Alarm Mode LED 
MCPA 
Module
MCPA 
Disable signal 
(pin 4 inTable 2-1)
Condition 
Over Pwr  Critical  Red  Disable High  MCPA module output power >200 
watts (Note 4) 
Over Pwr  Critical  Red  Disable High  Input power >-2 dBm 
High Temp  Minor  Red  Enable  Low  High temperature detected 
High Temp  Critical  Red  Disable High  High temperature detected for longer 
than two minutes 
VSWR  Minor  Red  Enable  Low  14.5 W < Reflected Power < 38W 
VSWR Critical Red Disable High  60W < Reflected power detected at 
output longer than approx. two min. 
DC Fail  Minor  Red  Enable  Low 
One of the internal DC voltages 
dropped below or exceeded the safe 
threshold level 
DC Fail  Critical  Red  Disable High  Voltage out of range for longer than 
approx. two minutes (Note 2) 
DC Fail 
(Over  
voltage) 
Critical Red Disable High 
+27 Vdc input >30 V for longer than 
one sec. after initial detection of DC 
input >31 V (Note 3) 
Fan Fail 
(one)  Major  Red  Enable  Low  Any fan failure 
Loop Fail  Minor  Red  Enable  Low  Loop failure detected 
Loop Fail  Critical  Red  Disable High  Loop failure detected longer than 2 
minutes 
Low Pwr  Minor  Red  Enable  Low 
Rack controller detected MCPA out-
put is 3 dB below that of the other 
MCPA in the system. 
Low Pwr  Critical  Red  Disable High 
Rack controller detected low power 
condition for more than approx. two 
minutes 
LPA 
DISAB.  Critical Red Disable High 
Unit is manually switched off using 
the front panel RF ON switch, or dis-
abled by a serial command or auto 
shutdown by an alarm condition. 
NOTES: 
1.  RS-485 serial alarm will follow LED status. 
2.  The appropriate status LED shall turn off indicating which voltage is out of its range. 
3.  When overvoltage is detected: 
a)  MCPA shall shut down (disable) 
b)  Turn on red DC Fail LED 
c)  Set flag for DC Fail alarm 
4.  When overpower is detected: 
a)  MCPA shall shut down (disable) 
b)  Turn on Over Pwr LED 
c)  Set flag for Over Pwr alarm 
d)  The MCPA module shall use a peak power detector to determine the overpower 
fault. 

 G3S-800-140-031 Installation & Service Manual 
 Copyright Powerwave Technologies, Inc., September 2001. All rights reserved 
044-05095 Rev. A 3-4  September 2001 
3-3  Initial Start-Up And Operating Procedures 
The amplifier module has two operating controls, both located on the front face of the module: the 
power ON - OFF switch and the RF ON - ON/OFF/RESET switch (refer to figures 1-1 and 3-1).  
To perform the initial start-up, proceed as follows: 
1.  Verify that all input and output cables are properly connected. 
CAUTION 
Before applying power, make sure that the input and output of the amplifier are prop-
erly terminated at 50 ohms.  Do not operate the amplifier without a load attached.  
Refer to table 1-2 for input power requirements.  Excessive input power may damage 
the amplifier 
WARNING 
Ensure the amplifier is turned off while disconnecting and reconnecting cables be-
tween the antenna interface and power measurement equipment.  Failure to do so may 
cause damage to the equipment or personal injury. 
NOTE 
The output coaxial cable between the amplifier and the antenna must be 50 ohm co-
axial cable.  Use of any other cable will distort the output. 
2.  Verify that the amplifier front panel switches are in the OFF position. 
3.  Turn on supply that provides +27 Vdc to the amplifier system.  Do not apply an RF signal to 
the amplifier system 
4.  Place the ON - OFF circuit breaker on the amplifier in the ON position.  Visually check the 
indicators on the amplifier module, and verify that the following indicators are on: 
A.  LPA DISAB. indicator (red) should be on. 
B.  The +27VDC, +15VDC, +5VDC and -5VDC indicators (green) on the amplifier module 
should be on. 
5.  Set the RF ON switch to the ON (center) position.  All red LEDs should turn off after six sec-
onds. 
6.  Follow the power setting procedure set forth in the amplifier subrack or system integration 
manual. Turn on external exciter/transceiver and apply RF input signals.