Shinko Electric Co 199909010001 Communication Modem Controller User Manual Power Supply Operation Manual
Shinko Electric Co Ltd Communication Modem Controller Power Supply Operation Manual
Contents
Power Supply Operation Manual
1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM OPERATING MANUAL POWER SUPPLY MODEL: IEC-91-1 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM Preliminary ISSUED ON:1999.8.10 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM SHINKO ELECTRIC CO.,LTD ENGINEERING DEPARTMENT CONTENTS SECTION 1. INTRODUCTION SECTION 2. SPECIFICATIONS AND RATING 2-1 BASIC SPECIFICATIONS 2-2 ELECTRIC SPECIFICATIONS A. INTERFACE SECTION 3. FUNCTION OF CONTROLS 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM SECTION 4. OPERATING 4-1 DISTRIBUTION PANEL UNIT 4-2 POWER SUPPLY UNIT 4-3COMMUNICATION MODEM CONNTROLLER UNI 4-4EMERGENCY STOP A. MONITOR SECTION 5.TROUBLESHOOTING TABLE-1 TROUBLESHOOTING SECTION 6. SPARE PARTS LIST TABLE-2 SPARE PARTS LIST SECTION 7. BLOCK DIAGRAM FIG-1 BLOCK DIAGRAM 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM NOTICE SECTION 1. INTRODUCTION SHINKO OHT SYSTEM is constructed from Vehicle, Track, Maintenance Lifter, OHVC, Power Supply and etc. This Power Supply has the following part. 1) Supply of electric power to Vehicle It generates alternating current of 8.66KHz, 50A. It supplies electric power to Vehicle. 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM 2) Communication Modem Controller between Vehicle and OHVC 3) Receive and supply of electric power It receives electric power of 208 V of 3 phases. It supplies electric power to devices of the system. SECTION 2. SPECIFICATIONS and RATINGS 2-1 Basic specifications Operating Temperature Ranges:1040 Storage Temperature Ranges:050 Humidity3090RH CoolingAir cooling Weight400Kg Dimensions1000W*500D*2150H Paint colorWhite Mansel N9 Coating with paint 2-2 Electric specifications 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM 1) Distribution Panel Unit Input Capacity9KVA Phase 3-phase Voltage208V10% Frequency60Hz OutputMaintenance Lifter Capacity600W Phase 3-phase Voltage208V10% Frequency60Hz OutputOHVC Capacity600W Phase 1-phase Voltage120V10% Frequency60Hz 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM Power Supply Unit Capacity6KW Phase 3-phase Voltage208V10% Frequency60Hz 2) Power Supply Unit Output Capacity5KW Phase1-phase Voltage360440V Current50A Frequency8.66KHz CMC Frequency of communicationtransmit 300KHzcentral frequency receive 350KHzcentral frequency 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM CommunicationRS-422 A. Interface 1)Power-input of Distribution Panel Circuit Breaker MCB11 L1 L2 L3 GND 2) Power-output of Distribution Panelfor Maintenance Lifter Circuit Breaker MCB13 L12 L22 L32 GND 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM 3) Power-output of Distribution Panelfor OHVC Circuit Breaker MCB14 L13 L23 GND 4) Power-output of Power Supply Terminal Block TB21 GND 5) Connection with OHVC Terminal Block TB22 10 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM RTS+ RTSTXD+ TXDFG RXD+ RXDCTS+ CTC- 6)Emergency Stop Terminal Block TB11 EM1 EM2 11 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM SECTION 3. FUNCTION OF CONTROLS Control PanelInside Panel 12 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM 13 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM A. Handle Distribution Panel (with Key) B. Lamp (white) PL11Input Power C. Lamp (green) PL12Power ON D. Switch (green) PB11ON E. Switch (red) PB12OFF F. HandlePower Supply Unit (with Key) 14 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM G. Lamp (white) PL1Input Power H. Lamp (green) PL2Operation I. Lamp (yellow) PL3Over Voltage J. Lamp (yellow) PL4Over Current K. Lamp (yellow) PL5Over Heat L. Lamp (yellow) PL6Fan Alarm M. Switch (blue) PB3Reset N. Switch (red) PB4Emergency Stop O. Switch (green) PB1Start P. Switch (red) PB2Stop Q. Current Meter AOutput current R. Circuit Breaker MCB11Input power S. Magnetic Contactor MC11Operation T. Circuit Breaker MCB12Power supply of Power Supply Unit U. Circuit Breaker MCB13Power supply of Maintenance Lifter V. Circuit Breaker MCB14Power supply of OHVC 15 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM W. Circuit Breaker MCB1Input power of Power Supply Unit X. Magnetic Contactor MC1Operation SECTION 4. OPERATION 16 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM Before this operation, it supposes that the installation of the equipment, the wiring and the early adjustment have completed. 4-1Switch Panel Unit 1)Open the door of Distribution Panel Unit. Turn on Circuit Breakers (T)(U)(V). 2)Close the door of Distribution Panel Unit. Make Handle (A) the position of ON . Circuit Breaker (R) becomes ON with the handle. Lamp (B) lights up. 3) Push Power Switch (D). Magnet Contactor(S) turns on. Lamp (C) lights up. 4) Push Power Switch (E). Magnet Contactor(S) turns off. Lamp (C) put out. 5) In case of work ending, make the Handle(A) OFF position. All power supplies become OFF. 17 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM 4-2Power Supply Unit 1) Open the door of Power Supply Unit . Turn on Circuit Breaker (W). 2)Turn on Circuit Breakers(R)(T)(U)(V). Lamp (G) lights up. 3)Push Start Switch (O). The output current flows and the ammeter indication displays about 50 A. Operation Lamp (H) lights up. 4)Push Stop Switch (P). The output current stops and the ammeter indication displays 0 A. Lamp (G) put out. 4-3 CMC Unit It is no adjustment and no operation. 4-4 Emergency Stop 1) Push EMO Switch (N). All power supplies of each equipment put off. 2) Make return EMO Switch (N). Magnet Contactor (S) is OFF. 18 1)When either of alarm lamps (I)(J)(K)(L) lights up, it stops output current. 2)Remedy the cause. 3)Push Reset Switch (M). The lighting alarm lamp put off. 4) Push Start Switch (O). Again, the output current flows. SECTION5. TROUBLESHOOTING Table-1 TROUBLESHOOTING SECTION6. SPARE PARTS LIST Table-2 SPARE PARTS LIST SECTION7. BLOCK DIAGRAM A. 19 3) Push Power Switch (D). Again, power is supplied to each equipment. Alarm lamps
Source Exif Data:
File Type : PDF File Type Extension : pdf MIME Type : application/pdf PDF Version : 1.2 Linearized : Yes Create Date : 2001:05:27 14:54:21 Producer : Acrobat Distiller 4.0 for Windows Modify Date : 2001:05:27 14:54:22-04:00 Page Count : 19EXIF Metadata provided by EXIF.tools